Samon GD Instructions Manual Download Page 5

 GD/GS/GSR/GR/GK-24/230

 

IS Atos 1004.doc 

 

 

GB 

 
FUNCTION 

When power supply is switched on, a green LED will flash to 
indicate power ”ON”. This will also start the heating process of 
the sensor. After approximately 4 minutes the green LED will 
light and indicate ”Sensor Active”. 
The detector has one yellow and two red LEDs. The yellow LED 
indicates low gas concentration 

(Alarm C) 

and the red LEDs 

indicate medium gas concentration 

(Alarm B) 

and high gas 

concentration 

(Alarm A)

When gas is detected the LEDs 

(2)

  will light and the relay 

corresponding to the alarm level will change state. If alarm 
delay is chosen (see below) the respective LED will flash and it 
will light (and the relay will change state) when the chosen 
delay time is exceeded. 
 

AUTOMATIC/MANUAL RESET  

Is managed by DIP switch 

(1)

 n

o

 3 where “on” means automatic 

reset and “off” means manual reset by pressing the “Reset/Test/ 
Service”-button (located under the cover). 
 

ALARM TIME DELAY (T1) 

Is managed by DIP-switches 

(1)

 n

o

1 and n

o

2: 

n

o

1  

n

o

on  

on  

No alarm delay 

off 

on  

(1) minutes alarm delay 

on 

off 

(10) minutes alarm delay 

off  

off  

(30) minutes alarm delay 

 

FAIL SAFE 

Relays are in normal mode energized and will change state if 
power failure or if a fault situation occurs. 
 

SELF TEST FUNCTION  

Press the “Reset/Test/Service”-button 

(5)

 for 5 seconds and the 

test program will start and go through all LED functions and all 
relay functions in five seconds intervals. 
 

FAULT FUNCTION 

If there is a voltage drop (GV-value below 0,1V) from the sensor 
there is a fault situation. During the first four hours the green 
LED will go out and the other LED’s will flash. Alarm relay C will 
change state. 
After four hours the LED “Alarm B” will light (other LED’s will go 
off) and relay “Alarm B” will also change state. 

 

 

 

 
SERVICE FUNCTION 

 

Pressing the ”Reset/Test/Service” button 

(5)

 for 10 seconds will 

lock all alarm functions for 60 minutes. During this period it is 
always possible to start a new 60-minutes period by pressing the 
button for 10 seconds again. Return to active status is automatic 
at the end of the 60-minutes period or may be done manually by a 
single press on the “Reset/Test/Service”-button. When the service 
function is activated all LED’s will flash and all relays will be in 
normal mode position. 
 

INSTALLATION 

Connect the detector according to the wiring diagram. 
 

CALIBRATION 

The detectors are delivered for a specific gas type and other 
calibrations are normally not necessary. The detector is named 
with the required gas type being detected. It is, however, very 
easy to change the thresholds by using a service adapter. 
SA200 is connected at the test terminal. 

(3)

 

 

ANNUAL FUNCTION CONTROL 

Testing the system is recommended to be done at least twice a 
year. A basic function test can be made using a service tool 
(SA200) and a voltage meter. 
Extended control and calibration requires also test gas with a 
specific concentration. 
Contact us for more information. 
 

TECHNICAL DATA 

Housing:  

Polycarbonate, PC 

Power supply: 

230 V AC, 50/60 Hz (model Gx230-XX) 

 

12-24V AC/DC (model Gx24-XX) 

Power consumption: 

Max 2W 

Indications:  

Power/Active and alarm indication on 
three levels. 

Outputs relay:  

Potential free contacts (230V, max 5A) . 

Ambient temp: 

-40

0

C - + 50

0

C (Automatic temperature 

 compensation) 

Humidity: 

0-95% Rh (non condensing) 

Glands: 

4 of M16 membrane glands 

Screw terminals: 

< 1,5 mm2, fuse < 10A 

 
 
NOTE! High voltage under lid! 
The unit must only be opened by authorised personnel! 
 

 
 

Please Note! 
The sensors used in the GD/GS/GR/GK/GSR range of products 
are not gas specific. Care should be taken when installing the 
equipment to minimize any cross contamination from other gases 
or vapours.  
For further guidance on specific applications contact us.

 

 
 
Specifications subject to change. 
 
 
 

n 4  not used

 

n 1 

n 2 

n 3  ALARM RESET: ON=AUTO, OFF=MANUELL

ON

 

A

 

RESET/TEST

TEST TERMINAL

C

 

B

 

LED A

LED B

LED C

POWER 

ALARM A
ALARM B
ALARM C
(-)

 

+ 5VDC
GV OFFSET

Summary of Contents for GD

Page 1: ...GD GS GSR GR GK 24 230 IS Atos 1004 doc 1 SE Instruktioner GB Instructions D Anleitungen ES Instrucciones FR Instructions...

Page 2: ...GD GS GSR GR GK 24 230 IS Atos 1004 doc 2 Placering Location Montageort Localizaci n Emplacement...

Page 3: ...rd EN 61 000 6 2 2001 EN 61 000 6 3 2001 EN 61 000 3 2 2001 EN 61 000 3 3 1995 EN 61 010 1 2001 GB This product is in conformity with the directive LVD 2006 95 EC EMC 2004 95 EC It fulfils the require...

Page 4: ...rst llning Test Service knappen 5 blockeras alla larmfunktioner under 60 minuter N r som helst kan en ny 60 minuts period startas genom ett nytt tio sekunders tryck p knappen terg ng sker automatiskt...

Page 5: ...ock all alarm functions for 60 minutes During this period it is always possible to start a new 60 minutes period by pressing the button for 10 seconds again Return to active status is automatic at the...

Page 6: ...ges Bet tigen der Taste eine neue 60 Minuten Periode zu starten Die R ckkehr in den aktiven Zustand erfolgt automatisch am ende der 60 Minuten Periode oder l sst sich durch einmaliges Bet tigen der Re...

Page 7: ...odas las funciones de alarma durante 60 minutos Durante este periodo siempre ser posible iniciar un nuevo periodo de 60 segundos pulsando de nuevo el bot n durante 10 segundos Al final del periodo de...

Page 8: ...0 secondes pour verrouiller toutes les fonctions d alarme pendant 60 minutes Durant cette p riode il est toujours possible de lancer une nouvelle p riode de 60 minutes en appuyant une nouvelle fois su...

Reviews: