                                    TROUBLESHOOTING

SYMPTOMS WHEN THE CHARGER IS POWERED AND CONNECTED TO 
THE  BATTERY 

THE RED LED IS OFF 

The DC side fuse may have blown due to wrong polarity of battery connection. Ensure 
positive of the battery is connected to the positive of the charger and the negative of the 
battery is connected to the negative of the charger. Check the fuses inside the charger and 
replace, if blown. 

The battery may be shorted. In this condition, the unit is shut down by the short circuit 
protection circuit. Remove the battery connection. If the red LED now comes on, the battery 
is shorted. If the red LED still does not come on, check if there is AC power in the receptacle. 
If there is power, check the AC side fuse inside the unit. If the fuse is not blown, call 
Technical Support. 

THE RED LED IS ON BUT THE AMMETER SHOWS NO READING 

The battery is fully charged. If the battery is not fully charged, the connection to the battery
may be loose or open. Check tightness and continuity of the battery connection.

 

THE BATTERY IS GETTING OVER CHARGED OR BOILS 

The charger is also feeding other DC load(s) in parallel with the battery. The Dip Switch is not 
selected for “Battery with Load“. Change Dip Switch setting to “Battery under Load“ 
(see under “Powering other DC loads“ on page 10. 

SYMPTOMS WHEN THE CHARGER IS POWERED AND DIS-CONNECTED FROM 
THE BATTERY 

THE RED LED IS OFF 

Check there is AC power in the receptacle. If there is power,  check the AC side fuse inside 
the unit. If the fuse is not blown, check the DC side fuse. If the DC side fuse is not blown, 
the output may be shorted. In this condition, the charger is shut down by the short circuit 
protection circuit. Check that the output terminals are not shorted. If the terminals are not 
shorted , call Technical Support.

 

AC SIDE FUSE BLOWS AS SOON AS POWER IS TURNED ON 

The AC input of charger is 230VAC but the unit is plugged into 115 VAC.  Please check 
that when operation. If the AC input voltage is correct, the charger is defective.

DC SIDE FUSE BLOWS AS SOON AS THE BATTERY IS CONNECTED 

Wrong polarity of the battery connection. Ensure positive of the battery is connected to the 
positive of the charger and the negative of the battery is connected to the negative of 
the charger.

11

Summary of Contents for SEC - 1215E

Page 1: ...SEC 1215E SEC 1230E SEC 2415E Model No AUTOMATIC BATTERY CHARGER OWNER S MANUAL Please read this manual before operating your charger...

Page 2: ...IMPORTANT SAFETY PRECAUTIONS 2 DESCRIPTION AND FEATURES 3 CHARGING STAGES 4 PROTECTIONS 5 INSTALLATION 6 CHARGER OPERATION 7 8 9 10 TROUBLESHOOTING 11 12 INTERNAL FUSE RATINGS 12 SPECIFICATIONS 13 WAR...

Page 3: ...e compartment as batteries ChargerRelated r Do not operate the charger in a closed in area or restrict ventilation in any way Install in a well ventilated cool dry place r The charger must not be oper...

Page 4: ...rolled cooling fan SEC 1230E SEC 2415E r Protectionsagainst short circuit overcurrent reverse battery connection and over temperature over temperature for SEC 1230E and SEC 2415E r Can be used as a po...

Page 5: ...e threshold of battery gassing termed boost or absorption voltage the charger automatically switches over to Stage 2 Boost or Absorption Stage The value of this voltage depends upon the type of batter...

Page 6: ...draw a higher current than these limits the output voltage of the unit will start to drop The unit will automatically recover when the overload condition is removed Reverse Battery Connection Cut Off...

Page 7: ...1230E 6mm CAUTION For firm connection when using stranded cable crimp solder pin style terminal on the charger end of the DC cables used for connecting to the battery other DC loads Cables To avoid p...

Page 8: ...ng Always change the Dip Switch setting when the charger is off i e after disconnecting the charger from the AC input power NOTE The voltages are for a temperature of 80 Degrees F DIPSWITCH SETTINGS S...

Page 9: ...nsisting of more than one battery in parallel is to be charged make sure that their negatives are connected to the common negative terminal of the charger and their positives are connected to the same...

Page 10: ...frame or engine block which is away from battery Do not connect to carburetor fuel lines or sheet metal body parts 6 For a positive grounded vehicle connect the negative black DC cable from the charge...

Page 11: ...current drawn by the DC load is below the maximum current rating of the charger Switch on the charger and then the DC load In a DC UPS Un interruptible Power Supply the charger simultaneously powers t...

Page 12: ...S GETTING OVER CHARGED OR BOILS The charger is also feeding other DC load s in parallel with the battery The Dip Switch is not selected for Battery with Load Change Dip Switch setting to Battery under...

Page 13: ...y reach up to 10 times their normal operating currents Ensure that the starting in rush current or the maximum operating current of the load is lower than the current limit value of the charger INTERN...

Page 14: ...1 13 8 VDC 13 8 VDC 27 6 VDC Output Amps 15 A 30 A 15 A Operating Temp Range 0 40 C 0 40 C 0 40 C Weight 2 35 kgs 3 1 kgs 3 1 kgs Housing Dimensions LXWXH mms 215x213x80 273x213x80 273x213x80 Protect...

Page 15: ...rmed only by the Warrantor Any attempt to remedy the defect by anyone other than the Warrantor shall render this warranty void There shall be no warranty for defects or damages caused by faulty instal...

Page 16: ...www samlex com www samlex solar com...

Reviews: