21
English
Parameters
Range of value
Default value
Description
Type of power supply
Mains
Mains
Type of power supply used for dry-run-
ning detection optimization
Variable speed
inverter
Defect post when :
Setting
If yes, dry-contact relay is set when
defect occurred and ‘other defect’ indica-
tor is turned ON
• Low speed
Yes
No
See « Maximum speed » parameter
No
• Direction of rotation
Yes
Yes
No
• X-care temperature
Yes
Yes
Defect occurred when X-care internal
temperature exceeds 70°C
No
• Over-pressure
Yes
Yes
See « Maximum head » parameter
No
• Ambient temperature
sensor disconnected
Yes
Yes
No
CAN bus address
OFF
OFF
When OFF, CAN bus is inactive
1 to 64
Maximum head
0 to P max.
(16 or 25bar)
P max.
(16 or 25bar)
Over-pressure threshold
Maximum speed
0 to V max
0
Low-speed threshold used to detect
some abnormal operating conditions
- Example of one wiring diagram .
L1
L2
L3
N
PE
Q1
SSM
KM1
N
L
X-Care
M
3~
U
V
W
KM1
8. Start up
8.1 Configuration settings
• X-care is configured in factory with a set of default value,
ready for use.
• List of available parameters and default values.
POMPES SALMSON SAS 12/2012