6. Maintenance, warranty and
service.
6.1.
Basic maintenance guide.
The main guidelines for a correct maintenance are similar to the
ones that are applying our Service and Technical Support in the
Preventive maintenance modality (see section 6.5).
6.2. Battery maintenance.
•
Pay attention to the safety instructions regarding battery and
the stated in section 1.2.3.3.
•
The SPS from SOHO+ series only requires a minimum main-
tenance. The used battery in the standard models is lead
acid, sealed, VRLA and maintenance free. These models
require a minimum of reparations. The only requirement
is to charge the SPS regularly, in order to prolong the bat-
tery lifetime. Meanwhile, it is connected to the power supply,
never mind if the SPS is ON or OFF, it will keep the batteries
charged and will give protection against overcharging and
undercharging.
•
The SPS has to be charged once, every 4 or 6 months if it
has not been used for long time.
•
In hot areas, battery has to be charged every 2 months. The
charging time has to be 12 hours as minimum.
•
Under normal conditions, the battery lifetime is from 3 to 5
years 25º C. In case that the battery was not in good condi-
tions, it has to be replaced before. This replacement has to
be done by qualified staff.
•
Always replace them with the same quantity and type.
•
Do not replace one battery only. All batteries have to be re-
placed at the same time and following the instructions of the
manufacturer.
•
Usually, the batteries should be charged and discharged
every 4 or 6 months. The charging would be started after shut-
down the SPS due to a low battery (discharging). Charging
time for standard SPS should be 12 hours as minimum.
6.2.1. Notes for installing and replacing the
batteries.
•
If it is needed to replace the connection of any wire, purchase
original parts through authorised distributors or service cen-
tres in order to avoid overheating and sparks with fire risk
because the size is not enough.
•
Do not short the + and - poles of the batteries, there is risk of
fire or electrocution.
•
Be sure that there is no voltage before touching the batteries.
Battery circuit is not isolated from the input. Hazardous volt-
ages can be found between the battery and earth terminals
•
Although the input circuit breaker the switchgear panel is
turned off, the internal parts of the SPS are still connected to
the batteries, so there are hazardous voltages inside.
Therefore, before doing any reparation or maintenance task,
the internal battery fuses have to be removed and/or the in-
terlink connections between them and the SPS.
•
Batteries have hazardous voltages. The battery maintenance
and replacement have to be done by qualified personnel and
familiarised with them. Nobody else can manipulate them.
6.3. SPS troubleshooting guide.
If the SPS doesn’t work properly, check the information given by
the LCD of the control panel. Try to solve the problem by means
of the established steps in the table 3. In case the problem per-
sists, consult with our Service and Technical Support S.T.S..
When it is needed to contact with our Service and Technical Sup-
port S.T.S. , provide the following information:
•
SPS model and serial number.
•
Date when the problem occurred.
•
Complete description of the problem, including the informa-
tion given by the LCD panel and the status of the alarms.
•
Power supply condition, type of load and the level connected
to the SPS, ambient temperature, cooling conditions.
•
Other informations that you may think that they are important.
Symptom
Possible Cause
Remedy
LCD display is not
illuminated
1. Unloaded battery.
1. Charge battery up to
8 hours.
2. Battery defect.
2. Replace with the
same type of battery.
3.When the Input cord
isn’t electrified and
Power switch is not
pressed.
3. Press the power
switch again or test the
Input cord.
Alarm buzzer beeps
continuously when AC
supply is normal.
Overload of the UPS.
Verify that the load
matches the UPS
capability specified in
the specs.
When power failure,
back-up time is
shorten.
1. Overload of the UPS.
1. Remove some
noncritical load.
2. Battery voltage is
too low.
2. Charge battery 8
hours or more.
3. Battery defect due
to high temperature
operation environment,
or improper operation to
battery.
3. Replace with the
same type of battery.
Communication lost
between UPS and
computer.
1. Software is not
installed well.
1. Check the setting of
the software .
2. Cable is not properly
connected.
2. Check the USB cable
is firmly connected
to the computer and
confirm the setting
again.
Mains normal but LCD
display Battery mode.
1. Circuit breaker
tripped.
1. Reset the circuit
breaker.
2. Power cord is loose.
2. Reconnect the power
cord properly.
Table 3.
SPS troubleshooting guide.
6.4. Warranty conditions.
The limited warranty only applies to those products that you ac-
quire for commercial or industrial use in the normal development
of your business.