41
Do not set the MBCB switches to ‘Off’ at this point.
Proceed as indicated in the previous points for all of the
units up to the highest number.
Verify that all of the static bypass switches are set to
‘On.’
Set the MBCB manual bypass switches on all of the
units to ‘Off.’
Following the instructions shown on the screen, move
the bypass selectors of all of the units to the NORMAL
position, starting with UPS number 1.
Attention.
When the OPEN ALL MBCB SWITCHES request
appears, the operator must set all of the MBCB switches
and/or those installed in outdoor cabinets to ‘Off.’
X-PERT
UNINTERRUPTIBLE POWER SUPPLIES (UPS)
USER MANUAL