45
7.4.5. Rated values menu.
User
Rated
Start
Batteries
Input / Output
Measurements
Alarms
Status & Ops
Ratings
Charts
Advanced
Rated Input voltage
Rated Input frequency
Rated output voltage
Rated output frequency
230 V
230 V
50 Hz
50 Hz
0/1
4-PM
S3.3
Configuration menu for the Rated Voltage and Frequency param-
eters.
•
Rated input voltage in volts.
•
Rated input frequency in Hz.
•
Rated output voltage in volts
•
Rated output frequency in Hz.
Measurements
Alarms
Status & Ops
Ratings
Charts
Advanced
User
Rated
Start
Input / Output
Batteries
Number of Batteries
Capacity (Ah)
Float / Fast cell / Cell
Charging current
40
24 Ah
2.25 V
1.75 V
1.65 V
0.2 x C
2.35 V
0/1
4-PM
S3.3
Configuration menu for the Rated Battery parameters:
•
Number of batteries in each half-bus, positive and negative
(40 = 20 + 20)
•
Battery charge current with respect to battery capacity
(If C = 24 Ah, Charge Current = 0.2 x 24 = 4.8 A)
•
Battery capacity in Ah.
•
Float Voltage per cell in Volts [Half-bus Float Voltage = 40
(batteries) / 2 (half-buses) x 6 (cells/battery) x 2.25 (V/cell)
= 270 Volts].
•
End of Backup Voltage at a discharge current of 0.15 x C
per cell in Volts [Half-bus EOD Voltage @ 0.15 x C = 40 (bat-
teries) / 2 (half-buses) x 6 (cells/battery) x 1.75 (V/cell) =
210 Volts].
•
End of Backup Voltage at a discharge current of 0.6 x C per
cell in Volts [Half-bus EOD Voltage @ 0.6 x C = 40 (batteries)
/ 2 (half-buses) x 6 (cells/battery) x 1.65 (V/cell) = 198 Volts].
•
Fast Charge Voltage per cell in Volts [Half-bus Fast Charge
Voltage = 40 (batteries) / 2 (half-buses) x 6 (cells/battery) x
2.35 (V/cell) = 282 Volts].
7.4.6. Charts menu.
User
Charts
Start
Measurements
Alarms
Status & Ops
Ratings
Advanced
Charts
Not available
0/1
4-PM
S3.3
Charts screen.
7.4.7. Advanced menu
Config. Power
Config Start
UPS Flags
PM Flags
Start menu
ON/OFF
0
User
Start
Measurements
Alarms
Status & Ops
Ratings
Advanced
Charts
0/1
4-PM
S3.3
Configuration menu for the Start Screen.
When the Config on Start button is pressed, a 1 appears in the
cell to the right. If the UPS is turned off under these conditions,
the next time it is turned on, the user will have to enter the Rated
Voltage and Frequency, Date and Time, and Language. Once
these parameters have been set, the value Config on Start will
be reset to zero.
SLC ADAPT 2
- UNINTERRUPTIBLE POWER SUPPLY SYSTEM
-
USER MANUAL