25
SALICRU
Alarm
Activation condition
Deactivation condition
Category
Delay(s)
Output voltage high alarm
1) Not exceptional charging:
For 125V
rated
, V
output
> 137.5 V
2) Exceptional charging:
For 125V
rated
, V
output
> 137.5 V
For 125V
rated
, V
output
> 1.05 x V
excep.
Manual reset using the fast/exceptional
charging buttons.
Urgent, Vout Not OK
60
Low output voltage alarm
Vout < 106 V
Vbatt ≥ 110 V
Urgent, Vout Not OK
10
High battery voltage alarm
Vout > 139.5 V
Vbatt ≥ 133.9 V
Urgent
30
Low battery voltage alarm
Vout < 116.3 V
Vbatt ≥ 121.0 V
Urgent
10
End of backup battery voltage alarm
Vbatt < 108.0 V
Vbatt ≥ 110.2 V
---
180
Battery disconnected alarm
Battery contactor open
or
Battery fuse blown
Battery contactor closed
and
Battery fuse not blown
---
5
AC input failure alarm
Vin < 0.80 x rated input voltage
Vin ≥ 0.84 x rated input voltage
AC failure
300
Input switch open alarm
Input switch open
Input switch closed
AC failure
10
RN or RS input undervoltage alarm
(6)
Vin RS < 0.90 x rated input voltage
Vin RS ≥ 0.94 x rated input voltage
AC failure
300
ST input undervoltage alarm
(6)
Vin ST < 0.90 x rated input voltage
Vin ST ≥ 0.94 x rated input voltage
AC failure
300
TR input undervoltage alarm
(6)
Vin TR < 0.90 x rated input voltage
Vin TR ≥ 0.94 x rated input voltage
AC failure
300
RN or RS input overvoltage alarm
(6)
Vin RS > 1.10 x rated input voltage
Vin RS ≤ 1.06 x rated input voltage
AC failure
30
ST input overvoltage alarm
(7)
Vin ST > 1.10 x rated input voltage
Vin ST ≤ 1.06 x rated input voltage
AC failure
30
TR input overvoltage alarm
(7)
Vin TR > 1.10 x rated input voltage
Vin TR ≤ 1.06 x rated input voltage
AC failure
30
Rectifier protection alarm open
Protection open (auxiliary contact open)
Protection closed (auxiliary contact closed)
Urgent
10
Batteries protection alarm open
Protection open (auxiliary contact open)
Protection closed (auxiliary contact closed)
Urgent
5
Current leakage alarm.
Isol res, approx. < 5 KΩ
Isol res, approx. > 5 KΩ
Not urgent
5
Electrolyte level low alarm
Electrolyte low level
Electrolyte normal level
Not urgent
1
Charger failure alarm
Abnormal rectifier operation due to internal
problem, input voltage high
(8)
, output voltage
high, heat Sink Temperature Alarm high for
more than 10min.
Manual reset using the fast/exceptional
charging buttons.
Urgent
30
Output switch open alarm
Output switch open
Output switch closed
----
5
Heat sink temperature high alarm
Ths > 85ºC
Ths ≤ 80ºC
----
1
Battery temperature high alarm
Tbatt > 45ºC
Tbatt ≤ 40ºC
----
5
Battery temperature low alarm
Tbatt < 0ºC
Tbatt > 0ºC
---
5
Battery temperature sensor failure
alarm
Tbatt < -10ºC
Tbatt > -10ºC
----
5
Phase rotation alarm
Connection of input phases incorrect.
Connection of input phases correct.
----
5
Battery high charging current alarm
Battery charging current at % with respect to
the rated is over:
I = HIGH BATT. CHARGING CURRENT
Battery charging current at % with respect
to the rated is below:
I = 0.9 x HIGH BATT. CHARGING
CURRENT
----
5
Rectifier overload alarm
The output current of the rectifier has
exceeded the percentage expressed in the
‘RECT. OVERLOAD’ parameter with respect
to the rated.
The output current of the rectifier is below
the percentage expressed in the parameter
(‘RECT OVERLOAD’ – 10%) with respect
to the maximum.
----
5
High reducer temperature alarm
Tdropper > 85ºC
Tdropper ≤ 80ºC for more than 10 minutes.
----
1
Diode reducer failure alarm
Reducer with a diode open.
Manual reset using the fast charging button.
----
35
Short circuit output alarm
Short circuit detected at the rectifier output
After 120 s an automatic reset is attempted
After 3 attempts, use manual reset with the
fast charging button.
----
1
(6)
For single-phase devices, the alarm corresponds to the voltage be-
tween the phase and the neutral (RN) and, for three-phase devices,
between the RS phases.
(7)
Alarms only available for three-phase devices (ST and TR phases).
(8)
Optional extra.
Table 7.
Alarm activation/deactivation conditions.