AHU WITH HEAT RECOVERY

Smarty 3X VER

Smarty 3X VEL

Smarty 3X VER 3.0

Smarty 3X VEL 3.0

User‘s and service technical manual

Summary of Contents for Smarty 3X VER

Page 1: ...Subject to technical modification AHU WITH HEAT RECOVERY Smarty 3X VER Smarty 3X VEL Smarty 3X VER 3 0 Smarty 3X VEL 3 0 User s and service technical manual...

Page 2: ...ter mode setting 24 10 Comfortable supply air temperature 25 11 Night cooling 25 12 Heat cool recovery 25 13 Fast button stand by mode 26 14 Filter timer 28 15 Boost fireplace function 29 16 Bypass da...

Page 3: ...s includes 1 Siphon 1 pcs 2 Key 1pcs 3 Anti vibration mounts 4 pcs 4 Anti vibration rubber 2 pcs 5 Mounting bracket 1 pcs 200003025238 IV PV KE PE M 0 084 kW 0 92 A 230 50 V Hz 1 0 085 kW 0 93 A 230 5...

Page 4: ...79 2013 Extract panel M5 WxHxD 435 x 175 x 25 mm Supply panel F7 WxHxD 435 x 175 x 25 mm Outdoor exploitation temperature 5 C to 40 C Not suitable for swimming pools saunas and other similar facilitie...

Page 5: ...onment Do not use the unit if external connections are broken or damaged If there are any defects stop operating the unit and replace the damaged parts immediately That can be performed only by qualif...

Page 6: ...for the life of the motor Detach fan from the unit Impeller should be specially checked for buil up material or dirt which may cause an imbalance Excessive imbalance can lead to accelerated wear on m...

Page 7: ...7 Smarty 3X VE Smarty 3X VE 3 0 www salda lt Smarty 3X VEL Smarty 3X VEL 3 0...

Page 8: ...to have been damaged in transit a claim should be made against carrier as we assume no responsibility for such damage 3 This warranty does not apply 3 1 when transportation storage installation and m...

Page 9: ...urrent kW A 0 3 1 3 control input ON OFF Pre heater EKA NIS phase voltage 1 230 power current kW A 1 0 4 3 control input 0 10 V Smarty 3X VER Smarty 3X VER 3 0 Smarty 3X VEL Smarty 3X VEL 3 0 Smarty 3...

Page 10: ...3X VE Smarty 3X VE 3 0 www salda lt 750 500 162 113 113 372 160 150 6 150 6 233 8 113 113 372 160 150 6 150 6 233 8 750 500 162 598 943 Smarty 3X VER Smarty 3X VER 3 0 598 943 Smarty 3X VEL Smarty 3X...

Page 11: ...evel of noise caused by the fans is admissible The installation is recommended at the distance of 400 mm from the nearest wall If it is not possible the installation of the unit is recommended on the...

Page 12: ...control panel technical manual Stretch the connection cable which is included into standard package between the control panel and control box The cable of the control panel can t be stretched togethe...

Page 13: ...twork connection place RS485_1 Control panel connection place PC Personal computer MBGateway Net module Flex Control panel Stouch Control panel M2 Fresh air damper actuator Recommended to use with ret...

Page 14: ...amper ZAKP0027 TF230 Spring return actuator for damper ZAKP0063 MPL Panel filter set GKOFILSMARTY3 FLEX Remote control panel PRGPU015 Stouch Remote control panel PRGPU051 S KCO2 CO2 sensor ZAKKT0049 E...

Page 15: ...the temperature reaches 3 C anti frost protection stars to work Pre heater EKA NIS for anti frost protection has to be ordered additionally The pre heater has overheat protection protection limiting t...

Page 16: ...heating or accidental oxygen burning The electrical supply air heater is controlled according to the PID controller on the basis of the on off control principle When the unit is switched off the heati...

Page 17: ...fan operation mode can be used where prompt indoor air changes are required at the increase of air pollution e g if the number of people in a room quickly increases The fan speed in this case is incre...

Page 18: ...u Additional Service password Vent Control off Where the CO2 transmitter is used by Stouch remote control In the remote control Flex select Menu Additional Service password Vent Control The parameter...

Page 19: ...xtra SAF Ctrl SAF low Where Stouch remote control is used all settings made by Flex remote control become inactive All settings of this function must be made by Stouch remote control Time can be confi...

Page 20: ...s supply and extract air it is necessary to use two pressure transmitters 1141 They are ordered individually Pressure transmitters are used only when connected by Flex remote control The use of forced...

Page 21: ...ding its proper connection Connection of a functional node to a ventilation unit To use this function the short circuiter must be removed from terminals 5 and 6 its installation is standard 5 6 PIR bu...

Page 22: ...Supply air actuator M3 phase L1 steady signal 20 Supply air actuator M3 phase L1 control variable signal Actuator supply voltage 230V 50Hz When the water cooler is used we recommend to connect the spr...

Page 23: ...F permit can be active by means of the unit shut down function Where the supply air temperature drops below 16 5 C the unit control automation records it as the minimum permissible supply air temperat...

Page 24: ...time meter is activated in the service menu Menu additional sevice FMisc Ftimer Function adjustment setting By FLEX remote control Menu Extra filters Set Timer service hours until the information mess...

Page 25: ...n the unit s technical decal on the unit casing The unit must be connected to the voltage plug socket of the grounded power network in compliance with the effective requirements The unit must be earth...

Page 26: ...tretching The standard length of the unit s power cable is 2 5 m long from the unit casing The supply air sensor SS must be installed as far from the unit as the sensor cable enables or to the first b...

Page 27: ...Fig 4 5 When the unit control automation must be extended from the automation compartment the limiting automation extension screw must be unscrewed and two connectors of the automation must be disconn...

Page 28: ...installed in the extract air duct Tool for drilling holes are required for its installation CO 2 concentration ppm 3000 Effect on an individual 2500 2000 Reduced concentration drowsi ness headache et...

Page 29: ...ation is stopped if the device has rotor heat exchanger In the remote controller temperatures the set and the measured are displayed as degrees Celsius C Room air temperature can be adjusted not only...

Page 30: ...of the FLEX description If water supply air heater is used and after HVAC unit is switched on fans are switched on after 20 seconds During this period water valve actuator is being opened to allow wat...

Page 31: ...perature sensor for supply air TJK 10K TE exhaust air damper actuator TJK 10K DTJ100 1 temp and humidity sensor for extract air PV supply air fan EC IV extract air fan EC FA fire alarm input B1 units...

Page 32: ...System alarm 1 2W max 4 5 6 10 9 X16 4 24 1 2W max System on 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 GND Transmitter 1 24 VDC P 23 X29 X25 N L 3 1 P DX Cooling A 0 10 COM 14 11 G M5 24VAC...

Page 33: ...System alarm 1 2W max 4 5 6 10 9 X16 4 24 1 2W max System on 11 12 COM FAN 25 24 23 24V DC 24 intput 0 10V DC 25 GND Transmitter 1 24 VDC P 23 X29 X25 N L 3 1 P DX Cooling A 0 10 COM 14 11 G M5 24VAC...

Page 34: ...5 3 2 NO 1 COM 6 7 8 L X31 X33 15 X33 16 COM A 0 10 X41 1 X41 2 X39 2 X39 1 X38 1 X38 2 X40 3 X40 2 X40 1 X34 8 X34 7 X34 6 X34 5 X34 4 X34 3 X34 2 X34 1 X33 26 X33 25 X33 17 X33 12 X33 18 X33 14 X33...

Page 35: ...5 3 2 NO 1 COM 6 7 8 L X31 X33 15 X33 16 COM A 0 10 X41 1 X41 2 X39 2 X39 1 X38 1 X38 2 X40 3 X40 2 X40 1 X34 8 X34 7 X34 6 X34 5 X34 4 X34 3 X34 2 X34 1 X33 26 X33 25 X33 17 X33 12 X33 18 X33 14 X33...

Page 36: ...l applicable safety and functional requirements diameters etc earthing and protection systems are properly installed condition of all seals and sealing surfaces is proper The recuperator can be connec...

Page 37: ...ir temperature set 0 30 17 RH_value 04h_Read_Input 13 1 DTJ 100 humidity sensor value 0 99 18 Motor1 04h_Read_Input 15 1 Motor1 fan speed value 0 3 19 Motor2 04h_Read_Input 16 1 Motor2 fan speed value...

Page 38: ...temperature limit day T is exceeded for the working unit and when temperature drops below Night T and the room temperature stays above Room T after switching the unit off 8 1 Day T 15 40 C maximum ou...

Page 39: ...pply fan speed deceleration On allowed Off forbidden 15 3 Bypp Rot On Off on activation of anti frost protection On possible to open the bypass valve o to stop the rotor Off impossible to open bypass...

Page 40: ...vel is exceeded the information message High CO2 level is displayed at the initial screen and the speed of fans is increased based on the amount at which allowable level is exceeded 5 In case of any f...

Page 41: ...selected Bypass 0 10 Not used Cooling X16 4 X16 8 NO contact closed non voltage X16 1 X16 3 Activated by remote control V LED4 atidaroma X16 2 X16 3 Deactivated by remote control LED5 u daroma Heatin...

Page 42: ...Fire input A1 A1 Fire alarm activation Extract humidity X40 Extract air humidity sensor readings Supply air temp X39 Supply air temperature sensor failure Extract air temp X38 Extract air temperature...

Page 43: ...Always Seasons Exit Switch season Exit 3 days mean v Calendar Summer Winter Settings Exit Outdor air temp 0 C Summer 4MM 1DD Winter 11MM 1DD PI Kp 10 Ki 8 RoomPI Kp 100 Ki 10 HeatPI Kp 30 Ki 10 ChilP...

Page 44: ...imer On AX 1 FansOn On AF AF detect Toutside FanReduct Off Bypp Rot Off PassiveTC Off Exercise AF 1 OutDoorTemp 1 RotorPWM 20 DefrStpTime 30 PassiveTemp 3 CONF1 3dayRH mean 30 3dayRHCurr 54 3dayOUTCur...

Page 45: ...t EAF 1 SAF Ctrl SAF Low 0 3 SAF Midd 0 6 SAF High 1 EAF Ctrl EAF Low 0 3 EAF Midd 0 6 EAF High 1 SERVICE PI Kp 10 Ki 8 RoomPI Kp 100 Ki 10 HeatPI Kp 30 Ki 10 Byp RotPI Kp 10 Ki 10 ChilPI Kp 10 Ki 10...

Page 46: ...SAF High 100 VentCtrl SAF Percent EAF Percent CO2 Off Misc RC_NC Off F Timer On AX 0 FansOn On AF AF detect Klingb FanReduct On Bypp Rot On PassiveTC Off Exercise AF 1 RotorPWM 20 DefrStpTime 30 Passi...

Page 47: ...reccuperation Calculating main PID value between Tset and Tsupply to determinate what type of ventilation we need ByPass CLOSE ByPass OPEN ByPass OPEN Toutside Troom ByPass OPEN Cold reccuperation Tou...

Page 48: ...48 Smarty 3X VE Smarty 3X VE 3 0 www salda lt...

Page 49: ...50Hz delay of 3 minutes after stopping fans and heaters O 3A 100 X35 5 EXT L damper motor ON OFF 230V 50Hz O 3A 100 X3 RS485_2 ModBus I O X4 RS485_1 Remote controller FLEX I O X32 1 LOW Electrical hea...

Page 50: ...itter DTJ100 1 DTJ100 1 Relative humidity transmitter has a built in NTC10K temperature sensor TA 3250 3300K Relative humidity transmitter supply voltage 5VDC Used current not higher than 5 mA Output...

Page 51: ...inigung Once a year Einmal im Jahr Filter replacement Filter Ersatz Every 3 4 months 3 4 Alle 3 4 Monate NOTE The purchaser is required to fill in the Product maintenance table HINWEIS Der K ufer ist...

Page 52: ...52 Smarty 3X VE Smarty 3X VE 3 0 www salda lt...