7

RIS 150P EKO

AHU (1) is built on a foundation in a such way that the side of 

AHU (1) with drainage exhaust pipe (2) is lower 0° - 3° than the 
other side. The side of AHU with drainage pipe can not be higher 
than the other side. 

The  system  must  be  connected  with  pipes  (4)  in  such  order: 

AHU (1), siphon (3) and sewerage system. Pipes (4) should be 
bended  not  less  than  3°  (1  meter  of  pipe  must  be  bended  55 

mm downwards)! 

It is necessary to use funnel trap for a dripping condensate 

(Accessorie).

Draining  system  must  be  installed  in  the  premise  where  the 

temperature is not lower than 0°C. If temperature falls below 0°C 
the draining system should be isolated with thermal isolation or 
heating installed. 

The siphon (3) must be mounted below the AHU (1) level.

Das  WRG-Gerät  (1)  wird  so  montiert,  dass  die  Seitenwand 

des  WRG-Gerätes  (1)  mit  dem Auslassrohr  des  Kondensates 
(2)  mit  0  -  3  Grad  niedriger  als  die  andere  Seitenwand  steht. 
Die  Seitenwand  des  WRG-Gerätes  (1)  mit  dem  Auslassrohr 
des  Kondensates  darf  nicht  höher  als  die  andere  Seitenwand 
stehen! Dann die Rohre (Metall-, Plastik oder Gummirohre) (4) 
sowie in angegebener Reihenfolge das WRG-Gerät (1), Siphon 
(3) und das Abwassersystem zusammenschließen. Die Rohre 
(4) sollten mindestens mit einem Winkel von (3) Grad verlaufen 
(1 Meter es Rohrs sollte 55mm Gefälle haben). 

Es ist notwendig, Siphon für tropfende Kondensat zu ver-

wenden (Zubehör).

 

Das Ablaufsystem darf nur in Räumen be-

trieben werden, in welchen die Raumtemperatur nicht unter 0°C 
sinkt! Ansonsten muss das System mit thermisch isoliert werden.

Der Siphon (3) muss unterhalb des WRG-Gerätes (1) montiert 

werden.

Le récupérateur (1) est fi xé au sol de sorte que le côté du récu-

pérateur (1) avec l’embout (2) du vidangeur du condensat soit à 
un niveau 0-3 plus bas que l’autre côté. Le côté du récupérateur 
(1) avec l’embout du vidangeur du condensat ne peut pas être 
plus haut que l’autre côté !

- Connecter entre eux avec les tuyaux (4) (métalliques, en plas-

tique ou en caoutchouc) dans l’ordre indiqué : récupérateur (1), 
siphon  (3)  et  système  de  canalisation.  Les  tuyaux  (4)  doivent 
avoir  un  angle  d’inclinaison  d’au  moins  3  degrés  (un  mètre  de 
tuyau doit être incliné à 55 mm vers le bas).

Il est nécessaire d’utiliser un siphon avec une soupape de re-

tour (accessoire). 

Le  système  d’évacuation  du  condensat  doit  être  utilisé  dans 

des locaux, où la température ambiante ne peut être inférieure 
à 0°C ! Si la température ambiante peut descendre sous 0°C, il 
faut isoler le système avec une isolation thermique ou installer 
un chauffage.

Le siphon (3) doit se trouver plus bas que le récupérateur (1). 

L

N

N

N

L

L

NC

NO

C

N

1A

4

1. Pompe à eau
2. Activateur automatique de la pompe
3. Récupérateur
4. Brun
5. Bleu
6. Vert
7. Noir
8. Jaune
9. Rouge

1. Water pump
2. Automatic switch for water pump
3. AHU
4. Brown
5. Blue
6. Green
7. Black
8. Yellow
9. Red

1. Wasserpumpe
2. Automatische Schalter für Wasserpumpe
3. WRG-Ventilatoren
4. Brown
5. Blau
6. Grün
7. Schwarz
8. Gelb
9. Red

Summary of Contents for RIS 150P EKO

Page 1: ...erungen in Konstruktion und Design sind vorbehalten Subject to technical modi cation CENTRALES DE TRAITEMENT D AIR AVEC RECUPERATION DE CHALEUR AHU WITH HEAT RECOVERY L FTUNGSGER TE MIT W RMER CKGEWIN...

Page 2: ...ical data 5 Filters 5 Dimensions 6 Mounting 6 Draining 7 Components 7 Accessories 8 Electrical connection 8 Basic electrical connection scheme 8 Electrical connection scheme of external terminals 9 El...

Page 3: ...ndiqu sur l tiquette du produit coll e sur l enveloppe de la centrale Utiliser uniquement l interrupteur externe fusible automatique de surintensit appropri cf puissance et valeur du courant nominal i...

Page 4: ...dry up Wird einmal j hrlich gereinigt Einmal j hrlich reinigen Zuerst vorsichtig die Kassette des W rmetauschers heraus ziehen In eine Wanne mit warmem Seifenwasser tauchen und reinigen kein Sodawass...

Page 5: ...rmique Thermal ef ciency Thermischer Wirkungsgrad 93 Isolation des parois Insulation of walls Isolation der W nde 20 Poids Weight Gewicht kg 33 La soci t se r serve le droit de modi er les donn es tec...

Page 6: ...e mounted to the ceiling using mounting elements bolts screws and etc It is needed to keep 1 inclination in drainage direction picture below do not mount AHU in opposite direction It is recommended to...

Page 7: ...er wenden Zubeh r Das Ablaufsystem darf nur in R umen be trieben werden in welchen die Raumtemperatur nicht unter 0 C sinkt Ansonsten muss das System mit thermisch isoliert werden Der Siphon 3 muss un...

Page 8: ...ndensat IV exhaust air fan PV supply air fan PR plate heat exchanger PF lter for supply air class EU5 IF lter for extract air class EU5 IV ventilateur d extraction PV ventilateur de souf age PR change...

Page 9: ...U label 3 Power supply cable must be selected according AHU electri cal data 4 Automatic circuit breaker with minimum 3 mm contact gap must be installed Circuit breaker must be selected corresponding...

Page 10: ...tesse La premi re vitesse est chang e de 3V 6V la deuxi me vitesse de 6V 8V La troisi me vitesse est gale la tension d entr e 10VDC Si on value le fonctionnement du moteur en pourcentage 3V correspond...

Page 11: ...11 RIS 150P EKO...

Page 12: ...la turbine prenez le par le caisson While removing the fan do not hold it by the impeller hold it by the housing Beim Herausnehmen des Ventilators an seinem Laufrad nicht halten Nur Halten am Geh use...

Page 13: ...and similar electrical appliances Safety Part 1 General requirements LST EN 60335 2 40 1997 Safety of household and similar electrical appliances Part 2 Particular requirements for electrical heat pum...

Page 14: ...14 RIS 150P EKO F7 F7 G4 G4...

Page 15: ...15 RIS 150P EKO...

Page 16: ...es ltres Filter replacement Filter Ersatz Tous les 3 4 mois Every 3 4 months Alle 3 4 Monate NOTE L acheteur est tenu de remplir le Tableau de maintenance du produit NOTE The purchaser is required to...