4
| EN
KUB T120_KUB EKO v2019.04
WORKING CONDITIONS
It is prohibited to use the devices in potentially explosion hazardous environment.
The device is used to extract air (free from metal corroding chemicals; aggressive substances for zinc, plastic, rubber; hard, sticky and fibrous
particles) from the room.
Please note the maximum allowed ambient temperature (-40 +40)
.
The maximum temperature of transported air can not exceed 120
O
C.
TECHNICAL DATA
KUB T120
355-4L3
400-4L3
450-4L3
500-4L3
560-4L3
630-4L3
- Voltage/Frequency
[V/Hz]
~3,400/50
~3,400/50
~3,400/50
3,400/50
~3,400/50
~3,400/50
- power
[kW]
0,35
0,54
0,92
1,44
2,5
4,876
- current
[A]
1,06
1,38
2,13
3,08
5,04
8,9
- speed
[min
-1
]
1340
1390
1430
1430
1440
1440
- max. airflow
[m
3
/h]
2619
3976
5645
7404
10942
14200
- max. ambient temperature
[C
o
]
+40
+40
+40
+40
+40
+40
- min. ambient temperature
[C
o
]
-40
-40
-40
-40
-40
-40
- weight
[kg]
33
55
62
66
98
138
- motor protection class
IP-55
IP-55
IP-55
IP-55
IP-55
IP-55
- wiring diagram
#1 - #2
2
#1 - #2
2
#1
#1 - #2
2
#1 - #2
2
#3
1
Speed is controlled only with the frequency inverter. Motors sandard IE2.
2
The provided technical data is by using #1 el. connection scheme. Using #2 el. connection scheme, technical data will be different.
KUB EKO
100-630
50-355
67-400
67-500
80-560
80-630
- Voltage/Frequency
[V/Hz]
~1,230/50
~1,230/50
~3,400/50
~3,400/50
~3,400/50
~3,400/50
- power
[kW]
0,407
0,764
1,286
1,573
2,956
2,900
- current
[A]
1,93
3,46
2,04
2,45
4,55
4,48
- speed
[min
-1
]
2010
1700
1400
1230
1230
1230
- max. ambient temperature
[C
o
]
60
60
60
60
60
60
- min. ambient temperature
[C
o
]
-15
-15
-15
-15
-15
-15
- weight
[kg]
28
50
51
75
87
116
- motor protection class
IP-54
IP-54
IP-54
IP-54
IP-54
IP-54
- wiring diagram
#1
#2
#2
#2
#2
#2
** - Available as an accessory
ACCESSORIES
KUB T120
355-4L3
400-4L3
450-4L3
500-4L3
560-4L3
630-4L3