EIOM v2018.04
Control cabinet **
Check if the control cabinet is firmly installed on the device (when integrated externally).
Check if there are no signs of damage outside and inside the control cabinet. Electrical components
are not damaged and in place.
Check if there are no foreign objects, waste, moisture or water inside the cabinet. If yes, remove.
Check if the cables inside the control cabinet are connected in accordance with the basic connection
diagram.
Check if the main power supply cable meets the safety requirements and long term current load
capacity (A).
Check if main power supply cable is not damaged. Tightness and strength of the cable to the control
cabinet is ensured.
Check if control cabinet is grounded. Make sure ground wire is tightly connected and not loose.
Temperature and air quality sensors **
Check cable connectors.
Check if the sensors are connected in accordance with the basic connection diagram.
Check if the sensors are not mechanically damaged.
Check if the sensors are installed as intended (check labeling).
Check if the sensors are not covered and do not contact foreign objects, which could influence the
measurement.
Damper, valve actuators **
Check if there are no trapped foreign objects in the dampers. If yes, remove.
Check if the actuators are not mechanically damaged or deformed.
Check if the actuators are connected in accordance with the basic connection diagram.
Check cable connectors.
** - based on the unit type.