background image

• Affix the two spring clips 
on to the sensor body

• Wire the sensor as per 
the wiring diagram

• Lift the spring clips 
straight up   

• Push the sensor into the 
cut-out of the ceiling until 
the clips press the ceiling 
and hold the sensor tight

• Fix the surface 
mounting box onto the 
ceiling

• Wire the sensor as per 
the wiring diagram

• Clip the sensor body 
into the surface 
mounting box

• Twist and fit the front 
cover

4.2.2 Recessed mounting

36mm

93mm

93mm

72mm

28mm

4.2 Installation

4.2.1 Surface mounting

4.3 Wiring

The sensor is a 3-wire sensor that requires neutral wire, offering stable 
performance. 
Please wire as per the wiring diagram.

5.2 Key parameters: Brightness threshold and hold-time

The sensor has two key parameters that need to be set according to the appilication requirements: Brightness threshold and hold-time. They can be adjusted 
on the dials under the front cover: the dial with the word ‘LUX’ is for brightness threshold, and the dial with the word ‘TIME’ is for hold-time. They can also be 
adjusted in the App, after the sensor being added into the App.
Important: Being able to adjust both on the phone and on the physical dials, a new setup will overwrite the previous setup.

Brightness threshold

The  brightness  threshold  adjustment  makes  the  sensor  activate  the  load  depending  on  the  ambient  brightness  when  there  is  movement  detected  in  the 
detection range. The adjustment can be set to allow the sensor to activate the load all day (under full daylight) when movement is detected, or only to activate 
the load when the ambient brightness is below a certain level upon detection of movement. For example, the user can ensure the load is only activated when 
movement is detected at night time, while in the day time there is adequate natural daylight, the sensor does not respond to movements in the detection range 
to activate the load, as it is unlikely to be necessary for typical energy saving considerations.

Rotate the dial clockwise toward “sun” to increase the brightness threshold, when the adjustment is fully clockwise and the arrow is pointing at the “sun”, the 
motion sensor will activate the load upon detection of movement all day regardless of ambient brightness.  Rotate the dial anti-clockwise toward the “moon“ 
to decrease the  brightness threshold, when the adjustment is fully anti-clockwise and the arrow is pointing at the “moon”, the motion sensor only activates the 
load upon detection of movement in the dark.

Hold-time

The  hold-time  adjustment  varies  the  time  duration  that  the  load  will  remain  ON  when  it’s  actived  by  movement  detection.  The  load  will  automatically  be 
switched  off  when  the  hold-time  period  elapse  if  there  is  no  new  movements  detected  prior;  should  a  new  movement  be  detected  before  the  hold-time 
elapses, the load will remain ON, another duration of hold-time will be added from the time of detection.

Rotate the dial anti-clockwise toward “+” to increase the hold-time, when the adjustment is fully anti-clockwise, the hold-time setting is 30 minutes. Rotate the 
dial clockwise toward “-“ to decrease the hold-time setting, when the adjustment is fully clockwise, the hold-time setting is 10 seconds.

5. Operation and Function

5.1 LED indicator

• LED indicator is built in under the Fresnel lens, it lights up differently in response to different 
working status.
• There are three color LED indicators: white, blue, and green.
• LED indicator color is white when product is new or has been reset.
• LED indicator color can be blue or green after product is added to a network, depending on 
working status.
• The LED indicator can be turned off after the sensor being added to the App.

Cut-out: 72mm

10A Fuse or MCB

A

N

Load

Reviews: