- 4 - 

Do not use a circuit breaker to control the start and stop of the AC Drive. 

Otherwise, the AC Drive may be damaged. 

Since the AC Drive makes the motor running speed from low to high in a short 

time,  please  confirm  that  the  motor  and  equipment  are  in  the  allowed  running 
range before running. 

Do not touch due to high temperature of the heat sink and braking resistor. 

The  factory  parameters  of  the  AC  Drive  can  meet  the  requirments  of  most 

equipment operation. Under normal circumstances, please do not modify the AC 
Drive parameters at will. Even if there is some special applications need to change 
the  AC  Drive  parameters,  only  necessary  parameters  could  be  changed. 
Otherwise, AC Drive damage may be caused.   

The PCB board has a CMOS integrated circuit. Do not touch it with your hands, 

otherwise, static electricity will damage the PCB board.

 

 

DANGER

 

Wiring  must  be  completed  by  qualified  professional  electricians,  otherwise, 

there may be electric shock or damage to the AC Drive. 

The power must be disconnected during wiring; otherwise, it may cause electric 

shock or fire. 

The  grounding  terminal  should  be  effectively grounded;  otherwise,  the  outer 

casing of the AC Drive may be energized. 

Do not touch the main circuit terminals, otherwise, it may cause electric shock. 

Terminals  for  brake  resistor  are  (+)  and  PB.  Do  not  wire  to  other  terminals, 

otherwise, fire may be caused. 

It is only allowed to power on the AC Drive after the wiring is finished and its 

cover is reinstalled. It is strictly prohibited to remove the cover of AC Drive while 
power is on. Otherwise, it may cause electric shock. 

Before programming the AC Drive with fault auto reset or restart option after 

power off, the mechanical device need to be implemented with safety protection 
measures first. Otherwise, personal injury will be caused. 

Summary of Contents for VM1000B

Page 1: ...VM1000B 0 VM1000B AC Drive User Manual Version Code 6 0004 0391 00 VM1000B E V01 1908...

Page 2: ...items of this manual before using this product and to ensure that relevant electrical installation testers professional qualification shall be in line with the provisions of the labor supervision depa...

Page 3: ...3 DISPLAY AND OPERATION 19 3 1 KEYPAD 19 3 2 DESCRIPTION OF INDICATORS AND KEYS 20 CHAPTER 4 PARAMETER FUNCTION 21 4 1 FUNCTIONAL PARAMETER 21 4 2 FAULT RECORDS 46 4 3 MONITORING PARAMETERS 47 CHAPTER...

Page 4: ...nvironment Otherwise fire may be caused When AC Drive is installed inside an electrical cabinet or other kind of enclosure please install fans or other cooling devices and keep ventilation well enough...

Page 5: ...e static electricity will damage the PCB board DANGER Wiring must be completed by qualified professional electricians otherwise there may be electric shock or damage to the AC Drive The power must be...

Page 6: ...Never touch the AC Drive connection terminals when power is on Otherwise it may cause an electrical shock Only qualified electricians can be authorized to do the jobs of maintenance checking or parts...

Page 7: ...luctuation range 15 Input frequency range 50 60Hz fluctuation range 5 Output voltage range 0 input voltage the error is less than 5 Output frequency range SVC 0 320Hz V F 0 1000Hz Running control Runn...

Page 8: ...ripping due to overvoltage and overcurrent Rapid current limit It helps to avoid frequent overcurrent faults of the AC Drive Torque limit and control It can limit the torque automatically and prevent...

Page 9: ...re 10 40 When it is higher than 40 for every 1 it needs to reduce power by 1 and the maximum ambient temperature is 50 Humidity 95 RH without condensing Vibration Less than 5 9m s2 0 6g Storage temper...

Page 10: ...el description VM1000B 4 T 18R5GB 022PB E Field No Identification Description Product series Product series VM1000B general vector series Voltage grade Voltage grade 2 220VAC 4 380VAC The input power...

Page 11: ...10 VM1000B 4T011GB 015PB 11 15 17 21 26 35 25 32 11 15 15 20 VM1000B 4T015GB 18R5PB 15 18 5 21 24 35 38 5 32 37 15 18 5 20 25 VM1000B 4T18R5GB 022PB 18 5 22 24 30 38 5 46 37 45 18 5 22 25 30 VM1000B...

Page 12: ...rall Dimensions Mounting Hole Mounting Hole Diameter H W D D1 H1 W1 d VM1000B 2SR75GB 187 88 138 130 177 73 5 VM1000B 2S1R5GB VM1000B 2S2R2GB VM1000B 4TR75GB VM1000B 4T1R5GB VM1000B 4T2R2GB VM1000B 4T...

Page 13: ...82 211 196 331 156 6 VM1000B 4T015GB 18R5PB VM1000B 4T18R5GB 022PB 373 220 205 190 356 156 6 VM1000B 4T022GB 030PB VM1000B 4T030G 037P 435 256 222 208 419 170 6 VM1000B 4T037G 045P VM1000B 4T045G 055P...

Page 14: ...m Keypad size Unit mm Figure 2 2 1 0 75kW 7 5kW Keypad structure size Figure 2 2 2 11kW 110kW Keypad structure size Keypad bracket Unit mm Power range 0 75kW 7 5kW 11kW 110kW Hole size 69 98 5 85 121...

Page 15: ...wiring diagram Terminal mark Name Description R L S T N Power supply input terminals Connect to the AC power supply Positive and negative terminals of DC bus Common DC busbar input terminal Connect t...

Page 16: ...peed terminal 2 Reserved 1 5k T1C T1B T1A AO1 GND AO1 0 10V 0 20mA COM Digital output 1 RS RS AI2 0 20mA 0 10V PE RS485 communication terminal I AO1 V J1 I AI2 V J2 ON R 0FF J5 R Digital input termina...

Page 17: ...k T1C T1B T1A AO1 GND AO1 0 10V 0 20mA CME Digital output 1 NO RS RS AI2 0 20mA 0 10V PE RS485 communication terminal I AO1 V J1 I AI2 V J2 ON R 0FF J5 R Digital input terminal Analog input Communicat...

Page 18: ...k AI2 GND Analog input terminal 2 1 Input range 0 10V 4 20mA decided by jumper J8 on the control board 2 Input resistance 22 k voltage input 500 current input Digital input DI1 Digital input 1 1 Optic...

Page 19: ...minal Contact driving capacity AC 250V 3A COS 0 4 DC 30V 1A T1A T1C NC terminal T2A T2C NO terminal Communication port and socket RS RS485 signal positive terminal RS RS485 signal negative terminal Ta...

Page 20: ...apter 3 Display and operation 3 1 Keypad You can modify the parameters monitor the working status and start or stop the AC Drive by operating the keypad as shown in the following figure Figure 3 1 1 K...

Page 21: ...arameter setting Increment Increase date or function code Decrement Decrease data or function code Shift Select the displayed parameters in the stop or running state and select the digit to be modifie...

Page 22: ...ontrol LED on 2 Communication LED LED blinking 0 0001 F0 02 UP DOWN standard 0 Operating frequency 1 Setting frequency 1 0002 F0 03 Setting main frequency sourceX 0 Digital setting non retentive at po...

Page 23: ...000A F0 11 Source of frequency upper limit 0 Set by F0 12 1 AI1 2 AI2 3 Reserved 4 Reserved 5 Communication setting 0 000B F0 12 Frequency upper limit Frequency lower limit F0 14 F0 10 50 00Hz 000C F0...

Page 24: ...g mode 0 Start directly 1 Speed tracing andstart 2 Pre excitation start 0 0100 F1 01 Speed tracking mode 0 Start with the frequency of input power failure 1 Start at zero speed 2 Start at the maximum...

Page 25: ...0 1kW 400 0kW Model dependent 0201 F2 02 Motor rated voltage 1V 440V Model dependent 0202 F2 03 Motor rated current 0 01A 655 35A 55kW 0 1A 6553 5A 55kW Model dependent 0203 F2 04 Motor rated frequen...

Page 26: ...eed loop integral time 2 0 01s 10 00s 1 00s 0304 F3 05 Switchover frequency 2 F3 02 F0 10 10 00Hz 0305 F3 06 Slip compensation coefficient of vector control 50 200 100 0306 F3 07 Speed loop filter tim...

Page 27: ...ion 0 Invalid 1 Valid 0 0315 F4 Group control parameters F4 00 V F curve setting 0 Linear V F 1 Multi point V F 2 Square V F 3 9 Reserved 10 V F complete separation 11 V F half separation 0 0400 F4 01...

Page 28: ...REV 3 Three wire operationcontrol 4 Forward point movement FJOG 5 Reverse point movement RJOG 6 Terminal UP 7 Terminal DOWN 8 Free stopping 9 Reset 10 Run pause 11 External faults often open input 12...

Page 29: ...Frequency source Y and preset frequency switchover terminals 41 42 Reserved 43 PID parameter switchover terminal 44 User defined fault1 45 User defined fault2 46 Speed control torque control switchov...

Page 30: ...e delay time 0 0s 3600 0s 0 0s 0522 F5 35 DI1 disabled delay time 0 0s 3600 0s 0 0s 0523 F5 36 DI2 disabled delay time 0 0s 3600 0s 0 0s 0524 F5 37 DI valid mode selection 1 0 High level 1 Low level S...

Page 31: ...rved 22 Positioning close Reserved 23 Zero speed running 2 having output at stop 24 Accumulative power on time reached 25 Frequency level detection FDT2 26 Frequency 1 reached 27 Frequency 2 reached 2...

Page 32: ...0612 F6 19 FMR connectting delay time 0 0s 3600 0s 0 0s 0613 F6 20 Relay 1 connecttingdelay time 0 0s 3600 0s 0 0s 0614 F6 21 Relay 2 connecttingdelay time 0 0s 3600 0s 0 0s 0615 F6 22 VDO connectting...

Page 33: ...digit output method 0 False value output 1 Real valueoutput 0 061D F6 30 User defined outputdead zone 1 0 65535 0 061E F6 31 User defined 1output comparison value 1 0 65535 0 061F F6 32 User defined 1...

Page 34: ...ine 0 0700 F7 01 MF K key function selection 0 MF K disabled 1 Switchover between keypad control and remote command control terminal or communication 2 Switchover between forward rotation and reverse...

Page 35: ...isplay 0 0704 F7 05 LED display stop parameters 0000 FFFF Bit00 Setting frequency Hz Bit01 DC bus voltage V Bit02 DI input status Bit03 DO output status Bit04 AI1 voltage V Bit05 AI2 voltage V Bit06 R...

Page 36: ...celeration time 3 0 0s 6500 0s Model dependent 0805 F8 06 Deceleration time 3 0 0s 6500 0s Model dependent 0806 F8 07 Acceleration time 4 0 0s 6500 0s Model dependent 0807 F8 08 Deceleration time 4 0...

Page 37: ...26 Deceleration time 1 2 switch frequencypoint 0 00Hz F0 10 0 00Hz 081A F8 27 Terminal JOG preferred 0 Disabled 1 Enabled 1 081B F8 28 Frequency detection value FDT2 0 00Hz F0 10 50 00Hz 081C F8 29 Fr...

Page 38: ...in 0 0Min 082C F8 45 AI1 input voltage lower limit 0 00V F8 46 3 10V 082D F8 46 AI1 input voltage upper limit F8 45 10 00V 6 80V 082E F8 47 IGBT temperature threshold 0 100 75 082F F8 48 Fast current...

Page 39: ...al limit range 0 00 100 00 0 10 090A F9 11 PID setting change time 0 00 650 00s 0 00s 090B F9 12 PID feedback filtering time 0 00 60 00s 0 00s 090C F9 13 PID output filtering time 0 00 60 00s 0 00s 09...

Page 40: ...D 1 Sleep PID 0 091C F9 29 PID sleep threshold 0 0 100 0 60 0 091D F9 30 PID sleep delay 0 0 3600 0s 3 0s 091E F9 31 ID wake up threshold 0 0 100 0 20 0 091F F9 32 PID wake up time delay 0 0 3600 0s 3...

Page 41: ...selection 3 0 Free stopping 1 Stop according to the stop mode 2 Continue to run Single digit User defined fault 1 Err27 Ten s digit User defined fault 2 Err28 Hundred s digit Reserved Thousand s digi...

Page 42: ...point Ten s digit The second failure frequency of the decimal point Hundred s digit The first failure frequency of the decimal point 222 0A1D FB Group swing frequency fixed length and count FB 00 Swin...

Page 43: ...mple PLC function FD 00 Multistage speed 0 100 0 100 0 F0 10 0 00 0D00 FD 01 Multistage speed 1 100 0 100 0 0 00 0D01 FD 02 Multistage speed 2 100 0 100 0 0 00 0D02 FD 03 Multistage speed 3 100 0 100...

Page 44: ...eference 1 0 0s h 6553 5s h 0 0s h 0D14 FD 21 Acceleration deceleration time of simple PLC reference 1 0 3 0 0D15 FD 22 Running time of simple PLC reference 2 0 0s h 6553 5s h 0 0s h 0D16 FD 23 Accele...

Page 45: ...LC reference 9 0 3 0 0D25 FD 38 Running time of simple PLC reference 10 0 0s h 6553 5s h 0 0s h 0D26 FD 39 Acceleration deceleration time of simple PLC reference 10 0 3 0 0D27 FD 40 Running time of si...

Page 46: ...e of simple PLC reference 16 0 3 0 0D31 FD 50 Time unit of simple PLC running 0 S second 1 H hour 2 Min minute 0 0D32 FD 51 The source of multistage speed 0 0 Set by FD 00 1 AI1 2 AI2 3 Reserved 4 Res...

Page 47: ...mmunication fault Err16 17 Contactor fault Err17 18 Current detection fault Err18 19 Motor auto tuning fault Err19 21 Data overflow Err21 22 On power EEPROM check fault Err22 23 Short circuit to groun...

Page 48: ...monitoring D0 00 Operating frequency Hz 0 01Hz D000 D0 01 Setting frequency Hz 0 01Hz D001 D0 02 Bus voltage V 0 1V D002 D0 03 Output voltage V 1V D003 D0 04 Output current A 0 01A D004 D0 05 Output p...

Page 49: ...r on time 1Min D019 D0 26 Current running time 0 1Min D01A D0 27 Reserved D01B D0 28 Communication setting 0 01 D01C D0 29 Reserved D01D D0 30 Main frequency X diaplay 0 01Hz D01E D0 31 Auxiliary freq...

Page 50: ...value 1000H 10000 10000 decimal 10000 correspond 100 00 10000 correspond 100 00 Read Write Communication control command 2000H 0001 Forward running Write 0002 Reverse running 0003 JOG forward 0004 JOG...

Page 51: ...Read DO Output sign 1009H 1 Read AI1 Voltage 100AH 0 01V Read AI2 Voltage 100BH 0 01V Read Reserved 100CH Read Count value input 100DH 1 Read Length value input 100EH 1 Read Load speed 100FH 1rpm Read...

Page 52: ...01BH 0 1min Read Reserved 101CH Read Communication set value 101DH 1 10000 10000 Read Reserved 101EH Read Main frequency Xdisplay 101FH 0 01Hz Read Auxiliary frequency Y display 1020H 0 01Hz Read Tabl...

Page 53: ...0A AC Drive overload 000B Motor overload 000C Input missing phase 000D Output missing phase 000E Module overheating 000F External equipment fault 0010 Communication fault 0011 Contactor fault 0012 Cur...

Page 54: ...This means you shall change 0 the highest position in RAM address into F which is to change into the way of writing EEPROM also means to change 0XXX into FXXX Writing life span of EEPROM is generally...

Page 55: ...acceleration 1 Input voltage abnormal 2 An external force drives the motor during acceleration 3 The acceleration time is too short 4 The braking unit and braking resistor are not installed 1 Turn the...

Page 56: ...mperature 2 Clean the air filter 3 Replace the fan 4 Ask for technical service Err15 External equipment fault 1 External fault signal is input DI terminal or VDI function 1 Check the input DI terminal...

Page 57: ...on time reaches the setting value 1 Clear the record through the parameter initialization function Err31 PID feedback loss during running 1 PID feedback signal is abnormal 2 PID actual feedback is le...

Page 58: ...is abnormal 1 Check and reset the parameters in group F5 2 Re connect the external signal cables 3 Ask for technical service 4 AC Drive interference 1 Carrier frequency setting is not suitable 2 The g...

Page 59: ...e City Guangzhou High tech Zone Guangdong P R China Postcode 510663 Web http www saj electric com Technical Support Service Fax 86 20 6660 8589 E mail service drive01 saj electric com International Sa...