VM1000B
- 30 -
Function
Code
Parameter Name
Setting Range
Default
Property
Address
(HEX)
F6.03
Relay 2 function
2: Fault out(stop)
3: Frequency level detection FDT1 output
4: Frequency reached
5: Zero-speed running(no output at stop)
6: Motor overload pre-warning
7: AC Drive overload pre-warning
8: Set count value reached
9: Designated count value reached
10: Length reached
11: PLC cycle complete
12: Accumulative running time reached
13: Frequency limited
14: Torque limited
15: Ready for running
16: AI1 larger than AI2
17: Frequency upper limit reached
18: Frequency lower limit reached
19: Undervoltage state output
20: Communication setting
21: Positioning completed (Reserved)
22: Positioning close (Reserved)
23: Zero-speed running 2
(
having output at
stop
)
24: Accumulative power-on time reached
25: Frequency level detection FDT2
26: Frequency 1 reached
27: Frequency 2 reached
28: Current 1 reached
29: Current 2 reached
30: Timing reached
31: AI1 input limit exceeded
32: Offload
33: Running direction
34: Zero current detection
35: Module temperature reached
36: Software overcurrent output
37: Lower limit frequency reached (non-
operational)
38: Fault output (continue operation)
39: Reserved
40: This running time arrive
41: User-defined output 1
42: User-defined output 2
43: Timer output
1
○
0603
F6.04
~F6.05
Reserved
-
-
-
F6.06
VDO output selection
0
●
0606
F6.07~
F6.10
Reserved
-
-
-
F6.11
Reserved
0: Running frequency
1: Set frequency
2: Output current
3: Output torque
4: Output power
5: Output voltage
0
○
060B
F6.12
AO1 function
0
○
060C
F6.13
AO2 function
1
○
060D