User Manual
6
User Manual
3.3 Technical Data
Type
Suntrio-TL6K
Suntrio-TL8K
Suntrio-TL10K
Input (DC)
Max. DC Power [W]
6300
8200
10400
Max. DC Voltage [V]
1000V
MPPT Voltage Range [V]
240~800
240~800
240~800
Nominal DC Voltage
600
Start Voltage[V]
300
Min. DC Voltage[V]
200
Max. DC input Current PV1 / PV2 [A]
16 / 16
Number of MPPT
2
String(s) per MPPT
2
DC Switch
Optional
Output (AC)
Rated AC Power [W](@230V,50Hz)
6000
8000
10000
Max. AC Apparent Power [VA]
6000
8000
10000
Rated AC Current[A]
8.7
11.6
14.5
Max. AC Current [A]
9.7
12.9
15.8
Nominal AC voltage/ range
3/N/PE, 220/380V,230/400V,240/415V;180V-280V/312V-485V
Grid frequency/ range
50Hz,60Hz /44Hz-55Hz,54-65Hz
Total Harmonic Distortion (THDi)
< 3%(at nominal power)
Power factor, adjustable
0.9 leading~0.9 lagging
Feed-in Phase / Connection Phase
3 / 3
Efficiency
Max. Efficiency
97.9%
97.9%
98.0%
Euro Efficiency (at 600V
dc
)
97.3%
97.3%
97.5%
MPPT Accuracy
>99.5%
Protection
Internal Overvoltage Protection
Integrated
DC Insulation Monitoring
Integrated
DCI Monitoring
Integrated
GFCI Monitoring
Integrated
Grid Monitoring
Integrated
AC Short Circuit Current Protection
Integrated
Thermal Protection
Integrated
Anti-island protection monitoring
AFD
Interface
DC Connection
H4/MC4
LCD Display
Graphic LCD Display, Backlight, Inverter Parameter and Data Display
Display Language
Multi Language
Datalogger & Communication
RS485,Ethernet(Webserver embedded), WiFi(Optional),
Device Data
Topology
Transformerless
Consumption at Night [W]
<1
Consumption at Standby [W]
<12
Operating Temperature Range
:-20°C to +60°C(45°C to 60°C with derating)
Cooling Method
Fans
Ambient Humidity
0% to 95% Non-condensing
Altitude
Up to 2000m without power derating
Noise [dBA]
<40dB
Ingress Protection
IP65
Dimensions [WxHxD] [mm]
480×680 ×200
Weight [kg]
35
Standard Warranty [Year]
5 / 10 (Optional)
Certificates
AS4777, AS 3100, VDE0126-1-1/A1, G83-2,G59-2, C10/11, UTE C15-712-1,
TF3.2.1, EN 50438, IEC 62116, IEC 61727, IEC61000-6-2/3, IEC 62109-1/2