User Manual
User Manual
User Manual
47
Error Code
LCD Display
Message
Phenomenon and Possible Cause
Phenomenon and
Possible Cause
32
Bus Volt Bal.Err M
1)The Voltage of the BUS middle point
is beyond half of the BUS voltage.
2)If random, a possible cause is the
quick
variation of grid voltage.
If the error is still active, please
contact the local agent or SAJ
Service line.
33
Bus Volt High M
1)The open-circuit voltage of the PV
generator is higher than the maximum
DC input voltage of the inverter.
2)Sudden DC surge.
If the error is still active, please
contact the local agent or SAJ
Service line.
34
Bus Volt Low M
1)Boost MOSFET/IGBT damaged or the
PV string configuration is not correct.
2)Happens during Sunset. Can reproduce
daily.
If the error is still active, please
contact the local agent or SAJ
Service line.
35
L1 Current High M
The output current is beyond the firmware
limited value.
If random, a possible cause is the quick
variation of grid voltage.
Repetitive error means firmware failure
(Iac sensor).
C h e c k t h e G r i d - v o l t a g e
stability and AC connection.
If the error is still active,
p l e a s e c o n t a c t t h e l o c a l
agent or SAJ Service line.
36
L2 Current High M
37
L3 Current High M
38
HWBus Volt High M
1)The voltage of PV string connect
to the inverter is higher than the
HW limited value.
2)Sudden DC surge.
C h e c k t h e P V s t r i n g
c o n f i g u r a t i o n . T h e S A J
D e s i g n e r c a n h e l p y o u .
If everything is correct,
you need to contact local
agent or SAJ Service line.
39
HWPV1 Curr.High M
Input current sensing circuit damaged or
wrong string configuration .
C h e c k t h e P V s t r i n g
c o n f i g u r a t i o n . T h e S A J
D e s i g n e r c a n h e l p y o u .
If everything is correct,
you need to contact local
agent or SAJ Service line.
40
HWPV2 Curr.High M
41
HWL1 Curr. High M
The output current is beyond the HW
limited value.
If random, a possible cause is the quick
variation of grid voltage.
Repetitive error means HW failure (Iac
sensor)
C h e c k t h e G r i d - v o l t a g e
stability and AC connection.
If the error is still active,
p l e a s e c o n t a c t t h e l o c a l
agent or SAJ Service line.
42
HWL2 Curr. High M
43
HWL3 Curr. High M
44
Reserved(bit 46) M
45
Fan1 Error M
Fan locked or damaged.
Check the fans under the case
of the inverter. If fans are good,
please clean them. If the error
is still active, please contact the
local agent or SAJ Service line.
46
Fan2 Error M
47
Fan3 Error M
48
Fan4 Error M