Saijo denki International co.,ltd.
90
Is there cloging in the
refrigerant system ?
Correct refrigerant system
Is compressor working
normal?
Check compressor
Check control board
Error 43
Compressor 2 Inverter Driver Over
Current
The electric current of control board of
compressor 2 is higher than the specified value.
Is there cloging on
outdoor unit heat
exchanger ?
Cleaning
Is outdoor unit fan
motor normal ?
Check fan motor
Is the supply voltage to
the outdoor unit normal?
Check power voltage
Check code
Check code name
cause