No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
69
Is slave board normal?
Change the slave board
Check the master board
Check code
Check code name
cause
Error 11
Communication loss with Slave PCB
There is not communicate with Slave PCB.
Is connector and wiring between
master board and slave board
correct ?
Correct connector connection and
check circuit wiring
Is jumper on slave
board correct ?
Correct setting