Flow Chart Error code
NO
YES
NO
Change the sensor
YES
NO
Change the sensor
YES
Chang the control board
Saijo denki International co.,ltd.
65
Is sensor connect on
control board position
P2 ?
Correct connector connection
Is the wire of sensor
normal ?
Is sensor resistance
normal ?
Check code
Check code name
cause
Error 04
Indoor unit Inlet Temperature sensor
fail
There is an error in the refrigerant temperature
sensor at the Evaporator inlet.