No
Yes
No
Yes
No
Yes
Saijo denki International co.,ltd.
72
Is the wire of the sensor
normal ?
Change the sensor
Is sensor resistance
normal ?
Change the sensor
Check the control board
Check code
Check code name
cause
Error 14
Outdoor unit Inlet Coil Temperature
sensor fail
There is an error in the refrigerant temperature
sensor at the heat sink coil Inlet.
Is sensor connect on
control board ?
Correct connector connection