Battery Run Time
37
Annex A Parallel Setting
1. Connect UPS1 with RS232 cable to PC. Connect UPS with monitoring software.
2. Enter in menu “
Setting
”, set System Mode as “
Parallel
” in the menu “
System Setting
”.
3. Set United Number as “
2
”, set System ID as “
0
”. Press “
se
t” to confirm setting.
4. Connect UPS2 and set System Mode as “
Parallel
”, set United Number as “
2
”, set System ID
as “
1
”. Press “
set
” to confirm setting.
If there are 3 UPS are paralleled, set the United Number as “
3
”.
5. Connect UPS3 and set System Mode as
“Parallel”
, set United Number as “
3
”, set System
ID as “
2
”. Press “
set
” to confirm setting.
Annex B Battery Run Time
Standard battery pack includes 16 blocks 9Ah batteries. Please refer to the table below for the
battery runtime to configure battery packs.
Pack’s
number
UPS
Backup Time (mins)
1kW
2kW
kW
4kW
5kW
6kW
7kW
8kW
9kW
10kW
1
6k
60
25
16
10
6
/
/
/
/
/
10k
60
25
16
10
6
/
/
/
/
/
2
6k
180
60
30
24
20
16
/
/
/
/
10k
180
60
30
24
20
16
13
10
8
7
3
6k
240
120
60
40
28
23
/
/
/
/
10k
240
120
60
40
28
23
20
18
16
15
4
6k
360
180
110
60
42
30
/
/
/
/
10k
360
180
110
60
42
30
26
23
21
20
5
6k
480
210
150
90
60
46
/
/
/
/
10k
480
210
150
90
60
46
37
28
25
22
NOTICE: Backup time of batteries is depending on other facts such as battery brand,
working temperature, working time and so on, the table is calculated according to ideal
situation.
NOTICE: Set charger current according to battery capacity, the charger current should
not be larger than 0.2C, normally the charger current is set as 0.1C. Too large charger
current could damage the batteries.