Installation

 

18 

2.5  Connect Parallel Cables 

1. Brief introduction 

As long as the UPS is equipped with parallel cables, up to 4 UPS can be connected in parallel 
to realize output power sharing and power redundancy. The unit ID in paralleled system must 
be set to be different.

 

2. Parallel installation 

(1) Users need to opt two standard 15-pin communication cables which length is appropriate to 
be less than 3m. 
(2)Strictly follow the stand-alone wiring requirement to perform the input wiring of each UPS.   
(3) Connect the output wires of each UPS to an output breaker panel. 
(4) Each UPS needs an independent battery pack. 
(5) Please refer to the wiring diagram in the next page, and opt suitable breaker. 
The requirement of the output wiring is as follows:   

    It’s recommended that the wires of output of the UPS to be less than 20m. 
    The difference between the wires of input & output of the UPS is required to be less than 

10%. 

The wiring diagram is shown as follows: 

 

6/10KH/S(1/1) 

Summary of Contents for EA900RT G4 10KH

Page 1: ...USER MANUAL UPS ON LINE EA900RT G4 6 10 KVA 1 1 ...

Page 2: ...Output Power 15 2 4 Connect External Batteries Long Backup Model UPS 17 2 5 Connect Parallel Cables 18 2 6 Connect Communication Cables 19 3 Controls and Indicators 21 4 Operation 27 4 1 Operation Mode 27 4 2 Parallel Operation 28 5 Communication 29 5 1 RS232 and USB Port 29 5 2 EPO Port 29 5 3 Intelligent Cards Optional 30 6 Maintenance 31 6 1 Battery Maintenance 31 6 2 Battery Disposal 31 6 3 Ba...

Page 3: ...0 230 240Vac is designed for use with a three wire input L N G 1 1 or a five wire input L1 L2 L3 N G 3 1 WARNING The battery can present a risk of electrical shock and high short circuit current Following precautions should be observed before replacing the battery Wear rubber gloves and boots Remove rings watches and other metal objects Use tools with insulated handles Do not lay tools or other me...

Page 4: ...or restricted sales distribution to informed partners Installation restrictions or additional measures may be needed to prevent radio interference Operated the UPS in an indoor enviroment only in an ambient temperature range of 0 40 C 32 104 F Install it in a clean environment free from moisture flammable liquids gases and corrosive substance This UPS contains no user serviceable parts except the ...

Page 5: ...ficient AC power compared with the previous generation Full digital control technology based on DSP to achieve high reliability and power function Fan speed can be auto conditioned according to the loads input voltage or working mode Digitally controlled charger current and voltage compared with the previous generation which is fixed in hardware Super high power density Failure waveform record fun...

Page 6: ...Product description 4 6 10KS Fig 1 1 Front View 6 10KH 1 1 6 10KS 1 1 6 10KH 3 1 ...

Page 7: ...s and function SNMP DB9 type used to connect monitoring software Fans intelligent fan speed control Parallel port option RS232 DB9 type used to connect monitoring software EPO NC USB B type used to connect monitoring software Battery temperature option GND Bypass breaker surge proection Terminal and cover Battery pack ...

Page 8: ...uring that the waveform of the input current used by the UPS is near ideal Extracting this sinewave input current achieves two objects The utility power is used as efficiency as possible by the UPS The amount of distortion reflected on the utility is reduced This results in cleaner power being available to other devices in the building not being protected by the UPS 1 5 3 Inverter In normal operat...

Page 9: ...ture of 15 25 C 1 5 7 Static Bypass The UPS provides an alternate path for utility power to the connected load in the unlikely event of a UPS malfunction Should the UPS have an overload over temperature or any other failure condition the UPS automatically transfers the connected load to bypass Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED To manually transfer t...

Page 10: ...If input power is failure when in normal mode UPS will transfer to battery mode In this mode the battery provide power to inverter Shown as Fig 1 6 NOTICE press in battery mode will shutdown UPS completely Fig 1 6 Battery Mode ECO Mode only available for single unit When UPS works in ECO mode load is feed by bypass Inverter is standby charger is working normally The efficiency is up to 98 but UPS ...

Page 11: ...ers want to burn in UPS without load could set the UPS as Self Aging Mode in this mode the current flow through rectifier inverter and back to input through bypass It needs only 5 loss to burn in UPS with 100 load Shown as Fig 1 8 Fig 1 8 Self Aging Mode 1 7 Product Specifications 1 General Specifications Model 6kH S 1 1 10kH S 1 1 6kH S 3 1 10kH S 3 1 Power Rating PF 1 kVA kW Frequency Hz 50 60 I...

Page 12: ...Humidity Altitude Storage temperature 0 C 40 C 95 1000m 0 C 70 C NOTICE If the UPS is installed or used in a place where the altitude is above than 1000m the output power must be derated in use please refer to the following Altitude M 1000 1500 2000 2500 3000 3500 4000 4500 5000 DeratingPower 100 95 91 86 82 78 74 70 67 Output Voltage Regulatio n Power Factor Frequency tolerance Distortion Overloa...

Page 13: ...nstallation mode according to the actual conditions 1 Notes for installation 1 The UPS must be installed in a location with good ventilation far away from water inflammable gas and corrosive agents 2 Ensure the air vents on the front and rear of the UPS are not blocked Allow at least 0 5m of space on each side 3 Condensation to water drops may occur if the UPS is unpacked in a very low temperature...

Page 14: ...s shown in Fig 2 2 Fig 2 2 Installing support bases with spacers Step 3 Adjust the direction of UPS operation and display panel 1 Remove the front plastic bezel cover gently as shown in Fig 2 3 Fig 2 3Removing the front plastic bezel cover 2 Pull the operation and display panel gently rotate it 90 degrees clockwise 1 1 or anticlockwise 3 1 and snap it back into position as shown in Fig 2 4 ...

Page 15: ...y panel have been rotated 90 degrees clockwise which provides upright viewing for users Step 4 Place the UPS and battery cabinet on the support bases Each UPS needs two pairs of support bases to install as shown in Fig 2 5 Fig 2 5 Tower installation 2 Rack Installation 1 Various installation configurations are available single UPS single UPS with single or ...

Page 16: ...cabinet onto the rack through brackets Installation method 1 Take out two brackets and six M4 screws from the accessories and fix the brackets onto the UPS using the screws through installation hole as shown in Fig 2 6 Fig 2 6Installing brackets 2 Place the UPS onto the guide rail in the rack and push it completely into the rack along the guide rail it is prohibited to move the UPS through the bra...

Page 17: ...hould not be used in the input of UPS 2 Installation Installation and wiring must be performed in accordance with the local electric code and the following instructions by professional personnel For safety please cut off the mains power switch before installation Open the battery breaker for long backup time model H model 1 Open the terminal block cover located on the rear panel of the UPS please ...

Page 18: ...nected tightly 4 Connect the input output and battery wires to the terminals as Fig2 8 5 The protective earth ground wire refers to the wire connection between the equipment which consumes electric equipment and the ground wire The wire diameter of protective earth ground wire should be at least as above mentioned for each model and green wire or green wire with yellow ribbon wire is used 6 After ...

Page 19: ... same voltage same type should be strictly followed 2 For UPS 6 10KH select the UL1015 10 8AWG 6 10mm2 or other insulated wire which complies with UL Standard for the UPS battery wirings The procedure of installing battery bank should be complied with strictly Otherwise you may encounter the hazardous of electric shock 1 A DC breaker must be connected between the battery pack and the UPS The capac...

Page 20: ...ropriate to be less than 3m 2 Strictly follow the stand alone wiring requirement to perform the input wiring of each UPS 3 Connect the output wires of each UPS to an output breaker panel 4 Each UPS needs an independent battery pack 5 Please refer to the wiring diagram in the next page and opt suitable breaker The requirement of the output wiring is as follows It s recommended that the wires of out...

Page 21: ...g Diagram 2 6 Connect Communication Cables Connect communication cables If there are 2 UPS are paralleled connect communication cables as Fig2 10 Fig 2 10 2 UPS Paralleled System If there are 3 UPS are paralleled connect communication cables as Fig 2 11 ...

Page 22: ...ed System If there are 4 UPS are paralleled connect communication cables as Fig 2 12 Fig 2 12 4 UPS Paralleled System NOTICE must set the UPS is parallel system as parallel mode via software according to Annex A before start parallel system ...

Page 23: ... utility 4 Press to confirm setting when in setting mode 5 Press and hold to enter or exit the setting mode 6 Press and hold to enter the self test mode when ups is normal otherwise to mute off the alarm press and hold again to mute on 7 Press to exit the fault page in fault mode If no operation in 10s return to the fault interface 1 Press to page up the LCD menu 2 Press and hold to enter the hist...

Page 24: ... is normal Fig 3 2 LCD Menu LCD display is divided into three areas Icons display area value display and settings area and operation mode area Icons display area There are following contents in the area of display page Load and battery icons indicate load and battery capacity and each square represents 25 of capacity Load icon will flash when UPS is overloaded battery icon will flash when battery ...

Page 25: ... fault code will be displayed in fault mode In menu setting interface include output voltage value OPU physical address Id parallel Enable PAL end of discharge point Eod Expert mode EP Battery numbers PCS Emergency power off EPO etc Operation mode area After starting up in 20 seconds this display area mainly indicates the UPS power rating This display area mainly indicates the UPS operation mode i...

Page 26: ...emperature information Page 4 Display UPS input information Page 5 Display UPS battery voltage battery capacity percentage Page 6 Display UPS battery numbers Warning code Page Display UPS warning code ALA means alarm All warning code information refer to troubleshooting ...

Page 27: ...ld the button again to return to thehome screen Parameters setting If want to set rated parameters Press and hold in setting mode STdby on the bottom of LCD present and all LED flicks Rated voltage setting Could select rated voltage as 200Vac 208Vac 220Vac 230Vac 240Vac press or to select press to confirm selection Rated frequency setting Could select rated frequency as 50Hz 60Hz press or to selec...

Page 28: ...d be set as 0 to 9 press or to select press to confirm selection ECO mode setting Could select ON enable OFF disable press or to select press to confirm selection EPO setting Could select ON enable OFF disable default doesn t work Press or to select press to confirm selection NOTICE when rated voltage is 200 208Vac the output PF is 0 9 If other parameters areneeded to change please set it via moni...

Page 29: ... 3 About 1 minute later the UPS turns intoBattery mode If utility power recovers UPS will transfer to normal mode 4 1 3 Turn off the UPS in Normal Mode 1 Shutdown the connected load and open external output breaker 2 Press button in condition of normal mode to transfer to bypass 3 For long backup model open the mains input breaker and bypass input breaker then open the battery breaker to turn off ...

Page 30: ...nd output wires the output breaker and the parallelcables 2 Open the input and output breakers of each UPS Connect the input wires output wires and battery wires 3 Connect each UPS one by one with the parallel cables 4 Close the battery breakers and the input breakersof all of the UPS in the parallel system in turn 5 Turn on each UPS in turn and observe their display Make sure that each UPSdisplay...

Page 31: ...e UPS or USB port 5 1 RS232 and USBPort USBport optional 5 2 EPO Port The Emergency Power Off EPO is a feature that will immediately disconnect all connected equipment from mains power The remoted EPO is located on the rear panel of UPS with green terminals shown as Fig 1 2 It s normal closed if it s opened it will acivate EPO function the UPS will be shutdown NOTE The system default EPO doesn t w...

Page 32: ...contact are installed in one intelligent slot A and B on the right side of ports are RS485 output A is B is Pins Definition PIN1 Close UPS fault PIN2 Close Alarm sounds system fault PIN3 Grounding PIN4 Remote shutdown PIN5 Common PIN6 Close bypass working PIN7 Close low battery PIN8 Close UPS working Open bypass working PIN9 Close Mains power Off The UPS has one intelligent slots for SNMP card dry...

Page 33: ...emove jewelry watches and other metal objects 2 Use rubber gloves and boots use tools with insulated handles 3 If it is necessary to replace any connection cables please purchase the original materials from the authorized distributors or service centers so as to avoid overheat or spark resulting in fire due to insufficient capacity 4 Do not dispose of batteries or battery packs in a fire The batte...

Page 34: ...ety observe the following precautions 1 Turn off the UPS before cleaning it 2 Clean the UPS with a dry cloth Do not use liquid or aerosol cleaners 3 Never block or insert any objects into the ventilation holes or other openings of the UPS 6 5 Checking UPS Status It is recommended to check the UPS once every half year 1 Check if the UPS is faulty Are the LED indicators abnormal Is there any alarm 2...

Page 35: ...de Fault mode Fig 7 1 Fault code Fault code informing Fault Code Cause Solution 35 39 Inverter forbidden 40 44 over temperature Rectifier heat sink is over temperature or the temp sensor is not connected correctly Check if fans are working normally Check if anything block ventilation Check if the sensor is connected correctly Check if the environmental temp is over the range of UPS 45 49 Output sh...

Page 36: ...ver voltage low voltage shorted or IGBT opened Please manually clear the fault and if the fault is still on please contact with local dealer 145 149 Fan fault One or more fans are faulty or blocked Check if all fans working normally Check if something blocks fan 150 154 EPO Check if EPO is closed correctly Check if EPO is activated manually 155 159 SPS abnormal Please contact your supplier Note Co...

Page 37: ...d Please contact with local dealer 209 EEPROM fault Clean the warning by LCD panel or using debug software Or shutdown UPS and startup again 210 Input over current time out Check the input voltage is abnormal 211 Battery voltage low Remove non critical devices and charge the battery as soon as possible 214 Synchronize signal loss Check whether the parallel wire connecting and parallel boards are a...

Page 38: ...ut voltage and frequency is over the working range Check if mains input breaker or external input breaker is opened Check if the input phase sequence against Please recover mains input power otherwise output will be shutdown if battery is discharged to EOD 235 Bypass abnormal Check if bypass input power is abnormal Check if bypass input breaker is opened Please recover bypass input power otherwise...

Page 39: ... 9Ah batteries Please refer to the table below for the battery runtime to configure battery packs Pack s number UPS Backup Time mins 1kW 2kW kW 4kW 5kW 6kW 7kW 8kW 9kW 10kW 1 6k 60 25 16 10 6 10k 60 25 16 10 6 2 6k 180 60 30 24 20 16 10k 180 60 30 24 20 16 13 10 8 7 3 6k 240 120 60 40 28 23 10k 240 120 60 40 28 23 20 18 16 15 4 6k 360 180 110 60 42 30 10k 360 180 110 60 42 30 26 23 21 20 5 6k 480 ...

Page 40: ... wheelie bin symbol indicating separate collection for electrical and electronic equipment EEE The Horizontal bar underneath the crossed out wheelie bin indicates that the equipment has been manufactured after the Directive came into force in 2005 The main parts of the drive can be recycled to preserve natural resources and energy Product parts and materials should be dismantled and separated Cont...