Installation
16
current is less than the UPS’s maximum input current. Otherwise the receptacle may be burned
and destroyed. For the long backup time modes, make sure that the capacity of batteries is
larger than 24Ah to avoid over charging. If not, please confirm the charge current and set the
charge current according to battery capacity.
6/10kH/S(1/1)
6/10kH/S(3/1)
Fig 2- 8: Terminal Block Wiring Diagram
NOTICE
:
Make sure that the input and output wires and the input and output terminals are
connected tightly.
(4)Connect the input, output and battery wires to the terminals as Fig2-8.
(5)The protective earth ground wire refers to the wire connection between the equipment which
consumes electric equipment and the ground wire. The wire diameter of protective earth ground
wire should be at least as above mentioned for each model and green wire or green wire with
yellow ribbon wire is used.
(6)After having completed the installation, make sure the wiring connection iscorrect.
(7) Please install the output breaker between the output terminal and the load.
(8) To connect the load with the UPS, please turn off all the loads first, then perform the
connection and finally turn on the loads one by one.