This warmer is to be used SOLELY with premoistened cloth and hair care products manufactured by Sage Products. The warmer has been designed
and safety tested to be used exclusively with these products only. ANY other use of this warmer by the facility including, but not limited to, use with
other brands of products, can result in overheating, fire or other hazardous conditions and is expressly forbidden.
General Use
1.
DO NOT
tamper with or make any adjustments to the control panel, housings, safety switches, or any other part of the warmer. Repairs
should only be done by a qualified service person. Contact Sage Products for authorized service.
2.
If a fire occurs in the warmer,
LEAVE DOOR(S) CLOSED
. Disconnect the power cord, or shut off power at the fuse or circuit breaker panel.
3.
DO NOT
store flammable materials next to, on top of, in or near the warmer. They could be a fire hazard.
4.
Your warmer is equipped with a protective device designed to turn the unit off in the event of overheating. The warmer will remain
inoperable until it has cooled.
CAUTION:
If there is any indication that the premoistened cloth and/or hair care products are excessively hot, do not use. Remember, gloves diminish your
sensitivity to heat. Closely monitor heat level with infants, unresponsive or skin sensitive individuals. Products are for individual use only
.
Examine
the warmer before plugging in power cord. If any part appears damaged, do not use the warmer. Contact your Sage Products
Representative immediately.
1.
To install warmer,
position unit on a sturdy, flat surface, such as a counter top or cart provided by Sage Products. For proper grounding,
plug cord into AC receptacle marked “hospital only” or “hospital grade.” Turn power switch on front panel to “ON” position. The red light in
the power switch should illuminate when switched to the “ON” position.
When power is turned on, the warmer goes through the following self-diagnostic tests:
•
All LED indicators will flash once.
•
Temperature indicator counts down.
If no faults are found
, LED indicators will turn off if no packages are present in warmer slots. If packages are present, the LED indicators for
the filled slots will indicate “NOT READY.”
If a fault condition exists
, LED indicators will not light up if a package is present in the warmer slots. Unused slots will indicate a “NOT
READY” status. Discontinue use of the warmer unit and contact Sage Products.
2.
Before stocking the warmer,
make sure you have set the Status Indicator Display to the desired setting [Position B or C] to display TAKE
FIRST or DISPOSE for packages that have remained in the warmer for an extended period. See page 2 of this manual for more information
on how to change the Status Indicator Display.
3.
To stock warmer,
open door(s) and fill slots with one package per slot. Place packages on shelves so they do not interfere with closing of
door(s). Packages should be placed far enough back that they contact rear of shelves, but not beyond. Close warmer door(s). DO NOT place
previously opened packages into warmer.
4.
Packages require approximately 2 hours to warm.
Packages are ready for use when the “READY” indicator is illuminated. To remove
a package for use, open door(s). Remove package(s). Close warmer door(s), making certain door(s) close completely.
5.
Replacement parts and service:
Before performing any repairs or service on this warmer, contact Sage Products.
6.
Fuses:
This warmer is equipped with two externally accessible fuses. Turn off and unplug the warmer before attempting to remove fuses. If the
warmer stops running, check the fuses on the back side of the cabinet’s exterior. If a fuse is blown, replace it with another fuse of identical
rating. If the new replacement fuse blows, contact Sage Products for further instructions.
To replace fuse:
Turn off and unplug unit. Find the round knob/receptacle on the rear panel of the warmer cabinet labeled “FUSE” and remove the
fuse cover as indicated by the arrow on the fuse cover. Remove the fuse and replace it with an 8-Amp, 250-Volt (8 A, 250 V) fuse and replace the
fuse holder cover. Plug the warmer into the 110 V power outlet and turn power switch to the “ON” position. If warmer will not run, or does not run
properly after replacing the fuse, call Sage Products for further direction.
SAFETY PRECAUTIONS
INSTRUCTIONS FOR USE
CAWR227