PESD
™
9
Approvals:
UL LISTED file No. E334957
Per ISA 12.12.01-2007
CAT REPORT No. E188860-A3
per UL61010-1, 3
RD
Edition
CAN/CSA-C22.2 No. 61010-1, 3
RD
Edition
Input
AC SINGLE or 3-P DELTA or WYE:
20 to 600VAC
3
, Line-to-Line, 50/60/400 Hz
DC OR STORED ENERGY:
20 to 1000VDC
, (Voltages Line-to- Line or Line-to-Ground)
Maximum Rating
750VAC
3
or 1000VDC
@ 1.2 Watts, Operating Ambient Air of 55°C Max.
Detection
Flashing : 14VAC
3
, 18.5VAC
1
, 15VDC
(typical cut-off’s)
Thresholds
Solid- ON : 15VAC
3
, 19VAC
1
, 17VDC
(typical cut-off’s)
Temperatures
Operate : -20C to +55C, Code T6
Storage : -45C to +85C
Terminations
3 Ft. Stranded Cu. Wires, 12 AWG 90° @1000V,
UL-1452 PVC Insulation w/ nylon jacket
Wire
4-Wire : L1- L3: BLK w/ bar code, GND: Grn/Yel (Fig. 1)
5-Wire : L1- L3 + N: BLK w/ bar code, GND: Grn/Yel, N: Wht Neutral (Fig. 2)
Indicators
4-Wire : (6) Red L1-L3, (2) Amber GND LEDs, Fully Encapsulated
5-Wire : (6) Red L1-L3, (4) Amber N & GND LEDs, Fully Encapsulaed
Enclosure
Threaded Base & Channel Ring Lexan 940 BLK,
Cover Lexan 943
Totally Encapsulated for Environment Protection
O-Ring Seals
#118 & #123 Blue FVMQ Flourosilicone,
UL approved material
MEASURING EQ. 46RD
IND. CONT. EQ. 496Y
HAZ. LOC. 42 RV
UL TYPE 4X
IP67
TYPE 12
TYPE 13
CAT III 1000V
CAT IV 600V
DC or AC-rms to Ground
(Peak Impulse Transient 8000V
20 repetitions, 2 ohm source)
SYMBOL IDENTIFICATIONS
3
3 Phase AC rms
DC Volts
Electric Shock Danger of Death
Caution
Double Insulated Symbol
EXPLOSION HAZARD – SUBSTITUTION OF ANY COMPONENT MAY
IMPAIR SUITABILITY FOR CLASS I, DIVISION 2
3 Phase, 4- Wire
3 Phase, 5- Wire
Fig. 1
Fig. 2
Summary of Contents for R-3D2 Series
Page 4: ...PESD 4 Mounting Instructions for M20 Knock Out Mount MA Control Dwg 206 R 3D2 ...
Page 11: ...PESD 11 R 3D2 R 3D2 SR WIRING INSTRUCTIONS AC APPLICATIONS ...
Page 12: ...PESD 12 WIRING INSTRUCTIONS R 3D2 R 3D2 SR DC APPLICATIONS ...
Page 13: ...PESD 13 WIRING INSTRUCTIONS R 3D2 W5 R 3D2 SRW5 AC APPLICATIONS ...
Page 14: ...PESD 14 R 3D2 W5 R 3D2 SRW5 DC APPLICATIONS WIRING INSTRUCTIONS ...
Page 16: ...16 ...
Page 25: ...25 ...
Page 34: ...34 ...
Page 60: ......