for  service  or  warranty  replacement.

  See  the  warranty  section  in  this 

manual. 

 

   

OPERATION 

  

 

  NORMAL 

 

 

  CO ALARM 
    

 

  

  PROPANE ALARM 

  

  ALARM  
  MALFUNCTION 
 
  END OF LIFE 
 
 
  WARM UP CYCLE 

  (ABOUT 10 MINUTES)

 

     

AUDIBLE SIGNAL        VISUAL SIGNAL

  

 

                                       

        NONE                      STEADY  GREEN 

   

   

  

 

      

4 “BEEPS”                    STEADY RED 

      5 SECONDS OFF 

 

 

“   CONSTANT BEEPING   FLASHING RED 

   

  

“    BEEP” EVERY              ALTERNATING 

   30 SECONDS               RED/GREEN 

 
B   BEEPS EVERY            RED RED GREEN GREEN   
     25-30 SECONDS              FLASHING  
  
     NO SOUND                   FLASHING GREEN  

 

TROUBLE-SHOOTING GUIDE  

Use this chart to trouble-shoot problems with this 85 Series Alarm. 

PROBLEM 

   

CAUSE/SOLUTION 

Green Operational LED Off 

1.Bad Wire Connection 

 

2. Reversed Wiring 

 

3. Main Power Off     

 

4. Missing or Blown Fuse 

 

5. Contact Customer Service                                      

No Sound When Testing  

Contact Customer Service 

No Red LED When Testing  

Contact Customer Service 

Locked In Alarm 

 

Contact Customer Service

 

 

MALFUNCTION ALARM LED  1. Check Battery Voltage 
Red/Green & Beeps 
Every 15 Seconds   

 

Battery Voltage is Good and it 

2. Contact Customer Service 

Will Not Reset To Normal operation  

END OF LIFE ALARM   

Push reset button to reset for               
3 days – Replace within 30 days.

        

                                           

Customer Service 800-383-0269    www.safetalert.com 

  

HOW TO TAKE CARE OF YOUR ALARM 

This  CO  /  Propane  Gas  Alarm  is  designed  to  be  as  maintenance  free  as 
possible.  To keep your alarm in good working order, you must: 

 

TEST THE ALARM WEEKLY. 

 See the section, 

Test Procedure

in this manual for further information.

 

 

VACUUM THE DUST OFF THE ALARM COVER. 

At least once 

a  month  (more  frequently  in  dusty  locations),  use  the  soft  brush 
attachment of your vacuum to clean the alarm cover. 

 

CLEAN THE  ALARM COVER WHEN DIRTY. 

  Wash the alarm 

cover  by  hand.  Use  a  cloth  dampened  in  clean  water.    Dry  with  a  soft 
cloth

 

DO  NOT  SPRAY  CLEANING  AGENTS  OR  WAXES

 

DIRECTLY  ONTO  THE  FRONT  PANEL.

    This  action  may  damage 

the sensor, cause an alarm or cause an alarm malfunction. 

 

OBSERVE  THE  COLOR  OF  THE  INDICATOR  LIGHT.   

At 

frequent  intervals  and  during  your  weekly  test,  check  the  indicator  light 
on the on the front panel of the alarm.  

 

 

See the section, 

Operation,

 in this manual for further information. 

 

 

 

 

 

PROCEDURES TO TAKE DURING GAS ALARM

 

     

  

1. Turn off all Gas appliances (Stove, Heater, Furnace, 
Refrigerator, etc.), extinguish all flames and smoking material.  

2. Press the Test/Mute switch. DO NOT DISCONNECT   
    POWER 

3. Evacuate the RV. Make sure everyone is accounted for.     
    Leave the door and windows open. 

4. Turn off the propane tank valve. 

5. Determine and repair the source of the leak. Get professional  
    help if necessary. 

CAUTION- DO NOT RE-ENTER UNTIL THE PROBLEM IS 
CORRECTED.

 

 

PROCEDURES TO TAKE DURING AN CO ALARM 

Follow the alarm procedures for your country.  The emergency number 
depends on your travel location.  

 

 

 

 

 

 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROCEDURES TO TAKE

  

DURING A CO ALARM IN THE USA 

!

 

WARNING: 

Actuation  of  this  device  indicates  the 

presence  of  carbon  monoxide  (CO)  or  propane  gases,  which  can 
KILL  YOU.  If  signal  sounds  (4  beeps  and  flashing  or  solid  red 
light): 

1)

  Operate  the  Test/Mute  button; 

2)

  Call  your  emergency 

local  service  (Phone  Number  _____________  )  (fire  department 
or  911); 

3)

  Immediately  move  to  fresh  air  -  outdoors  or  by  an 

open door/window. Check that all persons are accounted for. Do 
not  reenter  the  premises  or  move  away  from  the  open  door  / 
window  until  the  emergency  responders  have  arrived,  the 
premises  have  been  aired  out  and  your  alarm  remains  in  its 
normal  operation. 

4)

  After  following  steps  1-3,  if  your  alarm 

reactivates  within  a  24-hour  period,  repeat  steps  1-3  and  call  a 
qualified 

appliance 

technician. 

(Phone 

Number 

_______________)  to  investigate  for  sources  of  CO  from  fuel 
burning equipment and appliances, Inspect for proper operation of 
this  equipment.  If  problems  are  identified  during  this  inspection 
have  the  equipment  serviced  immediately.  Note  any  combustion 
equipment  not  inspected  by  the  technician  and  consult  the 
manufacturers’ instructions, or contact the manufacturer directly, 
for  more information about CO safety and this equipment. Make 
sure that the motor vehicles are not, and have not been, operating 
in an attached garage or adjacent to the residence. 

 

 
 
 
 
 
 

                     

                    PROCEDURES TO TAKE  

               DURING A CO ALARM IN CANADA 

!

 WARNING: 

Actuation of this device indicates the presence of 

carbon monoxide (CO) and propane gases which can KILL YOU. If 
signal sounds (4 beeps and flashing or solid red light: 1) Operate the 
Test/Mute. Immediately move to fresh air - outdoors or by an open 
door/window.  Check  that  all  persons  are  accounted  for.  Do  not 
reenter  the  premises  or  move  away  from  the  open  door/window 
until  the  emergency  responders  have  arrived,  the  premises  have 
been  aired  out,  and  your  alarm  remains  in  its  normal  condition; 2) 
call your emergency local service (telephone number _________) ( 
Fire department or 911). 

 

 