CS-I User and Maintenance, R.2.8 ENG
Safco Systems Ltd-Via Isonzo 17/b-20090 Cesano Boscone-Milan-Italy
tel. +39 024504433 Fax +39 024504321 E-mail:[email protected] Web site: www.safcosys.it
33 of 109
Default value D‰ e V‰:
50/100
Default Value in IK , EK, AD:
0.25/1.0
Default Value in PK :
0.2
It sets the temper current or the temper power
.
Hold time:
Range value:
in cycles from 0.5 to 99.0 step 0.5
in milliseconds from 10 to 1980 step 10
Cycles Default Value:
0.5
Milliseconds Default Value:
10
It sets the hold time, electrodes are closed with no current.
Off time:
Range value:
in cycles from 0.0 to 99.0 step 0.5
in milliseconds from 0 to 1980 step 10
Cycles Default Value:
0.0
Milliseconds Default Value:
0
Set the off time, electrodes open.
Pressure 5:
Range value:
from 0 to 99%
Default
Value:
0
It sets the percentage of the voltage for the analogical output of the proportional valve.
During the Forging time, if zero or less, the previously set value does not change
.
Forge:
Range
value:
NO;
YES
Default
Value:
NO
If set to “NO”, no forging pressure is applied, the forging valve will not go on, and will
activate pressure 5. Set to YES, in D‰, v‰, IK and PK mode, it will set the pressure 5 and
activate forging valve after delay forging time. Delay starts from beginning of weld.
Forge delay:
Range value:
in cycles from 0.0 to 99.0 step 0.5
in milliseconds from 0 to 1980 step 1
Cycles Default Value:
0.0
Milliseconds Default Value:
0
It sets the delay time, from the start of welding, in D ‰ V ‰, IK PK modes, it activates the
forging valve and set the pressure 5.
Cycle repeat:
Range
value:
NO;
YES
Default Value:
NO