Operation
Chapter Four Operation
Discharge
09
End voltage with different discharge rate must be less than the specified value. Charge the battery
as soon as possible after discharge.
In order to extend the service life, the depth of discharge should be less than 60% of the rated
capacity. The discharge over 60% DOD is deep discharge and would shorten the service life.
Under the temperature of -25
℃
,discharge over 60% DOD is prohibited, except protective measure
is adopted such as raising temperature.
Temperature
The operation temperature range is -25
℃
~60
℃
. All the performance data is measured at ambient
temperature of 25
℃
.The optimal temperature is 25
℃
±5
℃
, over high temperature would shorten the
service life and over low temperature would lower the capacity available. The highest acceptable
temperature is 60
℃
.
Floating Charge and Equalizing charge
Floating charge
Floating operation is the best operation condition for battery. In floating operation, the battery
keep fully charged state,under this condition,battery could reach the longest service life.Under
the temperature of 25
℃
, recommended floating charge voltage setting value is 2.23V/ cell,
In such method,it take about 24~36h for battery fully charged. For achieving better
performance, the floating charge voltage should be suitable adjusted according to ambient
temperature, temperature compensation coefficient is -3.5mV/
℃
/cell, for details please refer to
Table 4-1.