144
Energy Smart |
Table of compliance with Regulation EU 1254/14
Annex IV - Energy Smart
Supplier name or brand
Sabiana SpA
Supplier model identification
ENY-S-170
ENY-S-270
ENY-S-360
ENY-S-460
ENY-S-600
Specific energy consumption SEC
in [kWh/(m²a)] for each applicable
climate zone (temperate, hot, cold,
climate)
-39,4 -15,2 -77,2 -39,3 -15,1 -76,9 -39,7 -14,9 -78,3 -38,4 -13,9 -76,6 -37,9 -13,5 -76,0
SEC class - temperate climatic zone
A
A
A
A
A
Type declared according to EU
1253/14
BVU
BVU
BVU
BVU
BVU
Type of drive installed
Continuous speed
variator
Continuous speed
variator
Continuous speed
variator
Continuous speed
variator
Continuous speed
variator
Type of heat recovery system
Static sensitive heat
recovery unit
Static sensitive heat
recovery unit
Static sensitive heat
recovery unit
Static sensitive heat
recovery unit
Static sensitive heat
recovery unit
Thermal efficiency
87,0%
86,5%
90,1%
88,6%
88,0%
Maximum flow rate [m³/h]
3
170
270
360
460
600
Power absorbed by the fan drive,
including all motor control devices,
at maximum flow rate [W]
4
45
76
125
215
300
Sound power level (LWA) in [dB(A)]
40,6
46,6
49,0
47,9
52,4
Reference flow rate [m³/h]
120
190
250
320
420
Reference pressure difference [Pa]
50
50
50
50
50
SPI [W/(m³/h)]
0,183
0,184
0,209
0,237
0,247
Control factor and type of control
0,95
Timer control
0,95
Timer control
0,95
Timer control
0,95
Timer control
0,95
Timer control
Maximum percentages declared [%]
of internal and external leakage
Internal leakage:
0,4%
Internal leakage:
0,4%
Internal leakage:
0,7%
Internal leakage:
0,3%
Internal leakage:
0,6%
External leakage:
1,8%
External leakage:
1,4%
External leakage:
2,7%
External leakage:
0,7%
External leakage:
1,84%
Position and description of the visual
warning signal relating to the filter
for RVUs intended for use with filters,
including a text that emphasizes the
importance of replacing the filter at
regular intervals in order to safeguard
unit performance and energy
efficiency
Please refer to the following parts of the brochure:
• T-EP control description
• Recommendations for filter replacement: filters clogging could result into relevant flow rate reduction,
which implies the need of frequent windows opening and consequent thermal demand increase.
• Proper replacement period depends on background air quality, which can broadly vary between city centers
and countryside.
• In order to prevent filters clogging, optimum average period for filters replacement is 3 month. However, due
to normal dust collection and spring pollens, maximum suggested period should not exceed 6 months.
• For “ENY-S” range, in case where optional automatic flow system is provided, neglected filters replacement
does not result into air flow decrease, however it would imply relevant power consumption increase. As a
matter of fact, fans energy consumption due to filters operation could rise up by 2 or 3 times.
• Filters replacement period can be modified by maintainer with a precision of days (min 30, max 360).
Internet address with the disassembly
instructions
www.sabiana.it
www.sabiana.it
www.sabiana.it
www.sabiana.it
www.sabiana.it
AEC (Annual Energy Consumption)
[kWh/a]
252
207
789
253
208
790
281
236
818
313
268
850
325
280
862
AHS (Annual Heating Energy Savings)
[kWh/a]
4507 2038 8817 4492 2031 8787 4601 2080 8787 4555 2060 8912 4537 2052 8876
In Compliance with EU 1254/14 - Annex IV
TABLE OF COMPLIANCE WITH REGULATIONS EU 1253/14
AND EU 1254/14
Summary of Contents for ENY-SP-180
Page 2: ...Energy Smart...
Page 4: ...Energy Smart 2...
Page 17: ...15 Energy Smart...
Page 25: ...23 Energy Smart Vertical Version ENY SP and ENY S Versions 12 5 4 3 2 1 11 10 9 8 7 6...
Page 45: ...43 Energy Smart Horizontal Version Pro ENY SHP 150 Version 3 1 2 7 9 11 10 4 6 8 5...
Page 47: ...45 Energy Smart Horizontal Version Pro ENY SHP 170 Version 1 2 3 5 4 3 7 10 9 11 5 6 8...
Page 49: ...47 Energy Smart Horizontal Version Pro ENY SHP 270 Version 1 2 3 4 7 10 9 11 5 6 8...