T-EP TOUCH CONTROL
Introduction
This device was designed for the control of controlled
mechanical ventilation units. It is suitable for ENERGY
SMART units.
The Main Screen on the control panel permits access
to two settings sub-menus:
1. USER Settings Menu where the user can select the
operating mode and set the clock;
2. TECHNICAL Settings Menu where the installer can
calibrate the flow rate, change the standard unit op-
erating parameters and monitor the operating state.
On the main screen, the user can view alarm reports
and readings of the environmental temperature and
humidity.
The USER Settings Menu offers these options:
1. Manual selection of the following preset ventilation
modes:
a)
Party Mode
-
Intensive timed ventilation (pp. 91)
b)
Holiday Mode
- Permanent or timed anti-mould
ventilation (pp. 91)
2.
Automatic Mode
(pp. 89)
3.
Manual
Mode
- Customised selection of desired
air flow rate in manual mode (pp. 89):
a) 100% - Nominal ventilation (standard)
b) 70% - Reduced ventilation (nighttime)
c) 45% - Humidity Control for High Humidity Rate
Environments
d) 25% - Humidity Control for Low Humidity Rate
Environments
4.
Weekly Programming
(pp. 92).
5.
Weekly programming coupled with Automatic
Mode
(pp. 93).
6.
Free-Cooling Mode
- Customised selection of
bypass operating mode (pp. 94).
The MAIN SCREEN features the following op-
tions:
1. The preheating icon indicates activation of Anti-
freeze Mode.
2. A timed warning icon lights up to suggest filter
replacement.
3. A damper bypass icon indicates automatic activation
of free-cooling mode.
4. Weekly Program set
4
.
4
The 4 Weekly Programs can be set by the installer and
another 4 weekly programs can be set up according to the
user’s specific requirements.
The User Settings menu allows the user to enable or disable
the Weekly Program configured by the installer.
The TECHNICAL Menu offers these options:
1. Option of confirming or editing the operating pa-
rameters.
2. Monitoring of work conditions.
3. Setting the nominal calibration flow rate of the fans.
4. Input and Selection of the Weekly Program available
to the user.
Extracted stale air
temperature
Display (T3)
DAY
°C
T3