81
English
set the nominal pro-
ject flow rate (m
3
/h)
from the
TOUCH PAD
+
_
.
Press the Enter key to confirm
.
• COMMISSIONING
Once the unit has been installed
and powered and the T-EP control
has been connected, it is possible
to
SET THE FAN AIR FLOW RATE.
Once the unit has been installed and
powered, the air flow rate must be set.
Before carrying out the calibration, the fans are
set to the default flow rate
ATTENTION: If no flow rate calibration procedure
is carried out, the machine will operate using the
default flow rate as the calibration flow rate for
both fans. The default flow rate corresponds to the
reference value with respect to EU Reg. 1253/14 and
is equal to 190 m3/h.
• SETTING THE FAN AIR FLOW RATE
“
TECHNICAL”
MENU
The
“
TECHNICAL
”
menu must only be
used by the installer or by qualified
personnel.
2. Press the ON/OFF and “M” Menu keys at the
same time to access the
TECHNICAL MENU
.
3. Use the
TOUCH PAD
to select the technical
menu
.
Press the Enter key to confirm
.
Select the “
V
” symbol and confirm
.
The message V1 flashes;
Perform the setting of fan V1;
access the menu by pressing enter, the display
shows:
The control displays flashing “ V2 ”; confirm with
enter
.
set the nominal pro-
ject flow rate (m
3
/h)
from the
TOUCH PAD
+
_
.
When fan V2 has been set as well, go back to the
main screen by pressing “M”
3 times.
For fan V2, the same flow rate set for fan “V1” is
suggested by default.
To differentiate the extraction fan “V2” from intake
fan “V1”, repeat the same procedure for setting the
flow rate described for “V1”.
1. Turn the unit on from the ON/OFF key on the
display.
VV
VV
VV