Mounting and Installation

Devices are to be connected under dead-voltage condition. Devices must 
only be connected to safety extra-low voltage. Consequential  damages 
caused by a fault in this device are excluded from warranty or liability. 
Installation of these devices must only be realized by authorized qualified 
personnel. The technical data and connecting conditions shown on the 
device labels and in the mounting and operating instructions delivered 
 together with the device are exclusively valid. Deviations from the cata-
logue representation are not explicitly mentioned and are possible in 
terms of technical progress and continuous improvement of our pro-
ducts. In case of any modifications made by the user, all warranty claims 
are  forfeited. Operating this device close to other devices that do not 
comply with EMC directives may influence functionality. This device must 
not be used for monitoring applications, which solely serve the purpose 
of protecting persons against hazards or injury, or as an EMERGENCY 
STOP switch for systems or machinery, or for any other similar safety-
relevant purposes.
Dimensions of enclosures or enclosure accessories may show slight 
tolerances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original pack-
ing will be accepted.
Our “General Terms and Conditions for Business“ together with the 
“General Conditions for the Supply of Products and Services of the 
Electrical and Electronics Industry“ (ZVEI conditions) including supple-
mentary clause “Extended Retention of Title“ apply as the exclusive 
terms and conditions“.

Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations and 
standards applicable for the place of measurement (e.g. such as welding 
instructions, etc.). Particularly the following shall be regarded:
– VDE  ⁄  VDI directive technical temperature measurements, measure-

ment set - up for temperature measurements.

– The EMC directives must be adhered to. 
– It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with the shielding being 

 attached at one side to the DDC  ⁄  PLC.

Before mounting, make sure that the existing thermometer‘s technical 
parameters comply with the actual conditions at the place of  utilization, 
in particular in respect of:
– Measuring range 
– Permissible maximum pressure, flow velocity 
– Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

CONNECTING CONDITIONS

Output:   0  - 10  V
The output voltage follows linear to the temperature signal applied at  
the input terminals and generates a proportional output signal of 0 - 10 V. 
The voltage outputs are short-circuit proof against ground wire. Applying 
voltage supply to the output terminals will destroy the device.

Output:   4 ... 20 mA
In case of the 4 ... 20 mA measuring transducer, display and evaluating 
 elements are connected in series in the current loop. The measuring 
transducer thereby liWiths the flowing current in variance of the input 
signal. 4 mA are for the measuring transducer‘s internal current con-
sumption. The apparent ohmic resistance can either be connected in the 
plus or minus path of the measuring transducer. In case of an apparent 
ohmic resistance in the plus path, power supply and resist.

SAFETY REGULATIONS
These devices shall only be used for their intended purpose. Respective 
safety regulations issued by the VDE, the states, their control authori-
ties, the TÜV and the local energy supply company must be observed. The 
buyer has to ensure adherence to the building and safety regulations and 
has to avoid all dangers of any kind. We do not assume any warranty for 
faults or damages arising or resulting from improper use of our equip-
ment or from non-observance of operating instructions. These instru-
ments must be installed by authorised specialists only!

Preferably shielded cables should be used in order to prevent damages  ⁄  
errors. It is imperative to avoid laying parallel with current-carrying 
lines. EMC directives must be adhered to.

G  

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 
and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 
be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed by authorised specialists only.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively 

valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Summary of Contents for THERMASGARD HSM

Page 1: ...haltung und aktivem Ausgang G Operating Instructions Mounting Installation Top hat rail measuring transducers for temperature with multi range switching and active output F Notice d instruction Conver...

Page 2: ...THERMASGARD HSM D G F r Ma zeichnung HSM Dimensional drawing Plan cot 45 75 25 45 53 45 53 1 2 3 4 5 6 7 8...

Page 3: ...4 V DC Eingang Pt100 Pt100 Pt1000 Pt1000 Messstrom 0 25 mA 0 25 mA Nullpunkt 200 830 C 200 830 C Spanne 20 C 20 C F hlerbruch 10 V 20 mA Kurzschluss 0 V 4 mA zul ssige Restwelligkeit 10 10 Ausgang 0 1...

Page 4: ...hlussstrom kann zur Besch digung dieses Ger tes f hren Achten Sie daher auf die korrekte Verdrahtung Schaltung Schaltung 0 10V 0V GND 0 10V 0V GND Versorgung mit AC 24V 0V DC 15 36V GND AC 24V 0V DC 1...

Page 5: ...nleitung Abweichungen zur Katalogdarstellung sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger...

Page 6: ...24 V DC Input Pt100 Pt100 Pt1000 Pt1000 Testing current 0 25 mA 0 25 mA Zero point 200 830 C 200 830 C Range 20 C 20 C Sensor breakage 10 V 20 mA Short circuit 0 V 4 mA Residual ripple permissible 10...

Page 7: ...attention to correct wiring Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND G Measuring transducers cal...

Page 8: ...supply and resist SAFETY REGULATIONS These devices shall only be used for their intended purpose Respective safety regulations issued by the VDE the states their control authori ties the T V and the l...

Page 9: ...ation lectrique 0 2 VA 0 55 VA 24 V ca cc 24 V cc Entr e Pt100 Pt100 Pt1000 Pt1000 Courant de mesure 0 25 mA 0 25 mA Point z ro 200 830 C 200 830 C Plage 20 C 20 C Rupture de sonde 10 V 20 mA Court ci...

Page 10: ...e terrain peut endommager cet appareil Veillez donc au raccordement correct des fils Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power s...

Page 11: ...nders de leurs organes de surveillance du T V et des entreprises d approvisionnement en nergie locales sont respecter L acheteur doit respecter les dispositions relatives la construction et la s curit...

Page 12: ...0 Pt 1000 Pt 1000 0 25 0 25 200 830 C 200 830 C 20 C 20 C 10 20 0 4 10 10 0 10 4 20 Ra 3 UB 12 0 02 A 0 1 0 1 40 85 C 40 85 C 2TE 75 x 25 x 53 RAL 6029 III EN 60 730 IP 20 EN 60 529 CE EN 61 326 A1 A2...

Page 13: ...ND r 4 20 A 4 20 A 15 36 B 10 4 20 0 3 B Ra Ub 14 B 0 02 A Ub 0 10 B 24 B 20 5 0 4 K 25 C 0 8 K 30 70 C DIN IEC 751 0 3 CE EN 61 326 2006 2004 108 EC 30 70 C c Ia A 12 10 8 6 4 2 0 0 1 5 0 5 2 5 3 5 4...

Page 14: ...r EMV ZBEI VDE VDI DDC PLC 0 5 g 0 10 0 10 4 20mA 4 20 4 VDE r ZVEI VDE EMV...

Page 15: ...hniques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S...

Page 16: ...Pt 100 1 3 4 8 7 6 230 VAC 24 VDC PLC PC Pt 100 Messbereiche einstellbar Measuring ranges adjustable Plages de mesure r glables DIP 1 DIP 2 DIP 3 DIP 3 20 C 150 C O N O N O N O N 0 C 50 C OFF O N O N...

Reviews: