START-UP OVERRIDE 

There are application scenarios in which fan motors and measuring instruments are switched off and on again.  
When switched on, the fans take a few seconds to build up a flow.  
During this start-up time, the GLT could switch to fault mode (lack of flow). 

In the 

KLGFxx

 / 

KLSWxx

 (without display), the start-up override (60 s) is activated by a DIP switch.

In the 

KLGFxx LCD

 / 

KLSWxx LCD

 (with display) and in the 

KLGFT

 / 

KLGFVT LCD

,  

the start-up override (0...120 s) is activated and adjusted by a potentiometer.

After the supply voltage is switched on, a flow of 20 m/s or greater than the set switching threshold during  
this start-up time is assumed and the output signal is increased to 10 V or the relay is switched, depending on the type. 

After the start-up time has elapsed, the unit switches to normal measuring mode,  
in unit types without a changeover contact, a voltage proportional to the measured value is output, 
in unit types with a changeover contact, the relay switches according to the measured value < switching threshold  
or measured value > switching threshold.  

SWITCHPOINT 

In unit types with a changeover contact, the switching point (0.1...20 m/s) is adjusted by a potentiometer. 

OTHER PARAMETERS 

In the 

KLGFT

 / 

KLGFVT LCD

, the 

temperature

 is captured by another sensor (NTC 10k). 

In the 

KLGFVT LCD

, the alternative parameter 

Volume Flow

 is calculated internally.  

This value can be shown instead of the flow in the display. The switching is menu-controlled on the display.

RHEASGARD

®

  KLGFxx  ⁄  RHEASREG

®

  KLSW xx 

Rev.  Data - V35

Type ⁄ WG01 

Power

supply

Output 

active

Output

switching

other

 

Display

Parameters

Item no.

KLGF

U Variant

KLGF-U

24 V AC ⁄ DC

1x 

0 -10 V

1701-4111-0101-000

KLGF-U 

LCD

24 V AC ⁄ DC

1x 

0 -10 V

–   

1701-4111-1101-000

Optional:  

Cable connection with 

M12 connector

 as per DIN EN 61076-2-101  

on request

KLGF

(

V

)

T

AOS

KLGFT-W

24 V AC ⁄ DC

2x 

0 -10 V ⁄ 4...20 mA

1 changeover contact  

T

1701-4118-0201-001

KLGFVT-W LCD

24 V AC ⁄ DC

2x 

0 -10 V ⁄ 4...20 mA

1 changeover contact  

T | V

 

1701-4118-1401-001

KLSW-W24

KLSW-W24

24 V AC ⁄ DC

1 changeover contact – 

1701-4113-0101-001

KLSW-W24 

LCD

24 V AC ⁄ DC

1 changeover contact –   

1701-4113-1101-001

KLSW-W230

KLSW-W

230

230 V

 AC

1 changeover contact –  

1701-4133-0101-001

Note: 

 Changeover  contact

 with automatic reset  

(relay opens automatically when value falls below the threshold again)

 

AOS 

(

Automatic Output Switching

) = patented analogue interface (patent no. DE 10 2015 015 941 B4), 

 

the unit automatically detects the required output type 0 - 10 V or 4...20 mA

temperature

 (0...+50 °C) – additional measurand 

volume flow

 (0...200,000 m³/h) – alternative parameter, can be configured via display!

Summary of Contents for RHEASGARD KLGF Series

Page 1: ...ctronic with active switching output F Notice d instruction Capteur de d bit d air pour montage en gaine contr leur de d bit d air y compris bride de montage lectronique avec sortie active tout ou rie...

Page 2: ...90 50 20 32 3 13 4 20 60 87 30 32 62 M4 5 2 20 M16x1 5 20 M16x1 5 112 4 MFT 20 K Montageflansch aus Kunststoff Mounting flange plastic Bride de montage en mati re plastique KLSW W230 200 126 112 90 5...

Page 3: ...yp und schaltet automatisch auf U oder I Ausgang um Wechselkontakt 24 V max 5 A cos 1 0 Schalthysterese 2 EW Schwellwert ber Potentiometer einstellbar KLSW W24 Wechselkontakt 24 V max 5 A cos 1 0 Scha...

Page 4: ...ENNGR SSEN Beim KLGFT KLGFVT LCD wird ber einen weiteren Sensor NTC 10k die Temperatur erfasst Beim KLGFVT LCD wird intern die alternative Kenngr e Volumenstrom berechnet Dieser Wert kann anstatt der...

Page 5: ...g Taster Nullpunkt setzen 0m s DIP Anlauf berbr ckung 60s off default 12 11 13 1 2 3 UB 24V AC DC UB GND frei ffner Schlie er Wurzel Anschlussbild Anschlussbild KLSW W24 ohne Display KLSW W230 ohne Di...

Page 6: ...GFVT W LCD KLGFT W KLSW W24 LCD 12 11 13 1 2 3 4 UB 24V AC DC UB GND ffner Schlie er Wurzel frei frei 1 2 3 4 UB 24V AC DC UB GND Ausgang 0 10V Str mung frei KLGFVT W LCD Umschaltung von Messgr e Str...

Page 7: ...7 D Montage KLGF xx KLSW xx Einbauschema 5x d 3x d 115 mm d Montagehinweis Sensor arbeitet unidirektional Markierungen zur Str mungsrichtung beachten...

Page 8: ...ll die mechanischen und thermischen Belastungsgrenzen der Schutzrohre nach DIN 43763 bzw nach speziellen S S Standards D Montage und Inbetriebnahme Schaltbild Parallelbetrieb Schaltbild Einzelbetrieb...

Page 9: ...der zum Ger t gelieferten Montage und Bedienungs anleitung Abweichungen zur Katalogdarstellung sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung...

Page 10: ...via potentiometer KLSW W24 changeover contact 24 V max 5 A cos 1 0 switching hysteresis 2 final value threshold can be adjusted via potentiometer KLSW W230 changeover contact 230V AC max 5 A cos 1 0...

Page 11: ...METERS In the KLGFT KLGFVT LCD the temperature is captured by another sensor NTC 10k In the KLGFVT LCD the alternative parameter Volume Flow is calculated internally This value can be shown instead of...

Page 12: ...60s off default Relay Pushbutton DIP 12 11 13 1 2 3 UB 24V AC DC free UB GND NC Normally Closed NO Normally Open M Common Connecting diagram Connecting diagram KLSW W24 without display KLSW W230 witho...

Page 13: ...GFT W KLSW W24 LCD 12 11 13 1 2 3 4 UB 24V AC DC NC Normally Closed NO Normally Open M Common UB GND free free 1 2 3 4 UB 24V AC DC UB GND Output 0 10V Flow velocity free KLGFVT W LCD Switching from f...

Page 14: ...14 G Installation KLGF xx KLSW xx Mounting diagram 5x d 3x d 115 mm d Note when mounting Sensor works unidirectional Observe the markings for the direction of flow...

Page 15: ...fore pay attention to correct wiring Notes for mounting Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement e g such as welding ins...

Page 16: ...uctions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuou...

Page 17: ...quement sur la sortie U ou I contact inverseur 24 V max 5 A cos 1 0 hyst r sis de commutation 2 Vf valeur seuil r glable par potentiom tre KLSW W24 contact inverseur 24 V max 5 A cos 1 0 hyst r sis de...

Page 18: ...utation 0 1 20 m s se fait l aide d un potentiom tre AUTRES PARAM TRES Pour le KLGFT KLGFVT LCD la temp rature est relev e l aide d un capteur suppl mentaire NTC 10k Pour le KLGFVT LCD le param tre al...

Page 19: ...ing 60s off default Relay Pushbutton DIP 12 11 13 1 2 3 UB 24V AC DC free UB GND NC Normally Closed NO Normally Open M Common Sch ma de raccordement Sch ma de raccordement KLSW W24 sans cran KLSW W230...

Page 20: ...D KLGFT W KLSW W24 LCD 12 11 13 1 2 3 4 UB 24V AC DC NC Normally Closed NO Normally Open M Common UB GND free free 1 2 3 4 UB 24V AC DC UB GND Output 0 10V Flow velocity free KLGFVT W LCD le passage d...

Page 21: ...21 F Montage KLGF xx KLSW xx Sch ma de montage 5x d 3x d 115 mm d Instructions de montage Le capteur fonctionne unidirectionnel Respectez les marquages pour le sens d coulement...

Page 22: ...V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND Consignes de montage L installation doit tre effectu e en conformit avec les r glementations...

Page 23: ...u es sur la notice d instruction accompagnant l appareil sont applicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au...

Page 24: ...U KLGF V T 2 0 10 4 20 Automatic Output Switching U I 24 5 A cos 1 0 2 KLSW W24 24 5 A cos 1 0 2 KLSW W230 230 5 A cos 1 0 2 0 1 20 0 5 3 0 5 1 0 2 60 0 60 c KLGF KLSW DIP 0 120 c KLGF KLSW KLGFT KLG...

Page 25: ...1 4111 0101 000 KLGF U LCD 24 1 0 10 1701 4111 1101 000 M12 DIN EN 61076 2 101 KLGF V T AOS KLGFT W 24 2 0 10 4 20 1 T 1701 4118 0201 001 KLGFVT W LCD 24 2 0 10 4 20 1 T V 1701 4118 1401 001 KLSW W24...

Page 26: ...zero point setting 0m s DIP start bridging 60s off default Relay Pushbutton DIP 12 11 13 1 2 3 UB 24V AC DC free UB GND NC Normally Closed NO Normally Open M Common KLSW W24 KLSW W230 12 11 13 1 2 N L...

Page 27: ...KLGFVT W LCD KLGFT W KLSW W24 LCD 12 11 13 1 2 3 4 UB 24V AC DC NC Normally Closed NO Normally Open M Common UB GND free free 1 2 3 4 UB 24V AC DC UB GND Output 0 10V Flow velocity free KLGFVT W LCD 1...

Page 28: ...28 r KLGF xx KLSW xx 5x d 3x d 115 mm d...

Page 29: ...10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND VDE VDI 100 0 5 5 d 3 d DIN 437...

Page 30: ...30 ZVEI VDE EMV r...

Page 31: ...ed We warrant the faultless quality of our products as stated in our General Terms and Conditions Sous r serve d erreurs et de modifications techniques Toutes les informations correspondent l tat de n...

Page 32: ...beachten Note when mounting Sensor works unidirectional Observe the markings for the direction of flow Instructions de montage Le capteur fonctionne unidirectionnel Respectez les marquages pour le se...

Reviews: