14
G
PREMASREG
®
711x
1. For zero point setting, the device must be in operation for
at least 60 minutes.
2. Connect pressure inputs P (+) and P (–) with a hose.
(Pressure difference between the inputs = 0 Pa).
3. For zero point setting, press pushbutton uninterrupted for 10 seconds.
By pressing the pushbutton, a countdown of ca. 10 seconds is started.
The yellow LED is blinking and the countdown is shown on the display.
Zero point calibration takes place after the countdown period.
This is indicated by continuous LED light and at the display by switching from
"AUTO 0" to "PROG 0".
Note: By releasing the pushbutton during the countdown
(counter > 0), zero point setting is immediately cancelled!
Automatic offset setting:
1
2
3
12
11
13
AUTO
ZERO
SET
min. max.
OFFSET
1 2 3 4 5 6
ON DIP
Pushbutton
Zero point setting
SET-Setting relay
switchpoint
Plug for
display
Offset correction
ca. ±10 % of final value
Cont
act
pin side
The 1
st
line in the display shows the
actual pressure
.
The 2
nd
line shows the
unit
pascal (Pa).
The 3rd line shows the information regarding the
switching status of the relay
(as a circuit) on the left side,
as well as the respective
switching value
Pa on the right side.
The switchpoint can be adjusted via the "SET" potentiometer.
This depends on the adjusted measuring range.
Please note that the switchpoint is displayed without a comma
for the 25 Pa variant (e.g. 100 = 10.0 Pa)
Display readout:
Manual offset adjustment:
Automatic zero point calibration (optional):
The offset potentiometer functions additionally and
independently for automatically setting the zero point.
With the OFFSET potentiometer, a deviation outside of the zero
point can be aligned.
The range for adjustment is ca. ± 10 % of the pressure range.
A
zero point calibration
is carried out cyclically via an internal
valve.
Cycle time (approx. 90 minutes) is fixed in the factory.
During the automatic calibration, the output value remains at
its last pressure value.
Zero point calibration
active
Remaining
calibration time
(in seconds)
○
Circle empty
= relay in idle state
●
Circle solid
= relay activated