background image

Installation Guide

Pressure 

Z202882-0U 

Page 1 of 4 

©2013 Veris Industries   

 06131 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

TM

NOTICE 

•  This product is not intended for life or safety applications.

•  Do not install this product in hazardous or classified locations.

•  Read and understand the instructions before installing

 

this product.

•  Turn off all power supplying equipment before working on it.

•  The installer is responsible for conformance to all applicable codes.

 

No responsibility is assumed by Veris Industries for any consequences arising out of the 

use of this material.

Product Identification

Product Overview

The PW Series pressure transducer measures the differential pressure across pumps, filters, heat exchangers, and 
other non-corrosive wet media. Several operational pressure ranges are available, and the analog output is user 
selectable (4-20 mA, 0-5 V, or 0-10 V). PW Series devices are warranted to meet accuracy specifications for a period 
of five years.

PW Series

Wet Media Differential Pressure Transducer

available

Local Display

L = LCD Display
X = No Display

NIST

N = NIST
X = None

US or EU

S = Standard

3

C = CE

Operational Range 

1

03 = 0-50 psig
04 = 0-100 psig
05 = 0-250 psig
06 = 0-3.5 barg

2

07 = 0-7.0 barg

2

08 = 0-17 barg

2

PW

1

 Select operational range according to maximum gauge pressure, NOT differential pressure.

   Example:  High gauge pressure=90 psig, Select 100 psig model (04).

2

 barg models use BSPT threads on sensor fittings.

Not available with barg units.

Summary of Contents for PWXN07C

Page 1: ...equences arising out of the use of this material Product Identification Product Overview The PW Series pressure transducer measures the differential pressure across pumps filters heat exchangers and other non corrosive wet media Several operational pressure ranges are available and the analog output is user selectable 4 20 mA 0 5 V or 0 10 V PW Series devices are warranted to meet accuracy specifi...

Page 2: ...to 85 C 4 to 185 F Operating Environment 10 to 55 C 14 to 131 F 10 90 RH noncondensing Long Term Stability 0 25 Zero Adjust Pushbutton auto zero and digital input 2 position terminal block Fittings psig models 1 8 NPT female thread stainless steel 17 4 PH barg models 1 8 BSPT female thread stainless steel 17 4 PH Physical White powder coated aluminum PRESSURE RANGES 0 50 psig 5 10 25 50 psid 0 100...

Page 3: ... psi 100 psi 50 psi 50 psi 0 psi LO PORT 0 psi 50 psi 50 psi 100 psi 100 psi 4 20mA 0 10V 100 psi 50 psi 0 psi 50 psi 100 psi Bidirectional Operation Input Conditions Result Outputs Read DP 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V 17 0 bar 17 0 bar 8 5 bar 8 5 bar 0 bar 0 bar 8 5 bar 8 5 bar 17 0 bar 17 0 bar 17 0 bar 8 5 bar 0 bar 8 5 bar 17 0 bar 20mA 16mA 12mA 8mA 4mA 10V 7 5V 5V 2 5V 0V Outp...

Page 4: ... is read from the low port and the value is usually a negative number This product uses a half wave rectifier power supply If the installer is using a transformer to power the device do not use the same transformer to power other devices utilizing non isolated full wave power supplies Optional Connect the Zero terminals to the digital output contact closure of the control system The Zero input is ...