S+S Regeltechnik AERASGARD KLQ-CO2 Operating Instructions, Mounting & Installation Download Page 7

G  

Mounting and Installation

Automatic calibration of air quality (default)
The  minimum  initial  value  for  air  quality  is  memorized  within  a  period  of  ca.  4 
weeks.  After  that  period  has  lapsed,  the  output  signal  is  standardised  to  zero-
point (1.0 V). The maximum amount of correction is thereby limited to 1 V  ⁄  interval. 
In  this  way,  long-term  drifts  and  operational  aging  effects  of  the  sensor  element 
are completely eliminated. 

Manual calibration of air quality
Manual  calibration  can  be  started  independently  from  the  position  of  jumper  J2 
by  pushing  the  button.  After  connecting  the  device,  a  period  of  at  least  2  hours  
of  continuous  operation  of  the  device  at  “normal“  air  quality  is  to  be  ensured. 
Manual  calibration  of  the  output  signal  to  1 V  (zero-point)  is  started  by  pressing 
the  button  “Manual  calibration“  (for  ca.  5  seconds).  Preparing  for  calibration  is 
indicated by a blinking LED. Setting the output to 1 V at actual ambient conditions 
follows  automatically  thereafter.  During  this  phase,  the  LED  is  permanently  acti-
vated. After calibration is completed, the LED is deactivated.

General information of air quality
Due  to  its  functional  principle,  the  lifetime  of  the  sensor  depends  on  nature  and 
concentration  of  the  pollutant  gas  burden.  The  sensitive  layer  of  the  sensor 
element reacts with all volatile organic compounds and is thereby modified in its 
electrical properties or “exhausted“. This process results in a displacement of the 
characteristic  curve.  Such  characteristic  curve  displacement  however  amounts 
to less than 15 %   ⁄  year under normal burden. In measuring air quality, the general condition of air quality is detected. Whether air quality is “good“ 
or “bad“ is differently interpreted by each person. Different pollution burdens and concentrations influence the air quality signal (0 ...10 V) in different 
ways. Examples for this are cigarette smoke, deodorant sprays, cleaning agents, or also various adhesive materials for floor and wall coverings as 
well  as  dyestuffs.  Increased  burdens  e.g.  by  solvents,  nicotine,  hydrocarbons,  aerosol  propellants  etc.  intensify  consumption  ⁄ aging  of  the  sensor 
element. Particularly under high pollutant gas burdens – also during non-operational idle state periods of the devices (transport and storage) – zero-
point drift will occur. Consequently, this must be corrected at site according to the respective circumstances or basic burdens. Air quality measuring 
instruments of different manufacturers cannot directly be compared because of different functional principles, preset basic burdens (zero-point), 
and permitted burdens (amplification  ⁄ sensitivity). Devices are preset respectively calibrated according to the sensor manufacturer‘s specifications. 
Here, a zero-point and a final value is determined and thus a maximum burden. In particular cases, exceeding measuring ranges or excessive basic 
burdens on the devices will occur (outgassing floor carpeting, wall paint, etc.). In order to enable distinguishing different air qualities, devices need to 
be adjusted by the customer according to the conditions existing on site that do not correlate to the factory-preset definition range and calibration. 
Please note that factory calibration is thereby lost and compliance with technical data can no longer be guaranteed.

Automatic calibration of carbon dioxide measurement (default)
The device calibrates itself at an interval of 7 days. To ensure this function, the device needs to be supplied with fresh air (CO

2

 content 300 ppm ... 

400 ppm) at least for 10 minutes during each 7- day period. For self-calibration, the devices memorises device-internally the CO

2

 content minimum 

value measured during a 7- day period. After 7 days, this minimum value is standardised to 350  ppm CO

2

 and the output signal is corrected accord-

ingly. The maximum amount of correction is here limited to 40 ppm  ⁄  interval.

Manual calibration of carbon dioxide measurement 
Manual calibration can be started independently from the position of jumper J3 by pushing the button. After connecting the device, a period of at 
least 10 minutes of continuous operation of the device at fresh air (CO2 content 300 ppm...400 ppm) is to be ensured. Manual calibration of the 
output signal to 1.75 V (350 ppm = zero-point) is started by pressing the button “Manual calibration CO

2

 “ (for ca. 5 seconds). Preparing for calibra-

tion is indicated by a blinking LED. Setting the output to 1.75 V at actual ambient conditions follows automatically thereafter. During this phase, the 
LED is permanently activated. After calibration is completed, the LED is deactivated. Air quality is measured by a chemical sensor.

VOC   
(sensitivity adjustable)

JP  

1 

JP  

2 

JP  

3 

VOC LOW

VOC MEDIUM  (default)

VOC HIGH

CO

2

 content 

(measuring range adjustable)

JP  

1 

JP  

2 

JP  

3 

0 … 2000 ppm  (default)

0 … 5000 ppm

0 … 10000 ppm

Type ⁄ WG1 

Measuring Range 

Output 

Features 

 

VOC 

CO

2

   (switchable) 

KLQ - CO

2

0 …100 %  

0 … 2000 ppm  ⁄  0 … 5000 ppm  ⁄  0 … 10000 ppm 

0  - 10 V 

KLQ - CO

2

 - W 

0 …100 %  

0 … 2000 ppm  ⁄  0 … 5000 ppm  ⁄  0 … 10000 ppm 

0  - 10 V 

1x Changeover contact

xx - Display

Note: 

This unit must not be used as safety-relevant device!

Summary of Contents for AERASGARD KLQ-CO2

Page 1: ...h G Operating Instructions Mounting Installation Duct air quality VOC and CO2 sensors respectively measuring transducers self calibrating with multi range switching and active output including mountin...

Page 2: ...AERASGARD KLQ CO2 D G F r Ma zeichnung KLQ CO2 Dimensional drawing Plan cot...

Page 3: ...freiem Wechsler 24 V Messgenauigkeit Luftg te 20 EW bezogen auf das Kalibriergas Lebensdauer 60 Monate unter Normalbelastung Spannungsversorgung 24V AC DC KOHLENDIOXID CO2 Sensor CO2 optischer Sensor...

Page 4: ...ngestellten Grundbelastung Nullpunkt und der zugelassenen Belastung Verst rkung Empfindlichkeit nicht direkt mit einander verglichen werden Die Ger te werden nach den Vorschriften des Sensorhersteller...

Page 5: ...ung sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew...

Page 6: ...otential free changeover contact 24 V Measuring accuracy VOC 20 of final value referred to calibrating gas Service life 60 months under normal load conditions CARBON DIOXIDE CO2 CO2 sensor optical sen...

Page 7: ...ifferent manufacturers cannot directly be compared because of different functional principles preset basic burdens zero point and permitted burdens amplification sensitivity Devices are preset respect...

Page 8: ...om the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve ment of our products In case of any modifications made by the user a...

Page 9: ...nsibilit COV faible moyenne lev e Sortie qualit d air 0 10 V 0V air propre 10V air pollu ou avec inverseur libre de potentiel 24 V Incertitude de mesure qualit d air 20 Vf se r f rant au gaz de calibr...

Page 10: ...oint z ro et de la contrainte homologu e renforcement sensibilit les appareils de mesure de qualit de l air ne peuvent pas tre compar s directement l un avec l autre Les appareils sont r gl s et ou ta...

Page 11: ...t applicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produit...

Page 12: ...EN 61 326 A1 A2 2004 108 EC 8 36 x 14 x KLQ CO2 KLQ CO2 W 1 2 3 4 UB GND UB supply voltage 24V AC DC Output 0 10V CO2 content in ppm Output 0 10V air quality VOC 1 2 3 4 5 6 7 UB GND UB supply voltage...

Page 13: ...40 ppm J3 10 300 400ppm 1 75 350ppm CO2 5 1 75 VOC JP 1 JP 2 JP 3 VOC LOW VOC MEDIUM VOC HIGH CO2 JP 1 JP 2 JP 3 0 2000 pp 0 5000 pp 0 10000 pp 1 VOC CO2 KLQ CO2 0 100 0 2000 pp 0 5000 pp 0 10000 pp...

Page 14: ...4 20 0 10 10 95 0 50 C ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 3...

Page 15: ...chniques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S...

Page 16: ...AERASGARD KLQ CO2 D G F r...

Reviews: