S+S Regeltechnik AERASGARD KFTM-CO2-W Operating Instructions, Mounting & Installation Download Page 16

16

G  

General notes

–  This device may only be used in pollutant-free non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor  element. 
–  On outdoor and duct sensors, the sinter filter of the senor element protects the humidity sensor against potential dust exposure.  

In case of pollution  ⁄  contamination, this filter should be cleaned on a regular basis.

–  Dust and pollution falsify measurement results and are to be avoided. Slight pollution and dust sediments can be removed by using compressed air. 
–  Touching the humidity element is under any circumstances to be avoided, as that would result in considerable mismeasurements.
–  In case of pollution, we recommend cleaning and recalibration in the factory.
–  In any case, the sensor must not get in contact with chemicals or other cleaning agents.
–  Extremely high concentrations of VOCs, aggressive cleaning agents or silicone-containing vapours can destroy the sensor element or  

reduce its service life drastically.

–  The air quality signal “good“...“bad“ is represented by the output signal 0 -10 V or 4...20 mA.
–  The device operating range covers 10 ... 95 % relative humidity respectively –35...+80 °C. 

Beyond that range, mismeasurements or increased deviations will occur. 

–  The chemical sensor is a consumable. The lifetime of the sensor depends on nature and concentration of the pollutant gas burden.
–  When several sensors are connected to one voltage supply of 24 V  AC, correct polarity must be regarded as otherwise the  alternating  voltage source 

may be short-circuited. 

–  The outputs are short-circuit proof. Applying overvoltage or voltage supply to the output will destroy the device.
–  If the automatic system (automatic balancing of CO2 / VOC measurand) is activated, a cyclical fresh air supply must be provided,  

as otherwise incorrect measurements can occur.

–  The device must be permanently energized to measure the CO2 and VOC concentration correctly.
–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities,  

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent 
perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed and commissioned by authorised specialists.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid.   

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous  
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow.  

Direct sun irradiation or heat  irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of housings or housing accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

Notes on commissioning: 

This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an 
initial manual adjustment on-site during commissioning and subsequently at regular intervals. 

Commissioning is mandatory and may only be performed by qualified personnel! 

 

These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

Notes regarding mechanical mounting and attachment:

Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding instructions, 
etc.). Particularly the following shall be regarded:
–  VDE ⁄ VDI directive technical temperature measurements, measurement set - up for temperature measurements.
–  The EMC directives must be adhered to.
–  It is imperative to avoid parallel laying of current-carrying lines.
–  We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC. 
Before mounting, make sure that the measuring device technical parameters comply with the actual conditions at the place of utilization, in particular in 
respect of:
–  Measuring range
–  Permissible maximum pressure, flow velocity, temperature and humidity
–  Protection type and Protection class
–  Installation length, tube dimensions
–  Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

Attention! In any case, please observe the mechanical and  thermal load limits of the protective tubes according to DIN 43763 or according to specific 
S+S standards!

Summary of Contents for AERASGARD KFTM-CO2-W

Page 1: ...incl mounting flange for humidity temperature CO2 content and air quality VOC calibratable with active switching output F Notice d instruction Sonde transmetteur de gaine multifonctionnelle y compris...

Page 2: ...202 5 126 112 90 50 20 112 20 4 32 3 13 4 M16x1 5 60 87 30 32 62 M4 5 2 20 M16x1 5 MFT 20 K Montageflansch aus Kunststoff Mounting flange plastic Bride de montage en mati re plastique SF K Kunststoff...

Page 3: ...eingestellt Kxx CO2 W 0 10 V oder 4 20 mA B rde 800 ber DIP Schalter w hlbar gew hlte Variante gilt einheitlich f r alle Ausg nge mit Offset Potentiometer 10 vom Messbereich Relais Ausgang KTM CO2 SD...

Page 4: ...er Ist Feuchte Ist Temperatur Luftqualit t und oder des Ist CO2 Gehaltes ZUBEH R SF M Metall Sinterfilter 16 mm L 32 mm austauschbar aus Edelstahl V4A 1 4404 7000 0050 2200 100 AERASGARD KTM CO2 SD Ka...

Page 5: ...C 1 ausgezeichnet 0 19 keine Ma nahmen erforderlich 2 gut 20 39 baldige Bel ftung empfohlen 3 m ig 40 59 Bel ftung empfohlen 4 schlecht 60 79 verst rkte Bel ftung erforderlich 5 ungesund 80 100 intens...

Page 6: ...andbel ge sowie Farbstoffe Erh hte Belastungen von z B L sungsmittel Nikotin Kohlenwasser stoffe Treibgase verst rken den Verbrauch die Alterung des Sensorelementes Ins be sondere bei hohen Schadgasbe...

Page 7: ...assen 4 Nach 10 Minuten ist die Kalibrierung abgeschlossen Status LED erloschen Countdown abgelaufen und das Ger t sollte eine CO2 Konzentration zwischen 350 500 ppm anzeigen bzw bermitteln Automatisc...

Page 8: ...s f hren Achten Sie daher auf die korrekte Verdrahtung Schaltung Schaltung 0 10V 0V GND 0 10V 0V GND Versorgung mit AC 24V 0V DC 15 36V GND AC 24V 0V DC 15 36V GND Schaltung 0 10V 0V GND V Versorgung...

Page 9: ...d Sicherungsbestimmung zu gew hrleisten und Gef hrdungen aller Art zu vermeiden F r M ngel und Sch den die durch unsachgem e Verwendung dieses Ger tes entstehen werden keinerlei Gew hrleistungen und H...

Page 10: ...VA 24 V AC typical peak current 200 mA Outputs KTM CO2 SD 0 10 V fixed Kxx CO2 W 0 10 V or 4 20 mA working resistance 800 selectable via DIP switches selected variant applies for all outputs with off...

Page 11: ...ng actual humidity actual temperature air quality and or the actual CO2 content ACCESSORIES SF M Metal sinter filter 16 mm L 32 mm exchangeable stainless steel V4A 1 4404 7000 0050 2200 100 AERASGARD...

Page 12: ...IAQ Indoor Air Quality VOC 1 excellent 0 19 no action required 2 good 20 39 prompt airing recommended 3 moderate 40 59 airing recommended 4 poor 60 79 increased airing required 5 unhealthy 80 100 inte...

Page 13: ...Examples are cigarette smoke deodorant sprays cleaning agents and various adhesive materials for floor and wall coverings as well as dyes Increased levels of solvents nicotine hydrocarbons aerosol pr...

Page 14: ...now leave the room 4 After 10 minutes the calibration is complete status LED has gone out the countdown is complete and the device should indicate or transmit a CO2 concentration of between 350 500 p...

Page 15: ...ield device a supply voltage short circuit would be caused by that device The consequential short circuit current flowing through this field device may cause damage to it Therefore pay attention to co...

Page 16: ...to adhere to the building and safety regulations and has to prevent perils of any kind No warranties or liabilities will be assumed for defects and damages arising from improper use of this device Con...

Page 17: ...cc 10 Puissance absorb e 4 8 W 24 V cc typique 6 8 VA 24 V ca typique Pointe de courant 200 mA Sorties KTM CO2 SD 0 10 V r glage fixe Kxx CO2 W 0 10 V ou 4 20 mA charge 800 s lectionnable via interrup...

Page 18: ...r la temp rature effective la qualit de l air et ou la teneur en CO2 ACCESSOIRES SF M filtre fritt en m tal 16 mm L 32 mm rempla able en acier inox V4A 1 4404 7000 0050 2200 100 AERASGARD KTM CO2 SD S...

Page 19: ...int rieur Bundesgesundheitsbl Gesundheitsforsch Gesundheitsschutz 2007 50 990 1005 Journal du Minist re f d ral de la sant Recherche en sant Protection de la sant 2007 50 990 1005 Tableau d humidit pl...

Page 20: ...les produits de nettoyage ou aussi divers mat riaux adh sifs pour rev tement de sol et de mur ainsi que les colorants Les charges polluantes comme les solvants la nicotine les hydro carbures les gaz c...

Page 21: ...le faire sortir toutes les personnes de la pi ce 4 L talonnage est termin apr s 10 minutes LED d tat teintes compte rebours coul et l appareil doit indiquer une concentration en CO2 comprise entre 350...

Page 22: ...ppareil Veillez donc au raccordement correct des fils Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND R...

Page 23: ...entreprises d approvisionnement en nergie locales L acheteur doit respecter les dispositions relatives la construction et la s curit et doit viter toutes sortes de risques Nous d clinons toute respon...

Page 24: ...10 Kxx CO2 W 0 10 4 20 800 DIP 10 KTM CO2 SD Kxx CO2 W 24 1 A DIP 16 L 35 16 L 32 0 100 0 95 2 0 20 80 25 C 3 0 0 10 4 20 A DIP 35 80 C 10 60 C 0 2 K 25 C KTM CO2 SD 0 10 Kxx CO2 W 0 10 4 20 DIP VOC...

Page 25: ...CO2 W CO2 Deluxe AERASGARD KFTM LQ CO2 W VOC CO2 Deluxe WG02 CO2 VOC KTM CO2 SD KTM CO2 SD U 35 80 C 0 2000 5000 1 1501 8112 1001 200 KLQ CO2 W KLQ CO2 W 0 2000 5000 1 0 100 W 1501 8111 7301 500 KLQ...

Page 26: ...2 15 1 5 6 4 75 7 5 16 0 20 2 0 7 2 80 8 0 16 8 25 2 5 8 0 85 8 5 17 6 30 3 0 8 8 90 9 0 18 4 35 3 5 9 6 95 9 5 19 2 40 4 0 10 4 100 10 0 20 0 45 4 5 11 2 50 5 0 12 0 55 5 5 12 8 35 80 C C UA in V IA...

Page 27: ...ev 2021 V33 r CO2 350 1 1 75 0 2000 1 0 7 0 5000 1 0 10 KTM CO2 SD DIP KTM CO2 SD DIP4 0 2000 1 OFF 0 5000 1 ON 4 5 6 OFFSET CO C 1 2 3 4 ON ZERO CO DIP CO UB 24V AC DC UB GND Output CO in ppm free Ou...

Page 28: ...28 r 30 50 1 2 3 50 CO2 350 500 1 15 20 CO2 350 500 1 1 2 ZERO CO2 5 AUTO 0 5 600 3 4 10 350 500 1 15 20 7 VOC 1 15 2 ZERO VOC 5 AUTO 0 5 60 3 60 VOC...

Page 29: ...GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND 10 95 SET CO2 10 400 1 600 1900 1 0 2000 1 900 4700 1 0 5000 1 VOC 10 95 23 74 C 10...

Page 30: ...30 r VOC 0 10 4 20 10 95 35 80 C 24 CO2 VOC CO2 VOC ZVEI VDE EMV VDE VDI 0 5 g DIN 43763 S S...