background image

G  

General notes

–  This device may only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element.
– In the operating mode with current output, the device delivers an output current of either 0 ... 20 mA or 4 ... 20 mA (selectable via jumper).  

This device is not a transmitter.

– The voltage output is short-circuit proof. 
–  Applying overvoltage will destroy the device. 
– In case of pollution, we recommend cleaning and recalibration in the factory.
– The air quality signal “good“...“bad“ is represented by the output signal 0 ...10 V.
– The device operating range covers 10 ... 95 % relative humidity respectively 0. .. 50 °C. 

Beyond that range, mismeasurements or increased deviations will occur. 

–  The chemical sensor is a consumable. The lifetime of the sensor depends on nature and concentration of the pollutant gas burden.
– If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
 Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
– These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage 

induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, the TÜV 

and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils 
of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
– Consequential damages caused by a fault in this device are excluded from warranty or liability.
– These devices must be installed by authorised specialists only.
– The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

 Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve- 
ment of our products.

– In case of any modifications made by the user, all warranty claims are forfeited.
– This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat  irradiation by 

similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
– This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury, or as an 

EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
– Modifications of these records are not permitted.
– In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

,  the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Summary of Contents for AERASGARD ALQ-C02

Page 1: ...G Operating Instructions Mounting Installation On wall air quality VOC and CO2 sensors respectively measuring transducers self calibrating with multi range switching and active switching output F Not...

Page 2: ...AERASGARD ALQ CO2 D G F r Ma zeichnung Dimensional drawing Plan cot ALQ CO2 73 40 73 5 17 108 40 20 M16x1 5...

Page 3: ...hsler 24 V Messgenauigkeit Luftg te 20 EW bezogen auf das Kalibriergas Lebensdauer 60 Monate unter Normalbelastung Spannungsversorgung 24 V AC DC KOHLENDIOXID CO2 Sensor CO2 optischer zweistrahliger S...

Page 4: ...Hierbei wird ein Nullpunkt und ein Endwert und somit eine maximale Belastung festgelegt In besonderen F llen kommt es zu einer berschreitung des Messbereiches bzw einer zu hohen Grundbelastung der Ge...

Page 5: ...ng sind nicht zus tzlich aufgef hrt und im Sinne des technischen Fortschritts und der stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew...

Page 6: ...over contact 24 V Measuring accuracy 20 of final value referred to calibrating gas Service life 60 months under normal load conditions CARBON DIOXIDE CO2 CO2 sensor optical dual beam sensor NDIR with...

Page 7: ...s specifications Here a zero point and a final value is determined and thus a maximum burden In particular cases exceeding measuring ranges or excessive basic burdens on the devices will occur outgas...

Page 8: ...om the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improve ment of our products In case of any modifications made by the user a...

Page 9: ...lit d air se r f rant au gaz de calibrage commutation multi gamme s lectionnable via interrupteur DIP sensibilit COV faible moyenne lev e Sortie qualit d air 0 10 V 0 V air propre 10 V air pollu ou av...

Page 10: ...nts de capteurs Lors de l talonnage le point z ro et la valeur de fin d chelle c d la contrainte maximale sont d termin s Dans des cas sp cifiques il est possible que la plage de mesure soit d pass e...

Page 11: ...applicables des diff rences par rapport la pr sentation dans le catalogue ne sont pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produits...

Page 12: ...O2 W ALQ CO2 ALQ CO2 W 1 2 3 4 5 6 7 ALQ CO2 W min max low med high auto 2000 5000 10000 auto 1 2 34 ON 2000 5000 10000 1 2 34 ON 1 2 34 ON low med high 1 2 34 ON ATM Sensor plug Function switch CO2 V...

Page 13: ...4 ON OFF VOC DIP 1 DIP 2 DIP 3 VOC LOW ON OFF OFF VOC MEDIUM OFF ON OFF VOC HIGH OFF OFF ON VOC DIP 4 OFF ON 1 VOC CO2 2x ALQ CO2 ALQ CO2 0 100 0 2000 5000 10000 pp 0 10 ATM 1501 1111 1000 022 ALQ CO2...

Page 14: ...4 20 0 10 10 95 0 50 C ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 3...

Page 15: ...chniques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S...

Page 16: ...AERASGARD ALQ CO2 D G F r...

Reviews: