background image

9

English |

 

Original instructions

ETHANOL FUELS

 

 CAUTION

Do not use E15 or E85 fuel (or fuel containing greater 
than 10% ethanol) in the product. It is a violation of 
federal law and will damage the product and void your 
warranty.

Fuel system damage or performance problems resulting 
from the use of an oxygenated fuel containing more than 
the percentage of oxygenates stated below are not covered 
under warranty.
Ethanol. Gasoline containing up to 10% ethanol by volume 
(commonly referred to as E10) is acceptable. E15 and E85 
are not.

AC OPERATION

 

Ŷ

Unplug all loads from the generator.

 

Ŷ

Switch the AC circuit breakers to the OFF (O) position.

 

Ŷ

Start the engine. Refer to "STARTING THE ENGINE" 
section in this manual.

 

Ŷ

Switch the AC circuit breakers to the ON ( I ) position.

 

Ŷ

Plug in the appliance.

STARTING THE ENGINE

See figures 6-8

 

 CAUTION

On a level surface with the engine off, check the lubricant 
level before each use of the generator.

NOTE:

 If location of generator is not level, the unit may not 

start or may shut down during operation.

 

Ŷ

Turn the fuel valve to the ON position.

 

Ŷ

Move the choke lever to the START position.

NOTE: 

If engine is warm, push the choke lever in to the 

RUN position.

 

Ŷ

Put the engine switch in the ON ( I ) position.

 

Ŷ

Pull the recoil starting grip until the engine runs (a 
maximum of 6 times).

NOTE: 

Do not allow the grip to snap back after starting; 

return it gently to its original place.

 

Ŷ

Allow the engine to run for 30 seconds, then move the 
choke lever in to the RUN position.

STOPPING THE ENGINE

See figures 6-7

To stop the engine under normal operating conditions:

 

Ŷ

Remove any load from the generator.

 

Ŷ

Put the engine switch in the OFF ( O ) position.

 

Ŷ

Turn the fuel valve to the OFF position.

To stop the engine in an emergency situation:

 

Ŷ

Put the engine switch in the OFF ( O ) position.

 

 WARNING

While operating and storing, keep at least 1 m of 
clearance on all sides of the product, including overhead. 
Allow a minimum of 30 minutes of “cool down” time 

EHIRUH VHDW FUHDWHG E\ PXIÀHU DQG H[KDXVW

gases could be hot enough to cause serious burns and /
or ignite combustible objects.

USING THE GENERATOR

Connect devices to be powered by generator by following 
the steps below:

 

Ŷ

Make sure the generator can supply enough continuous 
(running) and surge (starting) watts for the items you 
will power at the same time. See the Electrical section 
for how to calculate total amount of power needed.

 

Ŷ

Start the generator with nothing connected.

 

Ŷ

Plug in and turn on the first load, preferably the largest 
load (highest wattage) you have.

 

Ŷ

Permit the generator output to stabilise (engine runs 
smoothly and attached device operates properly).

 

Ŷ

Plug in and turn on the next load.

 

Ŷ

Again, permit the generator to stabilise.

 

Ŷ

Repeat previous two steps for each additional load.

 

 WARNING

Never add more loads than the generator capacity. 
Take special care to consider surge loads in generator 
capacity.

MOVING THE GENERATOR

See figure 15-17

 

Ŷ

Remove any load from the generator.

 

Ŷ

Turn engine switch OFF ( O ).

 

Ŷ

Close the fuel valve.

 

Ŷ

Make sure the engine and the exhaust of the product 
has cooled down.

 

Ŷ

Unfold the generator frame handle.

 

Ŷ

Facing the side opposite the recoil starter, grasp the 
frame handle firmly.

 

Ŷ

Lift the generator toward you until it balances on the 
wheels.

 

Ŷ

Turn around and pull the product along behind you to 
the desired location.

 

Ŷ

Lower the generator until it sits securely on a flat 
surface.

HIGH ALTITUDE OPERATION

The product is not designed for high-altitude operation 
(altitudes greater than 1,500 m above sea level). Operating 
the product in higher altitudes may increase the engine’s 
emissions, decrease fuel economy and performance and 
reduce the generator life.

Summary of Contents for RGN3600B

Page 1: ...ORIGINAL INSTRUCTIONS Low Power Generating Set RGN3600B...

Page 2: ...Important It is essential that you read the instructions in this manual before assembling operating and maintaining the product Subject to technical modification...

Page 3: ...8 Fuel cap 9 Fuel tank 10 Oil fill hole 11 Oil cap dipstick removed 12 Fuel valve 13 Fuel valve on 14 Fuel valve off 15 Choke lever 16 To start choke closed 17 To run choke open 18 Screw 19 Spark plu...

Page 4: ...Fig 4 Fig 5 Fig 6 11 8 9 6 10 Fig 7 Fig 8 16 15 13 12 17 14...

Page 5: ...Fig 9 7 13 12 14 Fig 10 2 Fig 11 20 19 18 21 Fig 12...

Page 6: ...Fig 13 Fig 15 Fig 16 Fig 17 Fig 14 22 28 26 27 29 24 25 23 30...

Page 7: ...240V AC 240V ON OFF OIL ALERT LAMP 9 1 2 3 4 8 7 6 5 Fig 18 CONTROL PANEL LABEL See figure 18 1 Multimeter 2 Circuit breaker 3 AC receptacle 4 AC receptacle 5 PE Terminal 6 Oil alert lamp 7 Engine sw...

Page 8: ...generator and the transfer switch have been properly installed and the electrical output has been verified by a qualified electrician The connection must isolate the generator power from utility powe...

Page 9: ...rom all types of combustible material Do not touch the muffler or cylinder during or immediately after use they are hot and will cause burn injury Do not connect to a building s electrical system unle...

Page 10: ...ds and as necessary a full face shield when operating this product Failure to use in dry conditions and to observe safe practices can result in electric shock Running the generator gives off carbon mo...

Page 11: ...KHDW IURP WKH PXI HU LJQLWLQJ IXHO YDSRXUV ENGINE LUBRICANT WARNING RX PXVW DGG RLO EHIRUH UVW RSHUDWLQJ WKH JHQHUDWRU Always check the oil level before each operation The oil level should always reg...

Page 12: ...tput of the generator Motor Size HP Running Watts Watts required to start motor Universal Capacitor Split phase 1 8 275 N A 850 1200 1 6 275 600 850 2050 1 4 400 800 1050 2400 1 3 450 950 1350 2700 1...

Page 13: ...s to sequentially add loads as follows 1 With nothing connected to the generator start the engine as described later in this manual 2 Plug in and turn on the first load preferably the largest load hig...

Page 14: ...one end of the box and carefully slide out the generator and any accessories NOTE The generator is heavy If you must lift the product out of the box get another person to help you and lift with your l...

Page 15: ...nt or 2 stroke engine lubricants will damage the engine and should not be used Unscrew the oil cap dipstick and remove Wipe dipstick clean and re seat in hole do not re thread Remove dipstick again an...

Page 16: ...ency situation Put the engine switch in the OFF O position WARNING While operating and storing keep at least 1 m of clearance on all sides of the product including overhead Allow a minimum of 30 minut...

Page 17: ...n serious burns SPARK PLUG MAINTENANCE See figure 11 The spark plug must be properly gapped and free of deposits in order to ensure proper engine operation To check Remove the spark plug cap Clean any...

Page 18: ...e Half Load 13 86 hrs Approvals AS NZS 3010 Yes Euro Emission Yes EMC Yes Uncertainty dB 2 19 Noise level 4 m LpA dB A 70 81 Noise level 7 m LpA dB A 74 Noise level LwA dB A 93 TRANSPORTING Turn engin...

Page 19: ...OFF Turn ON the AC circuit breaker Item plugged in is defective Try a different item Generator makes a spark knock or pinging noise An occasional light knocking or pinging under heavy load is not a ca...

Page 20: ...adjust idle speed Check adjust valve clearance 1 OHDQ IXHO WDQN DQG OWHU 1 Check fuel hose XHO OWHU Inspect Replace Check all hose connections Inspect fuel tank vapor vent if equipped Inspect carbon c...

Page 21: ...WIRING DIAGRAM...

Page 22: ......

Page 23: ......

Page 24: ...ted by Techtronic Industries Australia Pty Ltd 31 Gilby Road Mount Waverley VIC 3149 Melbourne Australia Techtronic Industries N Z Limited 2 Landing Drive Mangere Auckland 2022 New Zealand 09997917700...

Reviews: