www.victorruoshui.co.kr
이 자료는 저작권법에 따라 보호받는 저작물이므로 무단배포 및 무단복제를 금하며, 내용의 전부 또는 일부를 이용하려면, 반드시 한국 VictorRuoshui 社 의 서면동의를 받아야 합니다.
Figure 9
(
6
)
Press
Key to save measurement results (see section six “saving and reading of the measurement
results”)
Note
The readings may not correct when the auxiliary earth resistance is too high. Stick the Auxiliary Earth Spikes
S and H in the moist part of the soil. Ensure that all parts are well connected.
Give enough water where the spikes have to be stuck into the dry, stony or sandy part of the earth so that it
may become moist.
In case of concrete, lay the Auxiliary Earth Spike down and water it, or put a wet cloth etc. on the spike when
making measurements.
The measurement result may be incorrect if interference voltage is higher than 5v, and the noise mark
“
”displays.
When message
or
or
is displayed, it means bad connection of the Test Leads, or warnings for failure