background image

 

 

Relative Temperature 

Relative Humidity 

Long-time Working 

Condition 

Short-time working 

Condition 

Long-time Working 

Condition 

Short-time Working 

Condition 

15ºC to 30ºC 

0ºC to 45ºC 

40%~65% 

5%~95% 

 

The ambient temperature and humidity are measured at a point 1.5 meters (4.9 feet) above the ground and 0.4 

meters (1.3 feet) before the device when there is no protective board in the front or back of the rack. 

 

The short-term working condition refers to a period no longer than consecutive 48 hours or accumulated 15 days a 

year. 

 

 

The extreme working condition refers to the temperature and humidity of the machine room where the air conditioner 

fails for no more than five hours.   

 

2.1.2  Cleanness Requirements 

Dust poses a serious threat to device operation. Dust that falls onto the surface of the device can be absorbed onto metal 

contact points by static electricity, resulting in poor contact. Electrostatic absorption of dust occurs more easily when the 

relative humidity is low, which may shorten the service life of the device and cause communication failures. Table 2-2 

shows the maximum concentration and diameter of dust allowed in the equipment room.   

Table 2-2 

Maximum Diameter (µm) 

0.5 

Maximum Content (Number of 

Particles in one Cubic Meter) 

1.4×10

7

 

7×10

5

 

2.4×10

5

 

1.3×10

5

 

Besides, the contents of salts, acids and sulfides in the air are also strictly limited for the equipment room. These 

substances can accelerate metal corrosion and the aging of some parts. Table 2-3 describes the limit of some hazardous 

gases such as SO

2

, H

2

S, NO

2

 and Cl

in the equipment room. 

Table 2-3 

Gas 

Average (mg/m

3

)   

Maximum (mg/m

3

)   

SO

2

 

0.2   

1.5   

H

2

0.006   

0.03   

NO

2

 

0.04   

0.15   

NH

3

 

0.05   

0.15   

Cl

2

 

0.01   

0.3   

2.1.3  Static Discharge Damage Prevention 

Although much has been done in RG-WS6008 to prevent static electricity, great damage may be caused to the circuitry 

when the static electricity exceeds a certain limit. Electrostatic induction may come from the following sources:   

 

External electric field produced by the high-voltage supply cable, lightning, etc;   

Summary of Contents for RG-WS6008 Series

Page 1: ...RG WS6008 Series Wireless Controller Hardware Installation and Reference Guide V1 0...

Page 2: ...rm or by any means without the prior written consent of Ruijie Networks is prohibited Exemption statement This document is provided as is The contents of this document are subject to change without an...

Page 3: ...ttp www ruijienetworks com service aspx Technical Support Hotline 86 4008 111 000 Related Documents Documents Description Configuration Guide Describes network protocols and related mechanisms that su...

Page 4: ...B ports Interface Standard Ethernet port 10Base T 100Base TX 1000Base TX and 1000BASE SX LX ZX Configuration port Console port RS 232 Dimensions W x D x H 440 mm x 200 mm x 43 6 mm excluding foot pad...

Page 5: ...system sends out an alarm 1 8 Gigabit copper ports link ACT Solid green The copper port is connected at 10 100 1000 Mbps Blinking green The copper port is receiving or transmitting data 1 8 Gigabit co...

Page 6: ...ttery by yourself Instead contact Ruijie Service Center for the replacement of battery This device is an A class product It may cause radio interference in living environment which may require you to...

Page 7: ...st occurs more easily when the relative humidity is low which may shorten the service life of the device and cause communication failures Table 2 2 shows the maximum concentration and diameter of dust...

Page 8: ...tions and high frequency high current devices Use EMI shielding when necessary 2 1 5 Installation Site Requirements To install the wireless controller whether in the cabinet or on the workbench pay at...

Page 9: ...ss controller is ready for installation Mount it to either of these two places A cabinet A workbench 3 2 1 Mounting RG WS6008 in Cabinet RG WS6008 is designed according to the specification of 19 inch...

Page 10: ...ee wire power socket or multi functional microcomputer socket with neutral point connector The neutral point needs to be grounded safely Check whether the power supply in your building is grounded pro...

Page 11: ...sole port of the wireless controller and the other end to the DB 9 male serial adapter of the microcomputer 3 6 Verification When you have installed the wireless controller before powering on it pay a...

Page 12: ...mputer you will need to run a terminal emulation program like Windows operating system s Hyperterm Take Hyperterm for example 1 Run Hyperterm and create a connection 2 Select the serial port to be con...

Page 13: ...r Serial Port After building the configuration environment you may power on the wireless controller 4 2 Powering on Wireless Controller 4 2 1 Verification Before Power on Before powering on the wirele...

Page 14: ...the front panel of the wireless controller are in the proper state See LED Indicators in Chapter 1 If the configuration terminal displays information as expected When the wireless controller is power...

Page 15: ...Starting snooping elf OK Starting postgresql server mnt sata0 pgsql bin postgres not found OK Starting rg mtdoops cli OK Starting sntp elf OK Press RETURN to get started May 15 11 08 01 CAPWAP 4 NO_IP...

Page 16: ...shooting If the system is operational relevant information is displayed on the terminal as described in chapter 4 Otherwise nothing or gibberish is displayed If nothing is displayed please check the f...

Reviews: