Connecting Power
The following shows the proper relay connections.
1
3
2
Figure 5: Failsafe Alarm Relay Wiring
1.
Normally Open
2.
Common
3.
Normally Closed
Section 2.5
Connecting Power
The RUGGEDCOM RSG2300 supports a single or dual redundant AC and/or DC power supplies.
The RUGGEDCOM RSG2300 can be equipped with either a screw-type or pluggable terminal block, which provides
power to both power supplies. The screw-type terminal block is installed using Phillips screws and compression
plates, allowing either bare wire connections or crimped terminal lugs. Use #6 size ring lugs for secure, reliable
connections under severe shock or vibration.
CAUTION!
Electrical hazard – risk of damage to the device. Disconnect the device from the power supply if power
input is above or below the specified input range. For more information, refer to
.
NOTE
• For maximum redundancy in a dual power supply configuration, use two independent power
sources.
• Use minimum #16 gage copper wiring when connecting terminal blocks.
• For 110/230 VAC rated equipment, an appropriately rated AC circuit breaker must be installed.
• For 125/250 VDC rated equipment, an appropriately rated DC circuit breaker must be installed.
• A circuit breaker is not required for 12, 24 or 48 VDC rated power supplies.
• It is recommended to provide a separate circuit breaker for each power supply module.
• Equipment must be installed according to applicable local wiring codes and standards.
CONTENTS
•
Summary of Contents for RuggedSwitch RSG2300
Page 4: ...RUGGEDCOM RSG2300 Installation Guide iv...
Page 10: ...Preface RUGGEDCOM RSG2300 Installation Guide x Customer Support...
Page 16: ...Chapter 1 Introduction RUGGEDCOM RSG2300 Installation Guide 6 Supported Fiber Optic Cables...
Page 28: ...Chapter 2 Installing Device RUGGEDCOM RSG2300 Installation Guide 18 Wiring Examples...