Ruckus ICX 7850 Switch Hardware Installation Guide
63
Part Number: 53-1005580-01
Power Supplies
Inserting a New DC Power Supply
FIGURE 41
Installing an AC Power Supply Unit
1.
If replacing a power supply, remove the previously installed power supply from the appropriate slot by pressing the release lever
and pulling the power supply handle.
2.
If installing a new power supply into a slot covered with a filler panel:
a.
Press the release lever on the filler panel.
b.
Remove the filler panel.
3.
Before opening the package that contains the power supply, touch the bag to the switch casing to discharge any potential static
electricity. Ruckus recommends using an ESD wrist strap during installation.
4.
Remove the power supply from the anti-static shielded bag.
5.
Holding the power supply level, guide it into the carrier rails on each side and gently push it all the way into the slot, ensuring that
it firmly engages with the connector and the release lever clicks into its locked position.
When the Ruckus ICX 7850 switch is powered on, the LEDs on the power supply rear panel should light up green to confirm that the
power supply is correctly installed and supplying power.
Inserting a New DC Power Supply
NOTE
This equipment installation must meet NEC/CEC code requirements. Consult local authorities for regulations.
Use the following steps to install a DC power supply in the Ruckus ICX 7850 switch.
1
Power supply slot
2
Release lever
CAUTION
If you do not install a power supply in a slot, you must keep the slot filler panel in place. If you run the device with an
uncovered slot, the system will overheat.
CAUTION
All devices with DC power supplies are intended for installation in restricted access areas only. A restricted access area is
where access can be gained only by service personnel through the use of a special tool, lock and key, or other means of
security, and is controlled by the authority responsible for the location.