26
9:51
9:51
9:51
9:51
9:51
9:51
9:51
P23
0 V 0
P24
10V 2000
P20
P14
P29
P14
CO2
P14
CO2
1400 PPM
EXT.SENSOR
EXT.SENSOR
AIR QUALITY
P 23 and P 24
These settings can be found in the measuring range of the used measuring transducer. The measu
-
ring range is already preset for devices with integrated CO2 sensor.
Example: Measuring area sensor 0 - 5000 ppm
P 23 = 0
P 24 = 5000
P 20 Air quality
When using external measuring transducers, the maximum air flow rate can be adjusted by para
-
meter P 20.
Example:
Class room
CO²:
Measuring area sensor 0 - 5000 ppm
VOC:
Measuring area sensor 0 - 5000 ppm
Continued on page 32!
SENSORTYPE
W/O EXT.SENSOR
Factory setting
P 14 Sensor type CO2
Volumetric flow, demand controlled by CO2 of the extract air
SENSORTYPE
W/O EXT.SENSOR
SENSORTYPE
SENSORTYPE
Sensor type -CO2-