LED Status:
1)
Good Communication (Solid Green) – Connected to a PROFINET IO Controller and Online.
2)
Not Connected (Flashing Green) – Configured but no PROFINET IO Connection was established.
3)
Fatal Error (Solid Red) –
a.
Invalid Configuration due to no input/output slots configured within the gateway
4)
Connection Timeout (Flashing Red) –
a.
PROFINET IO Controller’s slot configuration doesn’t match the gateway’s slot
configuration
b.
PROFINET IO Controller was communicating to the gateway and is no longer
communicating
5)
No Ethernet cable plugged in (Off)
Variables:
1)
Parameters Read: Rollover counter for the number of parameters read by the IO Controller.
2)
Parameters Written: Rollover counter for the number of parameters written by the IO
Controller.
3)
PN Ethernet Pkts Rcvd: Rollover counter for the number of PROFINET Ethernet packets received.
4)
PN Ethernet Pkts Sent: Rollover counter for the number of PROFINET Ethernet packets sent.
5)
UDP Pkts Rcvd: Rollover counter for the number of PROFINET UDP packets received.
6)
UDP Pkts Sent: Rollover counter for the number of PROFINET UDP packets sent.
7)
OutData Pkts Rcvd: Rollover counter for the number of PROFINET IO cyclic data packets
transmitted and/or received.
8)
Connection Timeouts: Rollover counter for the number of connection timeouts between the
gateway and the IO Controller. If this counter is incrementing, check the Ethernet connection
and verify the gateway is in the IO Controller.