9. OPTIONAL ITEMS - Sold Separately
EASYPROG
10. ANNEXES - Reference Images
Image V
Image X
Image VI
Image VII
Y
X
PANEL
PANEL
LATCHES
CONTROLLER
CONTROLLER
Image VII
CONTROLLER
VINYL
Image IX
Para uma instalação correta e
segura, realize todas as conexões
antes de fixar o controlador.
F41 - Indicação do Display:
Defines wheter the display will show the sensor temperature in real time or a static message on the
display.
[tEMP]
- Displays the sensor temperature in real time
[CooL]
- Does not display the temperature, only the message
[CooL]
on the display
[,USE]
- Does not display the temperature, only the message
[,USE]
on the display
Note:
If this function is configured as
[CooL]
or
[,USE]
it is possible to view the temperature
measured by the sensor at any time with a short touch on the
>
key, where, firstly the message of the
process in progress will be displayed as well as the elapsed time of this process and then the message
[tEMP]
followed by the display of the temperature measured by the sensor, for a few seconds on the
display.
F42 - Functions lockdown:
This allows and configures the functions lockdown.
[,,,0]
- Do not allow the functions lockdown.
[,,,1]
- Allow a partial lockdown where the control functions will be locked but the adjustment of the
setpoint, manual defrost, and maximum and minimum record are allowed.
[,,,2]
- Allow the full lockdown, enabling only the manual defrost and maximum and minimum
record.
F43 -Time for functions lockdown:
Allow lockdown of control functions (see item 7.3.3).
[,,15]
-
[,,60]
Defines the time in seconds for the controller to activate.
F44 - Control functions shutdown:
Allow control functions shutdown (see item 7.3.4).
[no,,]
- Disables the control functions shutdown.
[,,,1]
- Enables activation/deactivation of the control functions only if the functions are unlocked.
[,,,2]
- Enables activation/deactivation of the control functions even if the functions are locked.
8. SINALIZAÇÕES
[Err1]
[Defr][On,,]
[defr][Off,]
Sensor disconnected or damaged.
Manual activation of defrost process.
Manual activation of end of defrost process.
Control functions off.
Contact Full Gauge Controls.
Reconfigure the values of the functions.
[OFF,]
[eCAL]
[pppp]
Low temperature alarm.
[Atlo]
[inib]
[LOC,][On,,]
[LOC,][OFF,]
[AVoL]
[AOPn]
[OpEn]
Power outage alarm indication.
Open door alarm indication.
Open door indication.
Functions lockdown.
Unlocking of functions.
Buzzer inhibited.
[Athi]
[ALrC]
High temperature alarm.
Compressor reached maximum time on limit without reaching SP.
- version 2 or higher
EasyProg
It is an accessory that has as its main function to store the parameters of the controllers. At any time, you
can load new parameters of a controller and unload them on a production line (of the same controller),
for example. It has three types of connections to load or unload the parameters:
- Serial RS-485:
It connects via RS-485 network to the controller (only
for controllers that have RS-485).
- USB:
it can be connected to the computer via the USB port, using
Sitrad's Recipe Editor.
- Serial TTL:
The controller can be connected directly to
EasyProg
by the TTL Serial connection.
Ecase
It is recommended for the Evolution line, keeps water from entering the back part of the instrument. It
also protects the product when the installation site is washed.
Extension Frame
The Full Gauge Controls extension frame allows the installation of Evolution / Ri line with measures
76x34x77 mm (dimensions of the clipping for fixing in the extension frame is 71x29mm) in varied
situations, since it eliminates precision cut to embed the instrument. Allows customization via a sticker with
the brand and the company contact, and accompany two 10A (250 Vac) switches that can trigger internal
light, air curtain, on / off system or fan.
Note:
Ecase is compatible with the use of
small type Faston terminals, usually with
silicone protection.
Electrical noise suppressing filter
Contact suppressor connection
diagram
A1
A2
A1 and A2 are the
contactor coils.
Diagram for suppressor installation
for direct drive load inputs
Load
Suppressor
For direct activation the
maximum specified current
should be taken into
consideration.
RC FILTER
Suppressor
IMPORTANT:
Faston connectors should be
protected with covers, preferably
silicone.