RSG LogiTemp MT-514E FASTON Operation Manual Download Page 4

F06 - Control differential (Hysteresis) (

):

[Rc1,]

It is the difference in temperature (hysteresis) between TURNING ON and OFF the cooling (or heating) 
when recipe (

[rc1,]

) is used.

Example:

 One wants to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the 

cooling is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0).

F07 - Cooling time (interval between defrosts)  (

):

[Rc1,]

Corresponds to the time the controller will act on cooling when preset (

), is used; following this 

[Rc1,]

period, the controller enters the natural defrost process.

F08 - Defrost time (

): 

[Rc1,]

It is the defrost duration time when preset (

) is used. Within this period, the relay will remain off; 

[Rc1,]

following this period, the controller will then return to the cooling state.

F09 - Operation setpoint  (

): 

[Rc2,]

It is the reference value for temperature control, that is, the temperature to be maintained in a controlled 
environment when preset (

) is used.

[Rc2,]

F10 - Control differential (Hysteresis) (

[rc2,]

):

It is the difference in temperature (hysteresis) between TURNING ON and OFF the cooling (or heating) 
when preset

 

(

[rc2,]

) is used.

Example:

 One wants to control the temperature at 4.0 °C with a differential of 1.0 °C. Therefore, the 

cooling is switched off at 4.0 °C and switched back on at 5.0 °C (4.0 + 1.0).

F11

 

- Cooling time (interval between defrosts) (

[rc2,]

):

Corresponds to the time the controller will act on cooling when recipe

 (

[rc2,]

) is used; following this 

period, the controller enters the natural defrost process.

F12

 

- Defrost time (

[rc2,]

):

It is the defrost duration time when preset (

[rc2,]

) is used. Within this period, the relay will remain off; 

at the end of this period, the controller will return to the cooling state.

F13 - Minimum setpoint allowed to the end user:

Avoids regulation of excessively low setpoint temperatures by mistake.

F14 - Maximum setpoint allowed to the end user:

Avoids regulation of excessively high setpoint temperatures by mistake.

F15 - Minimum OUT1 output time on:

It is the minimum time the compressor will remain on, i.e. the time interval between the last start-up and 
the next stop.

F16 - Minimum OUT1 output time off:

It is the minimum time the compressor will remain off, i.e. the time interval between the last stop and the 
next start-up. It is used to relieve the discharge pressure and increase the service life of compressor.

F17 - Initial status when energizing the instrument:

It allows  defrosting when controller is energized such as, for example, upon resuming of electric power 
(in the event of power outage).

[,,,0]

- Cooling

[,,,1]

- Defrost

F18 - Temperature indication locked during defrost:

If 

[,F18]

 is enabled, the indication will only be released at the next cooling cycle after the temperature 

reaches the “locked” value again, or after 15 minutes in cooling (as a safety measure).

F19 - Instrument energization delay:

This function being enabled, when the instrument is energized it only works as temperature indicator 
remaining with the output off during the defined time. In installations with several units of equipment, 
configuring different values for the delay time in the start-up of each instrument, it is possible to avoid 
peaks of demand by activating the loads at different times.
This delay may be of the compressor or of defrost (when defrost is configured at the start).

Note: 

At its end, the count of minimum time of output off is started, if there is any.

F20 - Compressor status with the sensor damaged:

If the sensor is in short-circuited, off or out of the measure range, the compressor assumes the set 
status in this function.

[,,,0]

- Compressor off

[,,,1]

- Compressor on

[,,,2]

- Cycling according to times defined in 

[,F21]

 and 

[,F22]

Note:

 If in the heating mode, and in error, the output will be switched off.

F21 - Compressor time on in case of error:

F22 - Compressor time off in case of error:

These determine the minimum time the compressor will remain on/off, respectively, if the sensor is off or 
out of the measure range.

F23 - Maximum Compressor on without reaching setpoint:

This is the maximum time the compressor may remain on without reaching the setpoint during the 
cooling process for safety reasons. If this time is surpassed, the output is switched off and also the visual 
alarm

 

[ALrC]

 and the audible alarm (buzzer) will be activated. This function can be switched off by 

setting it at the minimum value 0 

[no,,]

.

N

o

te 1:

 In this situation, the controller should be switched off and switched back on so as to continue 

with the operation.

Note 2:

 If the OUT2 output is set up to work differently from the alarm, this will also be switched off for 

safety reasons.

7.5. Parameter table

Access code: 123 (one hundred and twenty three)

Sensor indication offset

Using Recipes

Output operation mode (OUT1)

Output setpoint (rc1)

Output control differential (rc1)

Refrigeration time (rc1)

Defrost time (rc1)

Output setpoint (rc2)

Output control differential (rc2)

Refrigeration time (rc2)

Defrost time (rc2)

Minimum setpoint allowed for end user

Maximum setpoint allowed for end user

Minimum output time OUT1 turned on

Maximum output time OUT1 turned off

Initial state when powering up the instrument

Temperature indication locked during defrost

Delay in powering up the instrument (delay)

Compressor status with sensor disconnected

Time the compressor was on in case of an error

Time the compressor was off in case of an error

Max. Time the compressor was on without reaching

the setpoint

Low temperature alarm

High temperature alarm

Output Operating Mode OUT2

Fan Operation Mode during refrigeration

Fan On Time

Fan Off Time

Fan delay

Delay between compressors being turned on

Alarm inhibition time when turning on the controller

Alarm inhibition time by ambient temperature

Enable Buzzer (0-Disabled / 1-Enabled)

Digital input operation mode

Output time when switched on in OUT2 alarm state

Output time when switched off in OUT2 alarm state

Door open time to trigger alarm

Digital filter operating mode

Intesity of the digital filter applied to the sensors

Display indication

Blocking functions

Time for blocking functions

Shutdown of control functions

 

[,F01]

[,F02]

[,F03]

[,F04]

[,F05]

[,F06]

[,F07]

[,F08]

[,F09]

[,F10]

[,F11]

[,F12]

[,F13]

[,F14]

[,F15]

[,F16]

[,f17]

[,f18]

[,F19]

[,F20]

[,F21]

[,F22]

[,F23]

[,F24]

[,F25]

[,F26]

[,F27]

[,F28]

[,F29]

[,F30]

[,F31]

[,F32]

[,F33]

[,F34]

[,f35]

[,f36]

[,F37]

[,F38]

[,f39]

[,f40]

[,f41]

[,f42]

[,F43]

[,F44]

Description

Fun

Min

Max Unit

CELSIUS

FAHRENHEIT

Min

Max Unit Stand.

Stand.

-

-20,0

no

0-cool.

-50,0

0,1

1

0(no)

-50,0

0.1

1

0(no)

-50,0

-50,0

0(no)

0(no)

0-cool.

no

0(no)

0

1

1

0(no)

-50(no)

-50(no)

1

0

1

1

0(no)

0(no)

0(no)

0(no)

0(off)

0(no)

0

0

0(no)

0

0(no)

0

0

15

0(no)

-

-4

no

0-cool.

-58

1

1

0(no)

-58

1

1

0(no)

-58

-58

0(no)

0(no)

0-cool.

no

0(no)

0

1

1

0(no)

-58

-58

1

0

1

1

0(no)

0(no)

0(no)

0(no)

0(off)

0(no)

0

0

0(no)

0

0(no)

0

0

15

0(no)

-

20,0

yes

1-heat.

200,0

20,0

9999

999

200,0

20

9999

999

200,0

200,0

999

999

1-defr.

yes

240

2

999

999

9999

200,0

200,0

7

2

99

99

999

99

999

999

1

8

999

999

999

1

20

2

2

60

2

-

68

yes

1-heat.

392

36

9999

999

392

36

9999

999

392

392

999

999

1-defr.

yes

240

2

999

999

9999

392

392

7

2

99

99

999

99

999

999

1

8

999

999

999

1

20

2

2

60

2

-

°C

-

-

°C

°C

min.

min.

°C

°C

min.

min.

°C

°C

sec.

sec.

-

-

min.

-

min.

min.

min.

°C

°C

-

-

min.

min.

min.

seg.

min.

min.

-

-

sec.

sec.

min.

-

sec.

-

-

sec.

-

-

°F

-

-

°F

°F

min.

min.

°F

°F

min.

min.

°F

°F

sec.

sec.

-

-

min.

-

min.

min.

min.

°F

°F

-

-

min.

min.

min.

sec.

min.

min.

-

-

sec.

sec.

min.

-

sec.

-

-

sec.

-

-

0,0

no

0-cool.

4,0

1,0

240

30

0,0

1

240

30

-50,0

75,0

20

20

0-cool.

no

0(no)

0

15

15

0(no)

-50(no)

200(no)

1

0

2

2

2

15

0(no)

0(no)

0(off)

0(no)

1

1

0(no)

0

0(no)

0

0

15

0(no)

-

32

no

0-cool.

39

1

240

30

32

1

240

30

-58

167

20

20

0-cool.

no

0(no)

0

15

15

0(no)

-58

392

1

0

2

2

2

15

0(no)

0(no)

0(off)

0(no)

1

1

0(no)

0

0(no)

0

0

15

0(no)

F01 - Access code 123 (one hundred and twenty-three):

This is required when intending to change the configuration parameters. Entering of this code is not 
required if the intention is just visualizing the parameters adjusted. 
It allows entering of the expected access codes:

[,123]

- Allows access for changing the table parameters.

[,231]

- Allows configuring of the unit of measurement 

[,=f,]

 or 

[,=C,]

[,231]

- To select the unit in which the instrument will operate enter the function

[,F01]

 using the 

access code

[,231]

then press the

/

key. Then, select the unit desired 

[,=C,]

 or

[,=F,]

using 

the

< >

keys; to confirm press 

/

or

Note:

 Every time the unit is changed, the parameters should be reset, since they assume the ‘standard’ 

values of the parameter’s table.

F02 - Sensor indication displacement (offset):

Allows compensation for any temperature deviations from sensor replacement or change in the cable 
length.

F03 - Using Presets:

Allows configuration of the controller so as whether or not to use the presets:

[no,,]

- No:

 If configured this way, the instrument will not use the preset values in the control routines. 

For this purpose, the setpoint

[SP,,]

 will be used, adjusted via the quick access menu. The control 

differential to be used shall be the same as in preset

 [rc1,]

,

 [,F06] 

“OUT1 output control 

differential (

[rc1,]

)”. The cooling time to be used shall be the same as in preset 

[rc1,]

[,F07]

 

“OUT1  output  cooling  time  (

[rc1,]

)”.  Defrost  time  to  be  used  will  be  the  same  as  in  preset  1,

 

[,F08]

 “OUT1 output defrost time (

[rc1,]

)”.

The value configured in 

[SP,,]

 may be adjusted between 

[,F13]

 “Minimum setpoint allowed to the 

end user” and 

[,F14]

 “Maximum setpoint allowed to the end user”.

In this configuration, the controller will not indicate which preset is enabled.

[yEs,]

- Yes:

 Selection of presets will be made through the quick access menu, in the same way as for 

adjusting the setpoint. In this configuration, the controller will indicate in the display which preset is 
enabled, 

[rc1,]

 or 

[rc2,]

. If configured this way, in the control routines the instrument will use the 

values of setpoint, control differential, cooling time and defrost time configured in the parameters table.

F04 - Output operating mode OUT1:

Selects the out1 output operating mode:

[,,,0]

- Cooling

[,,,1]

- Heating

F05 - Operation setpoint (

): 

[Rc1,]

It is the reference value for temperature control, that is, the temperature to be maintained in a controlled 
environment when preset (

[rc1,]

) is used.

7.5.1. Description of parameters

Temperature [°C]

Setpoint

Cooling

Se Hysteresis

Time [S]

Relay Off

Relay On

4°C

5°C

Temperature [°C]

Setpoint

Heating

Setpoint - Hysteresis

Time [S]

4°C

5°C

Relay Off

Relay On

Summary of Contents for LogiTemp MT-514E FASTON

Page 1: ...LogiTemp Electronic Controller System Operations Manual Full Gauge Version MT514 PN 171571 REV 3 22 ...

Page 2: ...bles can be increased by user himself to up to 200 meters using a PP2x24 AWGcable 5 3 Recommendations of IEC60364 standard a Installoverloadprotectorsinthecontrollersupply b Install transient suppressors suppressor filter RC in the circuit to increase the service life of the controllerrelay Seeconnectioninstructionsofthefilteronthepreviouspage c The sensor cables may be together but not in the sam...

Page 3: ...ck touch maximum and minimum temperature display Hold down for 2 seconds inhibit audible alarm buzzer Pressed for 5 seconds turn on turn off the control functions Vinylprotector ImageIX item13 Protects the controller should when installed in a place with splashing water such as in refrigerated counters Thisadhesivevinylaccompaniestheinstrument onthepackaging IMPORTANT Applyonlyaftercompletingelect...

Page 4: ...state when powering up the instrument Temperature indication locked during defrost Delay in powering up the instrument delay Compressor status with sensor disconnected Time the compressor was on in case of an error Time the compressor was off in case of an error Max Time the compressor was on without reaching the setpoint Low temperature alarm High temperature alarm Output Operating Mode OUT2 Fan ...

Page 5: ... if configured as auxiliary compressor F26 7 Every time the OUT1 output is activated the time configured in this function will elapse beforeactivatingtheOUT2output F32 Alarminhibitiontimewhenenergizingthecontroller This is the time during which the alarm remains off even under conditions of alarm during the instrument start up This time will be counted after elapsing of the time configured in F19 ...

Page 6: ...of end of defrost process Control functions off Contact Full Gauge Controls Reconfigure the values of the functions OFF eCAL pppp Low temperature alarm Atlo inib LOC On LOC OFF AVoL AOPn OpEn Power outage alarm indication Open door alarm indication Open door indication Functions lockdown Unlocking of functions Buzzer inhibited Athi ALrC High temperature alarm Compressor reached maximum time on lim...

Page 7: ...t covered either natural wear and tear of parts external damage caused by falls or inadequate packaging of products LOSS OF WARRANTY Products will automatically lose its warranty in the following cases The instructions for assembly and use found in the technical description and installation procedures in Standard IEC60364 are not obeyed The product is submitted to conditions beyond the limits spec...

Page 8: ... U Hudson WI 54016 800 955 5253 Norlake Foodservice Sales 800 477 5253 Norlake Scientific Sales 800 388 5253 Norlake Parts Service 800 647 1284 Master Bilt Sales 800 684 8988 Master Bilt Parts Service Email rsgservice refsg com PN 171571 REV 3 22 ...

Reviews: