RSG LogiTemp MT-514E FASTON Operation Manual Download Page 2

DIGITAL CONTROLLER FOR HEATING OR COOLING

WITH DEFROST AND CONFIGURABLE

ALARM OUTPUT

MT514EF

AST

ONV03-01T

-18525

 4. INDICAÇÕES E TECLAS

 1. DESCRIPTION

The 

MT-514

e

 FASTON

 

is a temperature controller for cooling or heating applications. It has an 

internal audible alarm (buzzer) and an output for alarm control that can also be configured for electric 
defrost, hot gas defrost, fan or as a second compressor that will act in parallel with the main one. The 
minimum and maximum temperature record is displayed at the touch of a single key  (Flatec). Another 

;

available  feature  is  the  shutdown  of  control  functions,  making  it  possible  for  the

  MT-514

e

 

FASTON

 

to operate only as a temperature indicator. And through an intelligent function blocking 

system, it prevents unauthorized persons from changing the control parameters.
Product is compliant with UL Inc. (United States and Canada).
 

 2. APPLICATION

• Vaccine refrigerators
• Refrigerated counters
• Freezers rooms
• Hot counters
• Greenhouses

evolution

 

 

MT-514

e

 FASTON

Ver

.03

WARNING

ACESSÓRIOS:

Utilize apenas acessórios originais Full Gauge Controls. 
Em caso de dúvidas, entre em contato com o suporte técnico.

SERVIÇO AUTORIZADO:

A instalação ou manutenção do produto deve ser realizado somente por profissionais qualificados;

MT-514

e

MT-514

e

Image I

1

5 6

2 3 4

7

POWER
SUPPLY

SENSOR

8

9

10 11 12 13 14

RE

FR

115 Vac

Alimentação da carga

CO

MM

ON

D1

CO

MM

ON

NO

NC

3. TECHNICAL SPECIFICATIONS

* Blinking led (when 

[,F26]

 = 7): Indicates that OUT1 has been activated and the compressor delay is occurring 

before trigger OUT2

POR ESTAR EM CONSTANTE EVOLUÇÃO, A FULL GAUGE CONTROLS RESERVA-SE O DIREITO DE 

ALTERAR AS INFORMAÇÕES CONTIDAS NO MANUAL A QUALQUER MOMENTO, SEM PRÉVIO AVISO.

BEFORE  INSTALLING  THE  CONTROLLER,  WE  RECOMMEND  READING  THROUGH  THE 

ENTIRE  INSTRUCTION  MANUAL  IN  ORDER  TO  AVOID  POSSIBLE  DAMAGE  TO  THE 

PRODUCT

PRECAUTIONS WHEN INSTALLING THE PRODUCT:

Before performing any procedure on this instrument, disconnect it from the mains;
Ensure  that  the  instrument  has  adequate  ventilation  and  avoid  installation  in  panels  containing 
devices that may cause it to operate outside the specified temperature limits;
Install the product away from sources that may generate electromagnetic disturbances such as: 
motors, contactors, relays, solenoid valves, etc;   

Have this manual in the palm of 

your hand by 

FG Finder 

application.

1

5 6

2 3 4

7

POWER
SUPPLY

SENSOR

8

9

10 11 12 13 14

RE

FR

230 Vac

Power supply

CO

MM

ON

D1

CO

MM

ON

NO

NC

1

5 6

2 3 4

7

POWER
SUPPLY

SENSOR

8

9

10 11 12 13 14

RE

FR

12Vac/dc

Power supply

CO

MM

ON

D1

CO

MM

ON

NO

NC

0

1

5 6

2 3 4

7

POWER
SUPPLY

SENSOR

8

9

10 11 12 13 14

RE

FR

24Vac/dc

Power supply

CO

MM

ON

D1

CO

MM

ON

NO

NC

0

 5. WIRING DIAGRAM

5.1. Identifications (see Images I to IV)

- Image I: 

MT-512E 2HP Faston, supplied at 115 Vac. 

- Image II:

 MT-512E 2HP Faston, supplied at 230 Vac. 

- Image III:

 MT-512EL 2HP Faston, supplied at 12 Vac/dc. 

- Image IV:

 MT-512EL 2HP Faston, supplied at 24 Vac/dc.

Image II

Image III

Image IV

5.2. Temperature sensor connection

 

- Connect the 

sensor S1

 wires to terminals "1 and 2" spring type connector. The polarity is not relevant.

- Length of the sensor cables can be increased by user himself to up to 200 meters, using a PP 2x24 
AWG cable.

5.3. Recommendations of IEC60364 standard

a) 

Install overload protectors in the controller supply.

b)

 Install transient suppressors – suppressor filter RC – in the circuit to increase the service life of the 

controller relay. See connection instructions of the filter on the previous page.

c) 

The sensor cables may be together, but not in the same conduit where the power supply of the 

controller and/or of the loads passes through.

 6. FIXING PROCEDURE 

a)

  Cutout  the  panel  plate  (Image  V  -  item  13)  where  the  controller  will  be  fixed,  with  dimensions              

X = 71±0,5 mm and Y = 29±0,5 mm;

b)

 Remove the side locks (Image VI - item 13): To do this, squeeze the elliptical central part (with the 

Logo Full Gauge Controls) and move the latches back;

c)

 Pass the wires through the cutout of the plate (image VII - Item 13) and make the electrical installation 

as described in item 6;

d)

 Insert the controller into the panel cutout, from the outside in;

e)

 Replace the latches and push then until they are pressed against the panel, securing  the controller to 

the housing (see arrow in Figure VI - item 13);

f)

 Adjust the parameters as described in item 9.

      WARNING:

 

for installations requiring liquid-tight sealing, the cut-off for the installation of the 

controller should be at must 70.5x29mm. The side latches must be secured so that they press 

the rubber sealing to prevent infiltration between the cutout and the controller.

NEW CONNECTION SYSTEM (QUICK COUPLING):

FASTON and PUSH-IN FAST

CONNECTION:

- Hold the wire near its end and insert it into the 
desired slot.
-  If  necessary,  press  the  bottom  to  assist  the 
connection.

DISCONNECT:

- To disconnect the cord, press the bottom and 
remove it.

NOTE:

- In the Push-In connectors the maximum wire 
gauge that can be used is 1.5mm².
- The wires must be tinned or use Rocket Pin 
terminals with a maximum gauge of 0.75mm².

BOTTOM

WIRE INPUT

The wire should be picked
in  5  mm  and  tinned.

Terminal Rocket Pin.

Control

functions 

shutdown

Function

blocking

Serial

Programming

Defrost

Protection

level

IP 65

FRONT

Audible 

Alarm

Connector

for quick 
coupling

E251415

VE

NT

/

CO

MP

AU

X

VE

NT

/

CO

MP

AU

X

VE

NT

/

CO

MP

AU

X

VE

NT

/

CO

MP

AU

X

AL

AR

M/

DE

FR

AL

AR

M/

DE

FR

AL

AR

M/

DE

FR

AL

AR

M/

DE

FR

(*) 

This instrument measures and controls temperatures of up to 200°C/392°F, using the silicone sensor cable SB59 

(sold separately).

Note:

 

The sensor cable lenght can be increased by the user up to 200 meters using PP 2 x 24 AWG cable.

Control temperature

 

 -50 to 105ºC (-58 to 221°F)*

Power supply

MT-514 E Faston: 

115 or 230 Vac ±10%(50/60 Hz) 

MT-514 EL Faston:

 12 or 24 Vac/dc +10%  

Operating temperature

 

0 to 50 ºC / 32 to 122°F 

Operating humidity

10 to 90%RH (without condensation)

Dimensions (mm)

76 x 34 x 84 mm (WxHxD)

Load current (outputs)

 OUT1:

 16(12)A 250Vac 2HP

 OUT2:

 10A / 240Vac 1/4HP 

Dimensions of the clipping for fixing

of the instrument

71 ± 0,5 x 29 ± 0,5 mm (see item 5)

MT-514

e

Set key

Quick Access

Menu Key (Flatec)

Functions lock indication LED

Temperature unit indication LED

Increase key

Decrease key

Alarm indication LED

*Cooling indication LED 

Heating indication LED 

Defrost indication LED

FOR INSTALLATIONS WHERE A SEALING IS REQUIRED TO AVOID LIQUID CONTACT, THE CUT FOR THE 
CONTROLLER MUST BE OF 70,5X29mm MAXIMUM. THE SIDE LOCKS MUST BE FIXED SO IT PRESSES THE 
RUBBER SEALING AVOIDING INFILTRATION BETWEEN THE CUT AND THE CONTROLLER.

ATTENTION

Summary of Contents for LogiTemp MT-514E FASTON

Page 1: ...LogiTemp Electronic Controller System Operations Manual Full Gauge Version MT514 PN 171571 REV 3 22 ...

Page 2: ...bles can be increased by user himself to up to 200 meters using a PP2x24 AWGcable 5 3 Recommendations of IEC60364 standard a Installoverloadprotectorsinthecontrollersupply b Install transient suppressors suppressor filter RC in the circuit to increase the service life of the controllerrelay Seeconnectioninstructionsofthefilteronthepreviouspage c The sensor cables may be together but not in the sam...

Page 3: ...ck touch maximum and minimum temperature display Hold down for 2 seconds inhibit audible alarm buzzer Pressed for 5 seconds turn on turn off the control functions Vinylprotector ImageIX item13 Protects the controller should when installed in a place with splashing water such as in refrigerated counters Thisadhesivevinylaccompaniestheinstrument onthepackaging IMPORTANT Applyonlyaftercompletingelect...

Page 4: ...state when powering up the instrument Temperature indication locked during defrost Delay in powering up the instrument delay Compressor status with sensor disconnected Time the compressor was on in case of an error Time the compressor was off in case of an error Max Time the compressor was on without reaching the setpoint Low temperature alarm High temperature alarm Output Operating Mode OUT2 Fan ...

Page 5: ... if configured as auxiliary compressor F26 7 Every time the OUT1 output is activated the time configured in this function will elapse beforeactivatingtheOUT2output F32 Alarminhibitiontimewhenenergizingthecontroller This is the time during which the alarm remains off even under conditions of alarm during the instrument start up This time will be counted after elapsing of the time configured in F19 ...

Page 6: ...of end of defrost process Control functions off Contact Full Gauge Controls Reconfigure the values of the functions OFF eCAL pppp Low temperature alarm Atlo inib LOC On LOC OFF AVoL AOPn OpEn Power outage alarm indication Open door alarm indication Open door indication Functions lockdown Unlocking of functions Buzzer inhibited Athi ALrC High temperature alarm Compressor reached maximum time on lim...

Page 7: ...t covered either natural wear and tear of parts external damage caused by falls or inadequate packaging of products LOSS OF WARRANTY Products will automatically lose its warranty in the following cases The instructions for assembly and use found in the technical description and installation procedures in Standard IEC60364 are not obeyed The product is submitted to conditions beyond the limits spec...

Page 8: ... U Hudson WI 54016 800 955 5253 Norlake Foodservice Sales 800 477 5253 Norlake Scientific Sales 800 388 5253 Norlake Parts Service 800 647 1284 Master Bilt Sales 800 684 8988 Master Bilt Parts Service Email rsgservice refsg com PN 171571 REV 3 22 ...

Reviews: