2
V8514
A
L
N
G
B
C
C
D
E
F
N
L1
L2
S1
N
L1
L2
B
A. Maximum 10 units
B. Gear tray
C. Remove link
D. Maintained
E. Non-maintained
F. Fused spur with 1A fuse
G. Mains supply
A. Maximal 10 Notleuchten
B. Bauteileträger
C. Brücke entfernen
D. Dauerschaltung
E. Bereitschaftsschaltung
F. Mit 1 Ampere abgesicherte
Stichleitung
G. Netzversorgung
A. 10 unidades como máximo
B. Placa de cierre de la caja
C. Eliminación del enlace
D. Permanente
E. No permanente
F. Derivación con fusible
de 1 A
G. Fuente de alimentación
de red
A. 10 unités maximum
B. Plaque de montage
C. Enlevez la barrette
D. Maintenu
E. Non maintenu
F. Dérivation avec fusible 1 A
G. Secteur
A. Maksimum 10 enheder
B. Indmad
C. Fjern lus
D. Tilsluttet
E. Ikke tilsluttet
F. Sikret stikledning med 1A
sikring
G. Netforsyning
A. Maximaal 10 armaturen
B. Bak
C. Verwijder de doorverbinding
D. Continu
E. Niet continu
F. Gezekerde aansluiting met
1A-zekering
G. Netvoeding
A. Högst 10 enheter
B. Armaturinsats
C. Ta bort förbindelsen
D. Nät- och nödbelysning
E. Enbart nödbelysning
F. Extra fasledare med 1 A
säkring
G. Nätspänning
SE
NL
DK
6W Black Base Fluorescent Non-Maintained
565-816
6W Black Base Fluorescent Maintained
566-746
6W White Base Fluorescent Non-Maintained
236-243
6W White Base Fluorescent Maintained
236-259
Important:
PLEASE READ INSTRUCTION LEAFLET BEFORE COMMENCING
INSTALLATION.
Installers are reminded of the British Standard Code of Practice for The
Emergency Lighting of Premises BS5266 Part 1 to which all
installations should comply.
The battery is permanently connected to the printed circuit board which
may be live even though the mains is not connected and the lamps are
not operating. DO NOT TOUCH COMPONENTS OR TUBE LEADS.
CAUTION:
Some components may be too hot to touch immediately
after the mains supply has been switched off.
Installation
Separate diffuser from body by gently pulling apart and remove the
four screws retaining gear tray.
Discard any internal packaging pieces in the base. The body may be
fixed to ceiling or wall by screws through the BESA group of holes
provided. Do not mount directly above a heat source.
Mains cables from the 240V 50Hz supply may be brought in through a
central 20mm hole in the base of the body.
Supply connections
The fitting must be connected to a permanent uninterrupted
supply.
Connect the mains supply to the terminal block on the gear tray
moulding as follows: (The live terminal will be marked L1 or L2
according to the model).
Terminal size
2.5mm
2
Brown or Live
L1 or L2
Blue or Neutral
N
The luminaire is double insulated and does not itself require an earth
connection.
RS
Stock No.
Bank remote switching / Fernumschaltung mehrerer Notleuchten gleichzeitig /
Encendido remoto por banco de contactos / Déclenchement multiple à distance /
Samlet fjernomkobling / Schakelen op afstand van groepen / Fjärrmanövrering av flera enheter
2