Smart Positioner
YT-3100
Product Manual
Ver. 1.19
60
9.12.3
Reset Alarm Status (RST ALRM oFF / on)
The alarm is automatically released when the cause of the alarm is removed. For example, if a high-
temperature alarm is created, the alarm is automatically released when internal temperature drops
below the Temperature High Limit. However, if the Partial Stroke Test fails or Auto Calibration fails, use
this function to release the alarm.
Below is an alarm list that can be released using the RST ALRM function.
1)
Auto Calibration Running
2)
Diagnosis Running
3)
Critical NVM Fail
4)
Non-Critical NVM Fail
5)
PST Fail
6)
Auto Calibration Fail
3 seconds
→
→
3 seconds
→
Press <UP> or
<DOWN> button
if the above is not
displayed.
Press <UP> or
<DOWN> button
if the above is not
displayed.
<UP>/<DOWN>
→
<ESC>
→
<ESC>
3 times
→